ERROR MESSAGES
The upper display shows the OVER-RANGE and UNDERRANGE conditions with the following indications:
Over-range:
Under-range
The sensor break will be signalled as an out of range:
Note: When an over-range or an under-range is detected, the alarms operate as in presence of the maximum or the
minimum measurable value respectively.
To check the out of span Error condition, proceed as follows:
1. Check the input signal source and the connecting line.
2. Make sure that the input signal is in accordance with the instrument configuration. Otherwise, modify the input
configuration.
3. If no error is detected, send the instrument to your supplier to be checked.
List of possible errors
ErAT
Fast Auto-tune cannot start. The measure value is tooclose to the set point. Push the button in order to delete the
error message.
ouLd
Overload on the out 4. The messages shows that a short circuit is present on the Out 4 when it is used as output
or as a transmitter power suply. When the short circuit disappears the output restart to operate..
NoAt
Auto-tune not finished within 12 hours.
ErEP
Possible problem of the instrument memory. The messages disappears automatically. When the error continues,
send the instrument to your supplier.
RonE
Possible problem of the firmware memory. When this error is detected, send the instrument to your supplier.
Errt
Possible problem of the calibration memory. When this error is detected, send the instrument to your supplier.
FACTORY RESET
Sometime, e.g. when you re-configure an instrument previously used for other works or from other people or when you
have made too many errors during configuration and you decided to re-configure the instrument, it is possible to restore
the factory configuration. This action allows to put the instrument in a defined condition (the same it was at the first power
ON).
The default data are those typical values loaded in the instrument prior to ship it from factory. To load the factory default
parameter set, proceed as follows:
1. Press the
button for more than 5 seconds. The upper display will show PASS while the lower display
shows 0;
2. Using
and
buttons set the value -481;
3. Push
button;
4. The instrument will turn OFF all LEDs for a few seconds, then the upper display will show dFLt (default) and
then all LEDs are turned ON for 2 seconds. At this point the instrument restarts as for a new power ON.
The procedure is complete.
Note: The complete list of the default parameters is available in Chapter "Configuration".
Summary of Contents for TN90
Page 2: ......
Page 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 34: ...CIB UNIGAS M039259CA 34...
Page 54: ......
Page 63: ......
Page 64: ......
Page 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 82: ...M12927CA MOUNTING 2...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......