background image

PART I: INSTALLATION

9

AIR AND GAS FLOW SETTINGS  

WARNING:

 During commissioning operations, do not let the burner operate with insufficient air flow (danger of formation of car-

bon monoxide); if this should happen, shut down the burner, increase the opening of the air damper and start up the burner
again to ensure the purging of the carbon monoxide from the combustion chamber.

WARNING: 

changes to the gas flow rate require a new setting of the air rate and a new combustion check.

MULTIBLOC DUNGS

MULTIBLOC DUNGS
The multibloc is a compact assembly made up of two solenoid valves, a gas pressure switch, a pressure stabilizer and a gas fil-
ter. It can be used in combination with the Dungs VPS504 leakage control.

WARNING!

THE SEALED SCREWS MUST NOT BE UNSCREWED!

IN A SUCH CASE THE DEVICE WARRANTY IS IMMEDIATELY INVALIDATE!

Fig. 11 - Burners fitted with the Multibloc MB-DLE valve assembly

The servocontrol cams corresponding to the stand-by (0°) and high flame (70°) positions are factory-set and must not be modi-
fied. The low flame regulation cam is set to 10°, and, unless strictly necessary, should not be modified. To adjust the burner
when installed in the system, proceed as follows.

High Flame Calibration

1 Ignite the burner, bring it to high flame, adjust the gas flow-rate (Fig. 11) by loosening the screw VB (not sealed), turn the

adjustment nut RP, anticlockwise to increase the flow-rate (+ sign), and clockwise to decrease it (- sign); to increase the gas
flow-rate, use the screw (VS) located under the cover C (clockwise increases it, anticlockwise decreases it).

2 To adjust the flow-rate of the air at high flame, loosen the nut RA and turn the screw VRA (clockwise increases the flow-rate

of the air, anticlockwise decreases it) until reaching the desired flow-rate (Fig. 14).

3 To adjust the quick release, remove the cap T, turn it upside-down and place it on the pin (VR) with the groove on the upper

part. Tightening the pin decreases the ignition flow-rate, loosening it increases the flow-rate.

Low Flame Calibration

1 Bring the burner to low flame. To adjust the gas flow-rate loosen the nuts DB (Fig. 13a) and adjust the angle of opening of the

butterfly valve by turning the stud TG (Fig. 13b); turning it clockwise increases the gas flow-rate, anticlockwise decreases it.
The slit (S in Fig. 13a) on the pin of the butterfly valve indicates the angle of opening in reference to the horizontal axis. 

2 To adjust the output of the burner in low flame operation, use the corresponding servocontrol cam. After this operation, check

the gas flow-rate and if necessary repeat point 4.

3 When the operations have been completed, make sure the check nuts RA and DB have been tightened.

4 Replace the cover on the servocontrol.

Note: tighten the screw VB.

N.B. The high flame cam on the servocontrol is set to 70°, as this position corresponds to the maximum opening of the 
butterfly valve (90°).

Fig. 11

Key

LC

Consent light (successful leak test)

LB

Illuminated lockout and reset button

PA

Pressure test point

C

Cover

T

Cap

VS

Flow-rate adjustment screw

VR

Quick release adjustment pin

RP

Adjustment ring

VB

Adjustment locking screw

C-(VS) T(VR)

RP

VB

LC

LB

PA

Summary of Contents for S10

Page 1: ...Technical Documentation CIB Unigas Campodarsego PD Complying with 90 396 CEE GAS DIRECTIVE MANUAL OF INSTALLATION OPERATION MAINTENANCE GAS BURNERS S10 S18 DOUBLE STAGE VERSION M03952CC Rev 02 04 01...

Page 2: ...ry equipment only shall be used This unit shall be employed exclusively for the use for which it is meant Any other use shall be considered as improper and therefore dangerous The manufacturer shall n...

Page 3: ...ls or damage to property for which the manufacturer cannot be held liable Before installation it is recommended that all the fuel supply system pipes be carefully cleaned inside to remove foreign matt...

Page 4: ...3 OPERATION Available versions AB High low flame 4 BLAST TUBE LENGHT See overall dimensions S Standard L Long 5 DESTINATION COUNTRY see data plate 6 SPECIAL VERSIONS A Standard 7 EQUIPMENT Available...

Page 5: ...input in kcal h multiply value in kW by 860 Fig 4a Fig 4b A B BL C CL D E F G K J H P M N Q R S10 355 180 275 635 730 340 230 455 108 200 210 125 120 M8 169 7 55 100 S18 355 205 300 660 755 340 230 4...

Page 6: ...re in combustion chamber Fig 4 Key 1 Boiler 2 Gas pressure port on butterfly valve 3 Sightglass cooling port 4 Water column pressure gauge Curves are referred to a null pressure in combustion head NOT...

Page 7: ...boilers with a combustion chamber smaller in diameter or shorter than those described in the diagram please contact the supplier to verify that a correct matching is possible with respect of the appl...

Page 8: ...lves group 3 Leakage control device optional if burner input 1200 kW 4 Bellow joint 5 Manual shut off valve Remove the burner cover Carry out the electrical connections to the multiple con nector as s...

Page 9: ...e screw VS located under the cover C clockwise increases it anticlockwise decreases it 2 To adjust the flow rate of the air at high flame loosen the nut RA and turn the screw VRA clockwise increases t...

Page 10: ...rate using the nut RP1 turning it anticlockwise to increase it sign or clockwise to decrease it sig n 3 To adjust the output of the burner in low flame operation use the corresponding servocontrol cam...

Page 11: ...g 13a Fig 13b Key S Slit indicating the butterfly opening angle DB Stud TG lock nuts TG Butterfly valve opening adjustment stud RA Lock nut VRA Screw for adjusting combustion air to maximum flow rate...

Page 12: ...y means of the appropriate tool fitted with the servocontrol with SQN30 or by means of a screwdriver affecting on the screw into the cam all other servocontrols Landis SQN30 151 Berger STA6B3 41 Fig 1...

Page 13: ...t off valve n 5 in Fig 10 until the detected pressure is reduced by 50 Verify CO emissions of the burner if the measured value is less than 80 ppm screw down the adjusting ring nut until the burner lo...

Page 14: ...LIMINATE THE MALFUNCTION WARNING DURING NORMAL OPERATION THE PARTS OF THE BURNER NEAREST TO THE GENERATOR COUPLING FLANGE CAN BECOME VERY HOT AVOID TOUCHING THEM SO AS NOT TO GET BURNT OPERATION Bring...

Page 15: ...ctrodes is carried out after removing the combustion head Removing the combustion head Remove the burner from the gas supply line To access the combustion head abd the electrodes slcken the screw VE F...

Page 16: ...PEATS THE CYCLE NURMER DOESN T SWITCH TO HIGH FLAME BURNER S LOCKUOT DURING OPERATION BURNER STOPS AND REPEATS CYCLE DURING OPERATION BURNER S LOCKOUT AFTER START THE FLAME CONTROL DEVICE REPEATS CYCL...

Page 17: ...DIS servocontrol for air damper alternate SQN70 224A20 LANDIS servocontrol for air damper alternate ST Group of thermostats or pressure switches STA4 5B0 37 63N21L BERGER servocontrol for air damper S...

Page 18: ...PART III MAINTENANCE 18 ELECTRICAL DIAGRAMS Electrical diagram 01 320 Rev 3...

Page 19: ...PART III MAINTENANCE 19 Electrical diagram 01 427...

Page 20: ...PART III MAINTENANCE 20 SPARE PARTS...

Page 21: ...80703 2180703 7 CAPACITOR FOR SIMEL MOTOR 6030005 6030005 7 CAPACITOR FOR AEG MOTOR 6030003 6030003 8 TRANSFORMER 2170108 2170108 9 EXTENSION SCREW 2130016 2130027 10 DETECTION CABLE 6050211 6050211 1...

Page 22: ...GB 21 22 FLAME CONTROLLER 23 LANDIS LMG21 22 25 FLAME CONTROLLER 26 GAS MULTIBLOC REGULATOR DUNGS MB DLE 405 407 410 412 415 420 28 GAS MULTIBLOC REGULATOR DUNGS MB ZRDLE 28 VALVE PROVING SYSTEM DUNGS...

Page 23: ...n AGK11 s socket Command signal from flame control Input signals Conditions for starting up the burner The burner control must not be locked out The contacts of the gas pressure switch GP the temperat...

Page 24: ...iance is located a plexiglass lunette under which there is the indicator disc of programme s progress In the event of safety stop the programmer stops The disc shows as follows the position of the pro...

Page 25: ...stat or pressostat W Safety thermostat or pressostat Z Ignition transformer LGB21 Key programmer s diagram A start up command from regulator R AR main relay B burner operation C program start position...

Page 26: ...on time t3n Ignition time during TSA t4 Interval BV BV2 or BV1 LR t10 Specified time for air pressure signal t11 Programmed opening time for actuator SA t12 Programmed closing time for actuator SA Sta...

Page 27: ...lamp switched on Release of the flame control device Press the release button for 0 5 3 seconds Diagnosis of troubles Wait at least 10s Press the release button for 3s Count the number of flashing of...

Page 28: ...and their combinations MB410 412 Rp 3 4 1 1 4 and their combinations Max operating pressure 360 mbar Output pressure ranges MB S20 S22 4 to 20 mbar MB S50 S52 4 to 50 mbar Media Gases of families 1 2...

Page 29: ...APPENDIX COMPONENTS CHARACTERISTICS 29...

Page 30: ...APPENDIX COMPONENTS CHARACTERISTICS 30...

Page 31: ...APPENDIX COMPONENTS CHARACTERISTICS 31...

Page 32: ......

Reviews: