TABLE 5 - SUPPLY AIR BLOWER PERFORMANCE (7-1/2 & 10 TON)

BLOWER

SPEED,

RPM

CFM

2250

2550

3000

3400

3750

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

975

0.93

1.16

1.08

0.79

1.27

1.18

0.53

1.45

1.35

0.29

1.65

1.54

-

-

-

1025

1.08

1.21

1.13

0.95

1.34

1.25

0.68

1.54

1.44

0.42

1.75

1.63

0.17

1.97

1.84

1070

1.22

1.32

1.23

1.08

1.46

1.36

0.83

1.68

1.57

0.58

1.89

1.76

0.32

2.11

1.97

1130

1.41

1.43

1.33

1.29

1.57

1.46

1.02

1.83

1.71

0.77

2.04

1.90

-

-

-

1175

1.61

1.51

1.41

1.49

1.67

1.56

1.23

1.92

1.79

0.96

2.18

2.03

-

-

-

1220

1.78

1.66

1.55

1.66

1.81

1.69

1.39

2.10

1.96

-

-

-

-

-

-

MODEL BCB090 - (SIDE DUCT APPLICATIONS)

BLOWER

SPEED,

RPM

CFM

2250

2550

3000

3400

3750

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

975

0.86

1.16

1.08

0.70

1.27

1.18

0.40

1.45

1.35

0.12

1.65

1.54

-

-

-

1025

1.01

1.21

1.13

0.86

1.34

1.25

0.55

1.54

1.44

0.25

1.75

1.63

-

-

-

1070

1.15

1.32

1.23

0.99

1.46

1.36

0.70

1.68

1.57

0.41

1.89

1.76

0.12

2.11

1.97

1130

1.34

1.43

1.33

1.20

1.57

1.46

0.89

1.83

1.71

0.60

2.04

1.90

-

-

-

1175

1.54

1.51

1.41

1.40

1.67

1.56

1.10

1.92

1.79

0.79

2.18

2.03

-

-

-

1220

1.71

1.66

1.55

1.57

1.81

1.69

1.26

2.10

1.96

-

-

-

-

-

-

MODEL BCB090  - (BOTTOM DUCT APPLICATIONS)

BLOWER

SPEED,

RPM

CFM

3000

3500

4000

4500

5000

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

860

1.14

1.40

1.31

0.98

1.58

1.48

0.77

1.80

1.68

0.53

2.05

1.91

0.25

2.31

2.15

915

1.32

1.55

1.45

1.18

1.76

1.64

0.95

1.98

1.85

0.72

2.23

2.08

0.49

2.48

2.31

950

1.51

1.68

1.57

1.37

1.91

1.78

1.15

2.14

2.00

0.91

2.43

2.27

0.67

2.72

2.54

1000

1.69

1.83

1.71

1.57

2.07

1.93

1.35

2.33

2.17

1.14

2.62

2.45

0.92

2.91

2.72

1050

1.89

1.98

1.84

1.78

2.25

2.10

1.57

2.55

2.37

1.35

2.86

2.67

1.12

3.17

2.96

1090

2.08

2.12

1.97

1.97

2.41

2.24

1.78

2.72

2.54

1.55

3.06

2.86

-

-

-

MODEL BCB120  - (SIDE DUCT APPLICATIONS)

BLOWER

SPEED,

RPM

CFM

3000

3500

4000

4500

5000

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

860

1.01

1.40

1.31

0.80

1.58

1.48

0.54

1.80

1.68

0.23

2.05

1.9114

-

-

-

915

1.19

1.55

1.45

1.00

1.76

1.64

0.72

1.98

1.85

0.42

2.23

2.08

0.13

2.48

2.31

950

1.38

1.68

1.57

1.19

1.91

1.78

0.92

2.14

2.00

0.61

2.43

2.27

0.31

2.72

2.54

1000

1.56

1.83

1.71

1.39

2.07

1.93

1.12

2.33

2.17

0.84

2.62

2.45

0.56

2.91

2.72

1050

1.76

1.98

1.84

1.60

2.25

2.10

1.34

2.55

2.37

1.05

2.86

2.67

0.76

3.17

2.96

1090

1.95

2.12

1.97

1.79

2.41

2.24

1.55

2.72

2.54

1.25

3.06

2.86

-

-

-

NOTE:  Blower performance includes a wet indoor coil and 2" filters.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
             total static pressure of the blower. Refer to the Accssory Static ResistancesTable for the resistance of the unit accessories.

MODEL BCB120 - (BOTTOM DUCT APPLICATIONS)

            = Larger Horsepower Alternate Motor Required.

