FIG. 3 - TYPICAL FIELD WIRING
MODEL
POWER
SUPPLY
COMPRESSOR
(#1 and #2)*
OUTDOOR
FAN
MOTOR,
(#1 & #2)
FLA
EACH
SUPPLY
AIR
BLOWER
MOTOR,
FLA
TOTAL
UNIT
AMPACITY,
AMPS
MAX.
FUSE
SIZE,
1,2
AMPS
RLA
EACH
LRA
EACH
1.5HP
2HP
3HP
1.5HP
2HP
3HP
1.5HP
2HP
3HP
090
208/230-3-60
460-3-60
575-3-60
14.1
7.1
5.8
130
64
52
2.3
1.3
1.3
5.7
2.6
2.1
7.5
3.4
2.7
-
-
-
42.0
21.1
17.7
43.8
21.9
18.3
-
-
-
50
25
20
50
25
20
-
-
-
120
208/230-3-60
460-3-60
575-3-60
16.7/17.3
9.6
8.3
150
73
62
3.5
2.5
2.5
-
-
-
7.5
3.4
2.7
10.6
4.8
3.9
-
-
-
52.8
30.0
26.5
55.9
31.4
27.7
-
-
-
70
35
30
70
40
35
NOTES: 1. Dual element, time delay type.
2. Maximum HACR breaker of the same AMP size is applicable,
*Dual numbers indicate amps for compressor #1 / #2 respectively.
TABLE 2 - ELECTRICAL DATA
511.06-N2W
Unitary Products Group