 3 AC Input Connections

WARNING!

The power system is internally grounded.  Grounding 
is achieved through the 3 conductor AC power cord.

CAUTION

Depending on deployment region with regards to 
lightning strikes and heavy inductive energy, it is highly 
recommended to install AC Surge Protection Class C 
at the electrical panel.

AC connectors are situated on the right rear side of the 
system as shown below.

4

3

2

1

LOAD

+

_

+

_

+

_

+

_

BATTERY

+

_

AC INPUT 2

AC INPUT 1

SIGNAL

CONNECTIONS

BATTERY

AC

INPUTS

DC

OUTPUTS

+

-

+

-

+

-

+

_

The following breakers for isolating the AC source are 
recommended for each input:

120VAC operation - 20A.
230VAC operation - 16A.

 4 DC Output Connections

DC output connections are available at the rear, 
with connections labeled corresponding to each 
load breaker.

Load breakers should be in the OFF position when 
connecting the loads,

Mate-N-Lock connectors are used for DC ouptut 
connections.

4

3

2

1

LOAD

+

_

+

_

+

_

+

_

BATTERY

+

_

AC INPUT 2

AC INPUT 1

SIGNAL

CONNECTIONS

BATTERY

AC

INPUTS

DC

OUTPUTS

+

-

+

-

+

-

+

_

 5 Battery Connections

The battery connections are located at the center 
of the rear panel of the system.  Ensure that the 
battery breaker is in the OFF position.

4

3

2

1

LOAD

+

_

+

_

+

_

+

_

BATTERY

+

_

AC INPUT 2

AC INPUT 1

SIGNAL

CONNECTIONS

BATTERY

AC

INPUTS

DC

OUTPUTS

+

-

+

-

+

-

+

_

WARNING!

Improper handling with batteries can be dangerous. 
Please read and understand the information in the 
instruction manual Safety chapter before connecting 
batteries.

WARNING!

The battery breaker should be in the OFF position.
The battery cables should be connected to the battery 
first, then to the system.

Battery cable (ZLH.00254.01) is custom design for 
the Aspiro enclosure.

Connect to the battery first and then plug the 
connector end into the system battery connector.

Continued on page 4 