DESCRIPTION

EXTERNAL STATIC PRESSURE DROP - RESISTANCE, IWG

CFM

2250

3000

4000

5000

Economizer

0.02

0.02

0.03

0.05

Electric Heaters

9

9 KW 

1

0.06

0.11

0.20

0.31

18 KW
24 KW

0.06

0.12

0.21

0.33

36 KW

0.07

0.13

0.23

0.35

54 KW 

2

-

0.15

0.26

0.40

TABLE 6 - ACCESSORY STATIC RESISTANCES*

*Deduct these resistance values from
  the available external static pressure
  shown in the respective Supply Air
  Blower Performance Table.

1

9 KW Heater is only available on 

  7-1/2 Ton Units.

2

54 KW Heater is only available on 

  10 Ton Units.

511.06-N2W

Unitary Products Group

9

Summary of Contents for BCCB 090

Page 1: ...s available in the following reference forms 530 18 N9 1V Electric Heater Accessory 530 18 N3 2V Economizer Accessory 530 18 N3 8V Motorized Outdoor Air Damper Accy 530 18 N3 9V Manual Outdoor Air Dam...

Page 2: ...3 Physical Data 6 4 Point Loads 8 5 Supply Air Br Performance 9 6 Accessory Static Resistances 9 7 Blower Motor and Drive Data 10 8 Heat Anticipator Setting 11 9 Blower Motor Pulley Adjustment 11 FIGU...

Page 3: ...is recommended to prevent mud splashing WARNING The unit should not be installed in an area where mud or ice could cause personal injury Remember that condensate will drip from the outdoor coil durin...

Page 4: ...provide electric resistance heat only The compressors will not run The pilot light will indicate that the switch is on EM HT Nine conductors are required for this application POWER AND CONTROL WIRING...

Page 5: ...4 1 7 1 5 8 130 64 52 2 3 1 3 1 3 5 7 2 6 2 1 7 5 3 4 2 7 42 0 21 1 17 7 43 8 21 9 18 3 50 25 20 50 25 20 120 208 230 3 60 460 3 60 575 3 60 16 7 17 3 9 6 8 3 150 73 62 3 5 2 5 2 5 7 5 3 4 2 7 10 6 4...

Page 6: ...FINS PER INCH 15 13 FACE AREA Sq Ft 7 8 13 4 OUTDOOR FANS Two Per Unit PROPELLER DIA in 24 ea 24 ea FAN MOTOR HP 1 2 ea 3 4 ea NOM CFM TOTAL 2900 ea 4400 ea OUTDOOR COIL ROWS DEEP 2 2 FINS PER INCH 1...

Page 7: ...ontrol Wiring Side 7 8 Bottom B 2 Power Wiring Side or Bottom Knockouts in the bottom of the unit can be located by the slice in the insulation UTILITIES ENTRY DATA RETURN AIR SUPPLY AIR OUTDOOR AIR O...

Page 8: ...355 460 388 NOTE These weights are with economizer and 36 kW electric heat UNIT BCB 6 POINT LOADS LBS TOTAL A B C D E F 090 1 154 154 188 211 235 193 173 120 1 504 200 237 272 307 259 229 NOTE These...

Page 9: ...2 62 2 45 0 92 2 91 2 72 1050 1 89 1 98 1 84 1 78 2 25 2 10 1 57 2 55 2 37 1 35 2 86 2 67 1 12 3 17 2 96 1090 2 08 2 12 1 97 1 97 2 41 2 24 1 78 2 72 2 54 1 55 3 06 2 86 MODEL BCB120 SIDE DUCT APPLIC...

Page 10: ...compressors out when the suction line temperature drops below 26 F This is an automatic reset device HEATING SEQUENCE OF OPERATION The following sequence of operation is based on using a standard YOR...

Page 11: ...filter access and the blower access panels as shown in Figure 4 2 Insert at least 8 of 1 4 inch tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoo...

Page 12: ...rost time cycle will restart 10 minutes after the start of the defrost cycle even though the liquid sensor terminated defrost after 3 minutes During troubleshooting the defrost time can be reduced to...

Page 13: ...power to the unit to prevent personal injury FILTERS Inspect once a month Replace disposable or clean permanent type as necessary DO NOT replace permanent type with disposable MOTORS Indoor fan and ou...

Page 14: ...511 06 N2W 14 Unitary Products Group...

Page 15: ...511 06 N2W Unitary Products Group 15...

Page 16: ...es 511 06 398 Subject to change without notice Printed in U S A Copyright by Unitary Products Group 1998 All rights reserved 511 06 N2Z Code SBL F 5005 York Drive Norman Oklahoma 73069 Unitary Product...

Reviews: