9.0 BACK PANEL DESCRIPTION
9.1
Back View
. Figure 5 shows the back of the DPB1U and DPG1U distribution panel. Inputs
are at the left and right ends of the back panel. Side B outputs are at two rows of barrier
terminal strips on the left side, and side A outputs are the same on the right side. At the
center of the back panel are two spring clamp terminal blocks for the Form C relay contact
outputs.
Below these is a chassis ground terminal.
Alarm
Contacts
Alarm LEDs
B Input
¼-20 Studs
BAT
RTN
BAT
RTN
1 2 3 4 5 6 7 8 9 10
A
B
ALARM
Ground
8-32 Stud
A Side Breakers
B Side Breakers
A Outputs
6-32 Terminal Strip
B Outputs
6-32 Terminal Strip
A Input
¼-20 Studs
BAT
RTN
BAT
RTN
1 2 3 4 5 6 7 8 9 10
B SIDE A SIDE
NO-C-NC
NO-C-NC
5
6
3
4
1
2
OFF
O
ON
I
15
OFF
O
ON
I
15
OFF
O
ON
I
15
OFF
O
ON
I
15
OFF
O
ON
I
15
OFF
O
ON
I
15
5
6
3
4
1
2
OFF
O
ON
I
15
OFF
O
ON
I
15
OFF
O
ON
I
15
OFF
O
ON
I
15
OFF
O
ON
I
15
OFF
O
ON
I
15
17.12 (434.9)
1.74
(44.2)
REAR VIEW
FRONT VIEW
Case depth: 8.94 (227.1)
2.28
(57.8)
Clear Perspex
Safety Cover
Figure 5. Back Panel View
9.2
Input Connections
. See Figure 6. The DC power inputs to the distribution panels are made
by means of crimp type lugs or direct connection to ¼-20 studs to two copper bus bars on
side A and side B. The upper bus bar is the battery connection (w or -) and the
lower bus bar is the return (w or -).
0.625”
1.48”
0.5”
0.34”
0.375”
0.65”
0.32”
Figure 6. Input Bus Bar Detail
9.3
Crimp Type Lugs.
A list of compatible crimp type lugs is shown in the following table
for AWG wire sizes from no. 1 to 8 and one- or two- hole lugs. These lugs can be ordered
directly from the manufacturer, Panduit Corp., using the model numbers shown in table 4.
A standard kit of four two-hole crimp type lugs for no. 6 AWG copper wire is available from
UNIPOWER. Order kit no. 775-1434-0000.