For remote supervision of alarms, there are 4 potential free alarm contacts available. Each
alarm contact represents different condition. Multi Purpose Voltage Inputs 1-12 can be
reconfigured as external analog inputs.
The pin description detail for all signal connections is shown in Figure 4-5.
Alarm connections are Form C relays and can be monitored either Normally Closed (NC) or
Normally Opened (NO). When the power is OFF NC is closed and when the power is ON
NC is open.
NOTE
Each alarm contact represents a different alarm condition or conditions. These are
defined in the controller’s alarm matrix setup.