background image

NOTICES

3

3)

GENERAL INSTRUCTIONS DEPENDING ON FUEL 

USED 

3a) ELECTRICAL CONNECTION

* For safety reasons the unit must be efficiently earthed and
installed as required by current safety regulations.

* It is vital that all saftey requirements are met. In case of any
doubt, ask for an accurate inspection of electrics by qualified
personnel, since the manufacturer cannot be held liable for
damages that may be caused by failure to correctly earth the
equipment.

* Qualified personnel must inspect the system to make sure
that it is adequate to take the maximum power used by the
equipment shown on the equipment rating plate. In particular,
make sure that the system cable cross section is adequate for
the power absorbed by the unit.

* No adaptors, multiple outlet sockets and/or extension cables
are permitted to connect the unit to the electric mains.

An omnipolar switch shall be provided for connection to
mains, as required by the current safety regulations.

The use of any power-operated component implies

observance of a few basic rules, for example:

- do not touch the unit with wet or damp parts of the body and/
or with bare feet;

- do not pull electric cables;

- do not leave the equipment exposed to weather (rain, sun,
etc.) unless expressly required to do so;

- do not allow children or inexperienced persons to use equip-
ment;

* The unit input cable shall not be replaced by the user.

In case of damage to the cable, switch off the unit and contact
qualified personnel to replace.

* When the unit is out of use for some time the electric switch
supplying all the power-driven components in the system (i.e.
pumps, burner, etc.) should be switched off.

3b) FIRING WITH GAS, GASOIL OR OTHER FUELS

GENERAL

* The burner shall be installed by qualified personnel and in
compliance with regulations and provisions in force; wrong
installation can cause injuries to people and animals, or
damage to property, for which the manufacturer cannot be
held liable.

* Before installation, it is recommended that all the fuel supply
system pipes be carefully cleaned inside, to remove foreign
matter that might impair the burner operation.

* Before the burner is commissioned, qualified personnel
should inspect the following:

a) the fuel supply system, for proper sealing;

b) the fuel flow rate, to make sure that it has been set based
on the firing rate required of the burner;

c) the burner firing system, to make sure that it is supplied for
the designed fuel type;

d) the fuel supply pressure, to make sure that it is included in
the range shown on the rating plate;

e) the fuel supply system, to make sure that the system
dimensions are adequate to the burner firing rate, and that the
system is equipped with all the safety and control devices
required by the regulations in force.

* When the burner is to remain idle for some time, the fuel
supply tap or taps should be closed.

SPECIAL INSTRUCTIONS FOR USING GAS

* Have qualified personnel inspect the installation to ensure
that:

a) the gas delivery line and train are in compliance with the
regulations and provisions in force;

b) all gas connections are tight;

c) the boiler room ventilation openings are such that they
ensure the air supply flow required by the current regulations,
and in any case are sufficient for proper combustion.

* Do not use gas pipes to earth electrical equipment.

* Never leave the burner connected when not in use. Always
shut the gas valve off.

* In case of prolonged absence of the user, the main gas deli-
very valve to the burner should be shut off.

Precautions if you can smell gas

a) do not operate electric switches, the telephone, or any
other item likely to generate sparks;

b) immediately open doors and windows to create an air flow
to purge the room;

c) close the gas valves;

d) contact qualified personnel.

* Do not obstruct the ventilation openings of the room where
gas appliances are installed, to avoid dangerous conditions
such as the development of toxic or explosive mixtures.

Summary of Contents for S10

Page 1: ...Technical Documentation CIB Unigas Campodarsego PD Complying with 90 396 CEE GAS DIRECTIVE MANUAL OF INSTALLATION OPERATION MAINTENANCE GAS BURNERS S10 S18 DOUBLE STAGE VERSION M03952CC Rev 02 04 01...

Page 2: ...ry equipment only shall be used This unit shall be employed exclusively for the use for which it is meant Any other use shall be considered as improper and therefore dangerous The manufacturer shall n...

Page 3: ...ls or damage to property for which the manufacturer cannot be held liable Before installation it is recommended that all the fuel supply system pipes be carefully cleaned inside to remove foreign matt...

Page 4: ...3 OPERATION Available versions AB High low flame 4 BLAST TUBE LENGHT See overall dimensions S Standard L Long 5 DESTINATION COUNTRY see data plate 6 SPECIAL VERSIONS A Standard 7 EQUIPMENT Available...

Page 5: ...input in kcal h multiply value in kW by 860 Fig 4a Fig 4b A B BL C CL D E F G K J H P M N Q R S10 355 180 275 635 730 340 230 455 108 200 210 125 120 M8 169 7 55 100 S18 355 205 300 660 755 340 230 4...

Page 6: ...re in combustion chamber Fig 4 Key 1 Boiler 2 Gas pressure port on butterfly valve 3 Sightglass cooling port 4 Water column pressure gauge Curves are referred to a null pressure in combustion head NOT...

Page 7: ...boilers with a combustion chamber smaller in diameter or shorter than those described in the diagram please contact the supplier to verify that a correct matching is possible with respect of the appl...

Page 8: ...lves group 3 Leakage control device optional if burner input 1200 kW 4 Bellow joint 5 Manual shut off valve Remove the burner cover Carry out the electrical connections to the multiple con nector as s...

Page 9: ...e screw VS located under the cover C clockwise increases it anticlockwise decreases it 2 To adjust the flow rate of the air at high flame loosen the nut RA and turn the screw VRA clockwise increases t...

Page 10: ...rate using the nut RP1 turning it anticlockwise to increase it sign or clockwise to decrease it sig n 3 To adjust the output of the burner in low flame operation use the corresponding servocontrol cam...

Page 11: ...g 13a Fig 13b Key S Slit indicating the butterfly opening angle DB Stud TG lock nuts TG Butterfly valve opening adjustment stud RA Lock nut VRA Screw for adjusting combustion air to maximum flow rate...

Page 12: ...y means of the appropriate tool fitted with the servocontrol with SQN30 or by means of a screwdriver affecting on the screw into the cam all other servocontrols Landis SQN30 151 Berger STA6B3 41 Fig 1...

Page 13: ...t off valve n 5 in Fig 10 until the detected pressure is reduced by 50 Verify CO emissions of the burner if the measured value is less than 80 ppm screw down the adjusting ring nut until the burner lo...

Page 14: ...LIMINATE THE MALFUNCTION WARNING DURING NORMAL OPERATION THE PARTS OF THE BURNER NEAREST TO THE GENERATOR COUPLING FLANGE CAN BECOME VERY HOT AVOID TOUCHING THEM SO AS NOT TO GET BURNT OPERATION Bring...

Page 15: ...ctrodes is carried out after removing the combustion head Removing the combustion head Remove the burner from the gas supply line To access the combustion head abd the electrodes slcken the screw VE F...

Page 16: ...PEATS THE CYCLE NURMER DOESN T SWITCH TO HIGH FLAME BURNER S LOCKUOT DURING OPERATION BURNER STOPS AND REPEATS CYCLE DURING OPERATION BURNER S LOCKOUT AFTER START THE FLAME CONTROL DEVICE REPEATS CYCL...

Page 17: ...DIS servocontrol for air damper alternate SQN70 224A20 LANDIS servocontrol for air damper alternate ST Group of thermostats or pressure switches STA4 5B0 37 63N21L BERGER servocontrol for air damper S...

Page 18: ...PART III MAINTENANCE 18 ELECTRICAL DIAGRAMS Electrical diagram 01 320 Rev 3...

Page 19: ...PART III MAINTENANCE 19 Electrical diagram 01 427...

Page 20: ...PART III MAINTENANCE 20 SPARE PARTS...

Page 21: ...80703 2180703 7 CAPACITOR FOR SIMEL MOTOR 6030005 6030005 7 CAPACITOR FOR AEG MOTOR 6030003 6030003 8 TRANSFORMER 2170108 2170108 9 EXTENSION SCREW 2130016 2130027 10 DETECTION CABLE 6050211 6050211 1...

Page 22: ...GB 21 22 FLAME CONTROLLER 23 LANDIS LMG21 22 25 FLAME CONTROLLER 26 GAS MULTIBLOC REGULATOR DUNGS MB DLE 405 407 410 412 415 420 28 GAS MULTIBLOC REGULATOR DUNGS MB ZRDLE 28 VALVE PROVING SYSTEM DUNGS...

Page 23: ...n AGK11 s socket Command signal from flame control Input signals Conditions for starting up the burner The burner control must not be locked out The contacts of the gas pressure switch GP the temperat...

Page 24: ...iance is located a plexiglass lunette under which there is the indicator disc of programme s progress In the event of safety stop the programmer stops The disc shows as follows the position of the pro...

Page 25: ...stat or pressostat W Safety thermostat or pressostat Z Ignition transformer LGB21 Key programmer s diagram A start up command from regulator R AR main relay B burner operation C program start position...

Page 26: ...on time t3n Ignition time during TSA t4 Interval BV BV2 or BV1 LR t10 Specified time for air pressure signal t11 Programmed opening time for actuator SA t12 Programmed closing time for actuator SA Sta...

Page 27: ...lamp switched on Release of the flame control device Press the release button for 0 5 3 seconds Diagnosis of troubles Wait at least 10s Press the release button for 3s Count the number of flashing of...

Page 28: ...and their combinations MB410 412 Rp 3 4 1 1 4 and their combinations Max operating pressure 360 mbar Output pressure ranges MB S20 S22 4 to 20 mbar MB S50 S52 4 to 50 mbar Media Gases of families 1 2...

Page 29: ...APPENDIX COMPONENTS CHARACTERISTICS 29...

Page 30: ...APPENDIX COMPONENTS CHARACTERISTICS 30...

Page 31: ...APPENDIX COMPONENTS CHARACTERISTICS 31...

Page 32: ......

Reviews: