PART I: INSTALLATION
5
DOUBLE STAGE, PROGRESSIVE AND FULLY MODULATING BURNERS
Note: all the gas flow rates (m
3
/h) are referred to standard gas conditions: 1013 mbar pressure, 15° C temperature.
* Minimum pressure required to get the maximum rate with any back-pressure in combustion chamber (referring to the perfor-
mance curves). The burner operates correctly also with lowest pressure only if these are enough to guarantee the necessary
gas rate.
BURNERS TYPE/MODEL
P20 C-....25
P20 C-....40
P30 C-....40/50
P45 C-....40
Input
min. low flame kW
85
85
65
145
min. high flame kW
120
120
100
220
max. kW
230
280
350
520
min. low flame kcal/h
73.100
73.100
55.900
124.700
min. high flame kcal/h
103.200
103.200
86.000
189.200
max. kcal/h
197.800
240.800
301.000
447.200
Fuel
Town gas
Town gas
Town gas
Town gas
Category
I
2h
I
2h
I
2h
I
2h
Gas flow rate min.- max.
(m
3
/h)
21 - 58
21 - 70
16 - 87
36 - 130
Gas pressure min.* - max.
mbar
50 - 200
60 - 200
50 - 200
80 - 200
Power supply
230V - 50Hz
230V - 50Hz
230V - 50Hz
230V - 50Hz
Power consumption
W
650
650
650
900
Electric motor (2800 rpm)
W
370
370
370
620
Protection
IP40
IP40
IP40
IP40
Weight
Kg
30
30
30
58
Gas train size
1”
1”
1/2
1”
1/2
/ 2”
1”
1/2
Gas connections
Rp 1
Rp 1
1/4
Rp 1
1/4
/ Rp1
Rp 1
1/2
Operation
double stage
progressive
fully modulating
double stage
progressive
fully modulating
double stage
progressive
fully modulating
double stage
progressive
fully modulating
Destination country
*
*
*
*
BURNERS TYPE/MODEL
P45 C-....50
P65 C-....50
P65 C-....65
Input
min. low flame kW
145
270
270
min. high flame kW
220
480
480
max. kW
520
970
970
min. low flame kcal/h
124.700
232.200
232.200
min. high flame kcal/h
189.200
412.800
412.800
max. kcal/h
447.200
834.200
834.200
Fuel
Town gas
Town gas
Town gas
Category
I
2h
I
2h
I
2h
Gas flow rate min.- max.
(m
3
/h)
36 - 130
67 - 242
67 - 242
Gas pressure min.* - max.
mbar
60 - 200
120- 200
70 - 200
Power supply
230/400V - 50Hz
230V - 50Hz
230V - 50Hz
Power consumption
W
900
2000
2000
Electric motor (2800 rpm)
W
620
1500
1500
Protection
IP40
IP40
IP40
Weight
Kg
58
150
155
Gas train size
2”
2”
2”
1/2
Gas connections
Rp 2
Rp 2
DN 65
Operation
double stage
progressive
fully modulating
double stage
progressive
fully modulating
double stage
progressive
fully modulating
Destination country
*
*
*
Summary of Contents for P20
Page 30: ...PART II OPERATION 30 Electrical diagram code 18 020 Burners P45 C TN C AB C PR ...
Page 32: ...PART II OPERATION 32 Electrical diagram code 04 622 Burners P20 P30 C MD ...
Page 33: ...PART II OPERATION 33 Electrical diagram 04 642 Burners P45 C MD ...
Page 34: ...PART II OPERATION 34 Electrical diagram code 05 615 Burner P65 C MD ...
Page 35: ...PART II OPERATION 35 SPARE PARTS ...