background image

18

Unitary Products Group

CAUTION:

Combustion air adjustments

must be made only by a qualified technician.

Improper air adjustment may cause unsafe op-

eration, explosion or asphyxiation.

To adjust the combustion air:
1. To light and operate furnace see label inside lower

furnace door.

2. Allow the burner to burn for about 1 MINUTE.
3. Look through the observation window and observe

the appearance of the flame.

4. On natural gas, the base of the flame should be blue

but the tips of the flame will be yellow. (See Figure

19.)

5. On Propane gas, almost all of the flame will be yellow

although some blue should still be present at the

base of the flame next to the end of the burner. (See

Figure 20.)

6. If the flame is too yellow, the combustion air should

be increased. If the flame is excessively blue (no yel-

low) the combustion air should be decreased.

7. To adjust the combustion air, loosen the lock screw

holding the combustion air rod in place. Push in on

the rod to increase the combustion air. Pull out on the

combustion air rod to decrease the combustion air.

Tighten lock screw after adjustment is made. Do not

completely close air damper at any time. Complete

closure of air damper to burner will result in improper

operation. See caution above.

View of Burner Through the Observation Window

LIGHT BLUE

WITH YELLOW TIPS

DARK BLUE

BLUE TIPS JUST STARTING

TO BECOME PRONOUNCED.

YELLOW WITH

ORANGE TIPS

LIGHT BLUE

NO BLUE TIPS

EXTENDING

FROM THE END

OF THE BURNER

DARK BLUE

DARK BLUE

LONG AND EXTREMELY

PRONOUNCED BLUE TIPS

EXTENDING FROM THE

END OF THE BURNER

WHTISH YELLOW TO

LIGHT YELLOW

LIGHT BLUE

BLUE TIPS JUST STARTING

TO BECOME PRONOUNCED

DARK YELLOW TO

ORANGISH YELLOW

MAIN FLAME IS A

WHITISH YELLOW

REFLECTIVE COLOR.

VERY LITTLE BLUE

EXTENDING FROM

THE END OF THE

BURNER.

WHITISH YELLOW

LIGHT BLUE

LONG AND EXTREMELY

PRONOUNCED BLUE TIPS

EXTENDING FROM THE

END OF THE BURNER

CORRECT AMOUNT OF

PRIMARY AIR

TOO LITTLE PRIMARY AIR

PUSH SHUTTER ROD IN

TOO MUCH PRIMARY AIR

PULL SHUTTER ROD OUT

CORRECT AMOUNT OF

PRIMARY AIR

TOO LITTLE PRIMARY AIR

PUSH SHUTTER ROD IN

TOO MUCH PRIMARY AIR

PULL SHUTTER ROD OUT

FIGURE 20 --

PROPANE GAS FLAME APPEARANCE

FIGURE 19 --

NATURAL GAS FLAME APPEARANCE

View of Burner Through the Observation Window

If Furnace Fails to Operate Properly

1. Check setting of thermostat -- and position of HEAT/

COOL switch if air conditioning is installed. If a set--

back type thermostat is employed be sure that the

thermostat is in the correct operating mode.

2. Check to see that electrical power is ON.
3. Check to see that the knob on the gas control valve

is in the full ON position.

4. Make sure filters are clean, return grilles are not ob-

structed, and supply registers are open.

5. Be sure that furnace flue piping is open and unob-

structed.

If the cause for the failure to operate is not obvious, do

not attempt to service the furnace yourself. Call a quali-

fied service agency or your gas supplier.

Summary of Contents for DLAS

Page 1: ...ation adjustment service or maintenance can cause injury or property dam age Please refer to all the instructions of this manual for proper installation procedures Im proper installation will void the...

Page 2: ...nace Doors 19 Finish and Trim 19 Furnace and Air Conditioner Installations 19 HIGH ALTITUDE DERATION CHART 20 Natural Gas 20 Propane Gas 20 REPAIR PARTS 21 22 LIST OF FIGURES FIGURE 1 Furnace Dimensio...

Page 3: ...0BDF NATURAL GAS 70 000 57 000 DGAT075BDF NATURAL GAS 75 000 61 000 DGAT090BDF NATURAL GAS 90 000 72 000 DLAS Automatic Ignition Heating Only No Coil Cabinet Model No Factory Equipped for use with Inp...

Page 4: ...nt CSA stan dard CAN CGA Z240 4 2 Installation Require ments for Propane Appliances and Equipment in Recreational Vehicles 2 Unit electrical wiring and grounding shall complywith current CSA standard...

Page 5: ...cation of 200 or less 6 Non combustible pans having one inch upturned flanges are located beneath openings in the floor re turn duct system 7 Wiring materials located in the return duct system conform...

Page 6: ...er grill an undercut of 2 1 2 will provide 50 Sq In of free area 1 The closet door MUST have a minimum of 250 Square In ches of free area in the upper half of the door and a mini mum of 50 Square Inch...

Page 7: ...installed on a new home do the following 1 Inspect the furnace top collars for signs of insulation or ceiling debris which might have fallen in during cutting of the ceiling and roof holes Remove all...

Page 8: ...ITCH SLANT FLASHING 3 12 PITCH DLAS COAS Furnaces DGAT DGAM COAT CGAT Furnace Installation Dimensions Installation Dimensions A Adjustable Height B Adjustable Height 4000 7101 C 4000 7121 C 4000 7141...

Page 9: ...DGAT DGAM COAT CGAT Furnace Installation Dimensions Installation Dimensions A Adjustable Height B Adjustable Height 4000 8101 C 4000 8181 C 4000 9161 A 4000 9181 A 85 to 101 99 to 129 101 to 117 115 t...

Page 10: ...he furnace may be installed on combustible flooring without a separate sub base DUCT CONNECTOR DIMENSIONS DUCT CONNECTOR DIMENSIONS DUCT CONNECTORS FOR SCREW ATTACHMENT DUCT CONNECTORS FOR TAB ATTACHM...

Page 11: ...0 715 and U L standard 181 INSTALLATION OF TAB ATTACHMENT DUCT CONNECTORS 1 Make floor cut out as shown in figure 8 2 Determine the depth of the floor cavity from the sur face of the floor to the top...

Page 12: ...w hole is provided in the pipe and collar Excessively long screws may extend to flue pipe and puncture it Screws are not to exceed 1 1 2 in length NOTE Combustion air tube and flue pipe are part of th...

Page 13: ...n the left side of the furnace See Figure 14 If conduit is used it should be secured to the control box 3 Connect the hot wire to the BLACK pigtail lead and the neutral wire to the WHITE pigtail lead...

Page 14: ...bove the floor The preferred location is on an inside wall situated in an area with good air circulation and where the temperature will be reasonably representative of other living areas the thermosta...

Page 15: ...itch To Earth Ground Neutral L1 115 VAC To A C Condensing Unit If equipped Incoming Power Must Be Polarized Observe Color Coding NEUTRALS Ground Screw HEAT COOL L1 XFMR COM 24 VAC RED BLK BRN WHT WHT...

Page 16: ...Earth Ground Neutral L1 115 VAC To A C Condensing Unit If equipped Incoming Power Must Be Polarized Observe Color Coding NEUTRALS Ground Screw HEAT COOL L1 XFMR COM 24 VAC RED BLK WHT WHT BLK BLU RED...

Page 17: ...r is then reduced to 10 W C IMPORTANT When converting valve from or to Pro pane gas it will be necessary to change main burner ori fice to prevent an underfired or overfired condition See label inside...

Page 18: ...PRONOUNCED YELLOW WITH ORANGE TIPS LIGHT BLUE NO BLUE TIPS EXTENDING FROM THE END OF THE BURNER DARK BLUE DARK BLUE LONG AND EXTREMELY PRONOUNCED BLUE TIPS EXTENDING FROM THE END OF THE BURNER WHTISH...

Page 19: ...e and air condi tioner form operating at the same time This interlock system usually contains a heat cool switch which must be turned to either HEAT or COOL to activate either heating or cooling opera...

Page 20: ...0 128 30 9951 1281 0 136 29 9951 1361 0 152 24 9951 1521 PROPANE GAS 56 000 Input 70 000 Input 75 000 Input 90 000 Input Elevation Orifice Dia Drill Size Part Orifice Dia Drill Size Part Orifice Dia D...

Page 21: ...flow Furnace Repair Parts List for DGAM056BDF DLAS056BDF DGAM075BDF DLAS075BDF Repair Parts List for DGAT056BDF DGAT070BDF DGAT075BDF DGAT090BDF 13 26 27 28 15 14 14 30 34 35 33 32 31 29 22 21 16 23 2...

Page 22: ...EN 145 CLOSE 115 Limit Switch OPEN 150_ CLOSE 120_ 21 All 7970 5851 A Burner Assembly Less Gas Valve 22 All 1474 0521 Hot Surface Ignitor 23 All 7970 179 Ignitor Shield 24 All 7945 1631 A Mounting Pla...

Page 23: ...23 Unitary Products Group...

Page 24: ...ary Products Group Subject to change without notice Printed in U S A Copyright E by Unitary Products Group 1999 All rights reserved 1973 106 F Rev 2 599 5005 York Drive Unitary Products Group Norman O...

Reviews: