Circuit diagrams
Manual CWD 2005
___________________________________________________________________
98
Manual CWD2005.doc
10.2.1.5.
Serial interface RS232 (Option)
The RS232 interface can be used to transmit measured values to a remote location.
Parameter
selection is made in the menu “I/O Analog outputs”.
The RS232 interface is connected to block X 11 and to block X 1.
Interface parameters:
Transmission rate: 9600 Baud
Parity-bit
no
Stop-bit:
1
Data-bit:
8
Data output format:
111111.111 222222.222 333333.333 444444.444 555555.555 666666.666 777777.777
111111.111
= value analog output 1
222222.222
= value analog output 2
..................
.. ....... ..... ...................
..................
.. ....... ..... ...................
777777.777 = value analog output 7
Block X 11
Pin
Signal
1
Not connected
2
Not connected
3
Not connected
4
Not connected
5
PT100 air conditioner / heating enclosure
6
PT100 air conditioner / heating enclosure
7
Not connected
8
RI
9
RTS
10
CTS
11
DSR
12
DTR
13
TXD
14
RXD
15
DCD
16
RS232 GND+
Block X 1
Pin
Signal
1
DCD
2
RXD
3
TXD
4
DTR
5
RS232 GND
6
DSR
7
RTS
8
CT
9
RI