240/253
Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
18 Addendum 4: LMV52... with O2 trim control and O2 module
11.12.2008
Technical Data
PLL52...
Refer to chapter Technical Data!
Mains voltage «X89-01»
AC 120 V
–15 % / +10 %
AC 230 V
-15 % / +10 %
Safety class
I
with parts according to
II
as per DIN EN 60730-1
Mains frequency
50 / 60 Hz ±6 %
Power consumption
Ca. 4 VA
Ca. 4 VA
Degree of protection
IP54, housing closed
Transformer AGG5.210
-
Primary side
-
Secondary side
AC 120 V
AC 12 V (3x)
Transformer AGG5.220
-
Primary side
-
Secondary side
AC 230 V
AC 12 V (3x)
Storage
DIN EN 60 721-3-1
Climatic conditions
class 1K3
Mechanical conditions
class 1M2
Temperature range
-20...+60 °C
Humidity
< 95 % r.h.
Transport
DIN EN 60 721-3-2
Climatic conditions
class 2K2
Mechanical conditions
class 2M2
Temperature range
-30...+70 °C
Humidity
< 95 % r.h.
Operation
DIN EN 60 721-3-3
Climatic conditions
class 3K5
Mechanical conditions
class 3M2
Temperature range
-20...+60 °C
Humidity
< 95 % r.h.
Condensation, formation of ice or ingress of water are not permitted!
Terminal ratings, cable lengths and cross-
sectional areas
Refer to chapter «Technical Data / LMV5... and AZL5...!»
Cable lengths / cross-sectional areas
Electrical connection «X89»
Screw terminals up to max. 2.5 mm²
Cable lengths
≤
10 m to QGO20...
Cross-sectional areas
Refer to description of QGO20...
Twisted pairs
Analog inputs:
Fresh air temperature detector
Pt1000 / LG-Ni1000
Flue gas temperature detector
Pt1000 / LG-Ni1000
QGO20...
Refer to Data Sheet N7842
Interface
Communication bus for LMV52...
LMV52... basic unit
PLL52...
Environmental conditions
LMV52... basic unit
PLL52...
Summary of Contents for R91 VS Series
Page 37: ...PART III MAINTENANCE 37...
Page 39: ......
Page 42: ...Annex1 Example for motor cable...
Page 43: ......
Page 44: ...Annex 2 Example for sensor cable...
Page 45: ......
Page 46: ......
Page 50: ......