1
21/06/2012 rev. 0
Set-up for 600V RRR0-1-T73 regulator
Set up for temperature probe Pt100 (ex Siemens QAE2120 130°C max.)
The regulator comes out of the factory preset with the corresponding values of the Siemens RWF40.000 and
RWF50.2x
Verify wiring of the sensor
Regulation of the set-point =
80
It can be modified by using arrows "up" and "down".
By pushing
F
you go to parameters:
Hy.P
5 (hysteresis positive for output 1, terminals 21-22 (ex Q13-Q14)
Hy.n
-5 hysteresis negative for output ,1 terminals 21-22 (ex Q13-Q14)
Keep pushing
F
until you see
PASS
, release
F
and through the arrows set
99
, push
F
and visualize
Pro
(protection code) default is
12
, through the arrows set
128
and push
F,
keep it pushed until all parameters
InF
,
CFG
,
InP
,
Out
,
PASS
are visualized.
CFG
S.tun 0
hPb
1,2
hIt 5,83
hdt
1,33
…
InP
….
tyP
30 (Pt100)
…
dP_S
1 (decimals num.)
Lo.S
0 (min. sensor scale)
Hi.S
850,0 (max sensor scale)
oFS
0 (offset of input correction)
Lo.L
30,0 (lower set-point range limit)
Hi.L
130,0 (upper set-point range limit)
Summary of Contents for TN90
Page 2: ......
Page 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 34: ...CIB UNIGAS M039259CA 34...
Page 54: ......
Page 63: ......
Page 64: ......
Page 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 82: ...M12927CA MOUNTING 2...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......