Setting functions “TL_ThreshOff” and “TL_SD_On”
These functions enable the settable threshold for the immediate shutdown, if value set on TL_ThreshOff is exceeded. The automatic restart is performed
for values lower than the one set on TL_SD_On.
On display, values detected by temperature/pressure probe are shown at the same time.
TL_ThreshOff
turns the burner off if temperature exceeds the set value. Gas/Oil valves are suddenly closed.
TL_SD_On
automatically restart the burner if the temperature is lower than the set value.
SD_ModOff
automatically turns the burner to low flame and then shut down the burner if temperature exceeds the set value.
SD_ModOn
automatically restart the burner if the temperature is lower than the set value.
P-Part (Xp)
proportional band of modulation.
Note:
this function is available if a Pt100 Ni1000 or Pt 1000 temperature sensor is connected to X60.3 and X60.4 terminals.
ATTENTION
: basically, these parameters provide a function similar to the safety thermostat one, but can not replace it. The boiler must
always
operate with its safety thermostat connected properly.
NOTE:
the parameter TL_ThreshOff for the immediate shutdown, must always be set to a value higher than the SD_ModOff threshold for the normal
shutdown. TL_SD_On must be set at a higher temperature than SD_ModOn.
Following the below route access to the programming levels of the menu by means the Esc
1st level
2nd level
3rd level
4th level
Range
Default
Description
Params & Display
Menu level for making the
parameter set- tings
LoadController
Settings for the internal load
controller
TempLimiter
Settings for the temperature
limiter function
TL_ThreshOff 0...2000
°C 95°C
Temperature limiter OFF
threshold, in °C
TL_SD_On
-50...0%
TL_Thresh_Off
-
5% Temperature limiter switching
differential ON
TL_ThreshOff
SD_ModOn
P-Part (Xp)
P-Part (Xp)
SD_ModOff
TL_SD_On
Summary of Contents for RX92R-FGR
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......
Page 117: ...WB1 QF1 QF2...
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ...WB1 SCHEDA LED QF1 QF2...
Page 123: ......
Page 124: ......
Page 125: ......