272312-UIM-A-0407

Unitary Products Group

11

SUPPLY VOLTAGE CONNECTIONS

IMPORTANT: 

The power connection leads and wiring box may be relo-

cated to the left side of the furnace. Remove the screws and cut wire tie
holding excess wiring. Reposition on the left side of the furnace and fas-
ten using holes provided.

1.

Provide a power supply separate from all other circuits. Install
overcurrent protection and disconnect switch per local/national
electrical codes. The switch should be close to the unit for conve-
nience in servicing. With the disconnect or fused switch in the OFF
position, check all wiring against the unit wiring label. Refer to the
wiring diagram, Figure 31, in this instruction.

2.

Remove the screws retaining the junction box cover. Route the
power wiring through the opening in the unit into the junction box
with a conduit connector or other proper connection. In the junc-
tion box there will be three wires, a Black Wire, a White Wire and a
Green Wire. Connect the power supply as shown on the unit wiring
label on the inside of the blower compartment door or Figure 8.
The black furnace lead must be connected to the L1 (hot) wire
from the power supply. The white furnace lead must be connected
to neutral. Connect the green furnace lead (equipment ground) to
the power supply ground. An alternate wiring method is to use a
field provided 2” (5.1 cm) x 4” (10.2 cm) box and cover on the out-
side of the furnace. Route the furnace leads into the box using a
protective bushing where the wires pass through the furnace
panel. After making the wiring connections replace the wiring box
cover and screws.

3.

The furnace's control system requires correct polarity of the power
supply and a proper ground connection. If the power supply polar-
ity is reversed, the control board will flash 9 times. The furnace will
not operate until the polarity is corrected. Refer to "FURNACE
DIAGNOSTICS" section of the “User’s Information, Maintenance,
& Service Manual” provided with this furnace  for symptoms of
reversed power supply polarity.

LOW VOLTAGE CONTROL WIRING CONNECTIONS

Install the field-supplied thermostat by following the instructions that
come with the thermostat. With the thermostat set in the OFF position
and the main electrical source disconnected, connect the thermostat
wiring from the wiring connections on the thermostat to the terminal
board on the ignition module, as shown in Figures 9 & 10. Electronic
thermostats may require the common wire to be connected as shown in
Figures 9 & 10. Apply strain relief to thermostat wires passing through
cabinet. If air conditioning equipment is installed, use thermostat wiring
to connect the Y and C terminals on the furnace control board to the
proper wires on the condensing unit (unit outside).

IMPORTANT: 

 Some electronic thermostats do not have adjustable

heat anticipators. They may have other type cycle rate adjustments.
Follow the thermostat manufacturer's instructions.

The 24-volt, 40 VA transformer is sized for the furnace components
only, and should not be connected to power auxiliary devices such as
humidifiers, air cleaners, etc. The transformer may provide power for an
air conditioning unit contactor.

For additional connection diagrams for all UPG equipment refer to “Low
Voltage System Wiring” document available online at www.upgnet.com
in the Product Catalog Section.

 FIGURE 8:  

Electrical Wiring

BLK/BLK
WHT/WHT
GRN/GRN

HUM

EAC

L1
(HOT)

N

GND

HUM (HOT)

EAC (HOT)

GRN

WHT

BLK

JUNCTION
BOX

DOOR SWITCH

CLASS 2 SYSTEM
CONTROL WIRING
TO THERMOSTAT

WIRING INSIDE
JUNCTION BOX

BURNER
COMPARTMENT

BLOWER
COMPARTMENT

IGNITION
MODULE

Set the heat anticipator in the room thermostat as shown below. Set-

ting it lower will cause short cycles. Setting it higher will cause the 

room temperature to exceed the setpoint.

Two-Stage Thermostat

First Stage

.4 Amps

Second Stage

.6 Amps

Single Stage Thermostat

.4 Amps

Do not exceed 1.0 amp loading.

Summary of Contents for AHT8-UH

Page 1: ...RING DIAGRAM 30 LIST OF FIGURES Dimensions 6 Typical Attic Installation 7 Typical Suspended Furnace Crawl Space Installation 7 Side Return Cutout Markings 8 Gas Valve 8 Upflow Gas Piping 8 Horizontal...

Page 2: ...s from combustible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models...

Page 3: ...d Never store items such as the following on near or in contact with the fur nace 1 Spray or aerosol cans rags brooms dust mops vacuum cleaners or other cleaning tools 2 Soap powders bleaches waxes or...

Page 4: ...t the specified external static pressure and within the air temperature rise specified on the nameplate Table 2 is a guide for determining whether the rectangular duct system that the furnace is being...

Page 5: ...plenum On all installations without a coil a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi cate the presenc...

Page 6: ...essibility IMPORTANT If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size HORIZONTAL MODELS IMPORTANT This furnace may be install...

Page 7: ...removed and a new plenum installed that is the proper size for the new furnace Attach the return plenum to the furnace inlet duct flanges This is typi cally through the use of S cleat material when a...

Page 8: ...fer to Table 15 SECTION IV GAS PIPING GAS SAFETY IMPORTANT Plan your gas supply before determining the correct gas pipe entry Use 90 degree service elbow s or short nipples and con ventional 90 degree...

Page 9: ...e gas valve body is a very thin casting that cannot take any external pressure Never apply a pipe wrench to the body of the gas valve when installing piping A wrench must be placed on the octag onal h...

Page 10: ...o the proper gas orifice size when the furnace is installed Do not attempt to drill out any orifices to obtain the proper orifice size Drilling out a gas orifice will cause misalignment of the burner...

Page 11: ...ty is corrected Refer to FURNACE DIAGNOSTICS section of the User s Information Maintenance Service Manual provided with this furnace for symptoms of reversed power supply polarity LOW VOLTAGE CONTROL...

Page 12: ...lt Common is optional when used with batteries Thermostat Installer Setup Number 1 System Type must be set to 6 2 Heat 2 Cool Conventional R 24 Volt Hot Heat XFMR W2 Second Stage Heat RC 24 Volt Hot C...

Page 13: ...BSG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor W2 Second Stage Auxiliary Heat W2 Second Stage Auxiliary Heat AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary H...

Page 14: ...gas supplies must be provided as specified with these instruc tions Since the furnaces are side by side with no space between gas supplies must enter on the right and left respectively All gas piping...

Page 15: ...wers will come on in the selected continuous fan speed and will stay on until the G signal is removed SECTION VI VENT SYSTEM VENT SAFETY This Category I furnace is designed for residential application...

Page 16: ...ese instructions Approved Modular Homes must be vented with an approved roof jack and may not be common vented with other appliances VENTING Category I venting consists of vertically venting one or mo...

Page 17: ...se masonry chimney kits 3 The chimney must extend at least three 3 ft 0 91 cm above the highest point where it passes through a roof of a building and at least two 2 feet higher than any portion of th...

Page 18: ...tion should be located where it will not be affected by wind gusts light snow airborne leaves or allow recirculation of flue gases 4 Termination should be located where it will not be damaged or expos...

Page 19: ...anufacturer s instructions Dampers Louvers and Grilles Canada Only 1 The free area of a supply air opening shall be calculated by sub tracting the blockage area of all fixed louvers grilles or screens...

Page 20: ...horizontally from the burner level of the appliance Refer to COMBUSTION AIR SOURCE FROM OUTDOORS and VENT AND SUPPLY AIR SAFETY CHECK in these instructions for additional information and safety check...

Page 21: ...mounted on the burner assembly If the temperature around the burner exceeds the set point the ignition control and the gas valve are de energized The operation of this control indicates a malfunction...

Page 22: ...m Source 1 which has the following items 1 12 30 cm length x 1 8 0 3 cm diameter tubing 2 pieces of 4 10 cm length x 1 8 0 3 cm diameter tubing 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 3 175 mm reducing...

Page 23: ...at the gas meter times a barometric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas mul...

Page 24: ...h low and high have been calibrated at the factory Additional pressure adjustment should not be necessary If adjustment is necessary set to the following specifications After adjustment check for gas...

Page 25: ...eration Start the system by setting the thermostat above the room temperature Observe the system s response Then use the troubleshooting section in this manual to check the system s operation FURNACE...

Page 26: ...mit switch has opened its normally closed contacts and has remained open for more than five minutes This condition is usually caused by a failed blower motor or blower wheel 12 RED FLASHES This code i...

Page 27: ...the difference in ESP values in the table 0 60 w c 150 Pa 0 50 w c 125 Pa to obtain a percentage 0 58 0 50 0 60 0 50 0 8 Multiply percentage by airflow difference to obtain airflow reduction 0 8 X 70...

Page 28: ...50 1440 1430 1390 1360 1310 1270 1220 1150 41 6 41 1 40 8 40 5 39 4 38 5 37 1 36 0 34 5 32 6 Low 1260 1260 1260 1260 1250 1200 1150 1110 1070 1010 35 7 35 7 35 7 35 7 35 4 34 0 32 6 31 4 30 3 28 6 80...

Page 29: ...640 1550 1460 56 6 55 5 54 7 53 8 51 0 49 8 48 4 46 4 43 9 41 3 Medium 1440 1440 1430 1420 1400 1380 1340 1300 1220 1150 40 8 40 8 40 5 40 2 39 6 39 1 37 9 36 8 34 5 32 6 Low 1220 1230 1230 1230 1200...

Page 30: ...272312 UIM A 0407 30 Unitary Products Group SECTION IX WIRING DIAGRAM FIGURE 31 Wiring Diagram...

Page 31: ...272312 UIM A 0407 Unitary Products Group 31 NOTES...

Page 32: ...t to change without notice Printed in U S A 272312 UIM A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 167185 UIM C 0806 Unitary 5005 Norman Product York OK Group Drive...

Reviews: