6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Specifications
Type
R91
Model
MG. PR.
S. *.
VS.
8.
50.
ES
(1)
(2)
(3)
(4) (5)
(6) (7)
(8)
(9)
(1)BURNER TYPE
R91 - R92 - R93 - R515 - R520 - R525
(2)FUEL
(3)OPERATION
PR - Progressive
MD - Fully modulating
(4)BLAST TUBE
S - standard
L - Extended
(5)DESTINATION COUNTRY
* - see data plate
(6)BURNER VERSION
VS - Short flame
(7)EQUIPMENT
0 = 2 Gas valves
1 = 2 Gas gas proving system 7 = 2 Gas high gas pressure switch
8 = 2 Gas gas proving high gas pressure switchl
(8)GAS CONNECTION
50 = Rp2
65 = DN65
80 = DN80
100 = DN100
(9) GAS CONNECTION
ES = with no O
2
trim control, with no VSD control
EO = with O
2
trim control, with no VSD control
EI = with no O
2
trim control, with VSD control
EK = with O
2
trim control, with VSD control
BURNER TYPE
R91..VS
R92..VS
R93..VS
Output
min. - max. kW
480 - 2670
480 - 3050
550 - 4100
Fuel
Category
see next paragraph ”Gas category”
Gas rate
min - max (Stm
3
/h)
51 - 283
51 - 323
58 - 434
Gas pressure
min.- max. mbar
(see Note 2)
Power supply
400V 3N ~ 50Hz
Total power consumption
kW
4.5
6
8
Electric motor
kW
4
5.5
7.5
Protection
IP40
Approx. weight
kg
320
370
420
Operation
Progressive Fully modulating
Gas Train50
Gas connection
2” / Rp2
2” / Rp2
-
Gas Train65
Gas connection
2”1/2 / DN65
2”1/2 / DN65
2”1/2 / DN65
Gas Train
Gas connection
3” / DN80
3” / DN80
3” / DNN80
Gas Train
Gas connection
4” / DN100
4” / DN100
4” / DN100
Operating temperature
°C
-10 / +50
Storage Temperature
°C
-20 / +60
Working service *
Intermittent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar pressure, 15 °C temperature) and are valid for G20 Natural gas (nett
calorific value: 34.02 MJ/Stm
3
).
Note2:
Maximum gas pressure = 500mbar (with Siemens VGD gas valves).
Minimum gas pressure = see gas curves.
M
G
- Natural gas-Light oil
M
G
- Natural gas-Light oil
Summary of Contents for R91 VS Series
Page 37: ...PART III MAINTENANCE 37...
Page 39: ......
Page 42: ...Annex1 Example for motor cable...
Page 43: ......
Page 44: ...Annex 2 Example for sensor cable...
Page 45: ......
Page 46: ......
Page 50: ......