UniPOS Fire Control Panel FS4000
Instruction manual
Page 6
Revision 11/01.17
of 34
4.8.
Power supply
4.8.1. Mains:
voltage
- (100
÷240)V
frequency
- 50/60Hz
4.8.2. Backup batteries:
battery type
- lead, gel electrolyte
number of batteries
- 2 pcs
nominal voltage of the backup battery
-
2х12VDC
nominal capacity C
20
- (7,0) Ah
charge voltage
- 27,5 VDC
Operation in Duty mode upon interruption in main power supply
24V/ 7,0Ah
24V/ 4.5Ah
24V/ 1.2Ah
Configuration 2 lines
180h
120h
32h
Configuration 4 lines
140h
98h
24h
Configuration 6 lines
110h
80h
20h
Configuration 8 lines
90h
68h
16h
4.8.3. Consumption on backup batteries supply:
Configuration of 2 lines
- < 35mA at 24V
Configuration of 4 lines
- < 45mA at 24V
Configuration of 6 lines
- < 55mA at 24V
Configuration of 8 lines
- < 65mA at 24V
4.9.
Power supply to external devices:
voltage
- (19
÷27)V
maximum current value (including current
of monitored outputs)
- 1,2
А
4.10.
Fuses:
Main supply 230V
- 4.0A
Backup battery
- 6,0
А
Power supply to external devices
-1,85
А automatic
Monitored outputs
- 1,1
А automatic
4.11. Dimensions
-
304х222х94 mm
4.12. Weight, backup batteries not included
- 0,98kg
5. Contents of delivery:
Fire control panel FS4000
- 1 pc
End of line resistors 3,0k / 0.6W
for 2 lines
- 2 pcs
for 4 lines
- 4 pcs
for 6 lines
- 6 pcs
for 8 lines
- 8 pcs
Resistor 5,6k
/ 0,25W
- 2 pcs
Fuse 6,0A
- 1 pc
Fuse 4,0A
- 1 pc
Cable bridge
- 1 p
с
Brochure
- 2 p
с
Screws to fix the front cover
- 2 pcs.
Packing
- 1 pc