Aspiro 1U in 2U Enclosure Quick Install Guide - 2
START HERE
This guide includes the basic steps for installation
of a UL listed Aspiro 2U enclosure. For more detailed
information, please see the full instruction manual
which is available from UNIPOWER.
Disclaimer
UNIPOWER is not responsible for system problems that
are the result of incorrect installation or modification
of the instructions provided in this guide.
WARNING!
There are potential hazards related to the installation
of this system. It is recommended to carefully read and
understand the contents of the
Safety Chapter before performing this installation.
WARNING!
It is strongly recommended to turn off the AC Power
Source before performing this installation.
1 System Description
The system is supplied as a single 19 inch x 2U rack
mount enclosure and incorporates positions for up to
two rectifier modules and one controller.
1
2
3
4
1. Slot for optional controller.
2. Battery (x1) and load (x4) breakers.
3. Slots for one or two rectifier modules.
4. AC input, DC output and signal connections.
2 Rack Mounting
The system is designed for 19 inch rack mounting There
needs to be sufficient clearance at the front for rectifier
installation [>36” (914mm], and at the rear for connections
and airflow [>6” (152mm].
17.28”
(438.8mm)
0.78”
(19.7mm)
[typical]
19.00”
(482.6mm)
18.38”
(466.8mm)
11.78”
(299.2mm)
12.10”
307.4mm)
12.26”
(311.4mm)
0.16”
(4.0mm)
3.48”
(88.5mm)
3.12”
(79.2mm)
2.13”
(54.2mm)
1.40”
(35.6mm)
0.42”
(10.6mm)
0.25” x 0.5” Slot
(6.35mm x 12.70mm Slot)
NOTE:
It is recommended to remove the rectifiers before
installing the shelf to the cabinet or rack.