5
PID parameters set and modifications
(PArA):
Push
Enter
button, on the green display
Opr
appears; using the
down arrow,
scroll until group
PArA
is reached and push
Enter
.
On the green display
Pb1
e appears and on the red one the set parameter. Push is sequence the
down or up
arrow the menu is scrolled.
Push
Enter
to select and the
arrows
to choose the desired value.
Enter
to confirm
(*) Parameters affected by setting of decimal place (
ConF > dISP
parameter
dECP
)
Parameter
Display
Range
Factory
setting
Remarks
Proportional band
Pb1
1… 9999 digit
10
Typical value for temperature
erivative action
dt
0… 9999 sec.
80
Typical value for temperature
Integral action
rt
0… 9999 sec.
350
Typical value for temperature
Т
Dead band
(*)
db
0… 999,9 digit
1
Typical value
Servocontrol
running time
tt
10… 3000 sec.
15
Set servocontrol running time
Switch-on differential (*)
HYS1
0,0… -1999 digit
-5
Value under setpoint below which
the burner switches back on
(1N-1P closes)
Switch-off differential 2° stage
(*)
HYS2
0,0 … HYS3
3
(enable only with parameter bin1 = 4)
Upper switch-off
differential
(*)
HYS3
0,0… 9999 digit
5
Value over setpoint above which the burner
switches off (1N-1P opens)
Switch-on differential on cooling
controller (*)
HYS4
0,0… 9999 digit
5
Do not used
(enable only with parameter
CACt
= 0)
Switch-off differential 2° stage
on cooling controller (*)
HYS5
HYS6…0,0 digit
5
Do not used
(enable only with parameter
CACt
= 0 and parame-
ter
bin1
=0)
Upper switch-off
differential on cooling controller
(*)
HYS6
0,0… -1999 digit
5
Do not used
(enable only with parameter CACt = 0)
Delay modulation
q
0,0… 999,9 digit
0
Do not alter
T Outside temperature Curve
point 1 (*)
At1
-40 ...120 digit
-10
First point of external temperature for climatic curve
Boiler temperature Curve point 1
(*)
Ht1
SPL...SPH
60
Set-point temperature for the external temperature
1
TT Outside temperature Curve
point 2 (*)
At2
-40 ...120 digit
20
Second point of external temperature for climatic
curve
Boiler temperature Curve point 2
(*)
Ht2
SPL...SPH
50
Set-point temperature for the external temperature
2
Summary of Contents for KTP1030
Page 25: ...C I B UNIGAS M039207CB 25 Fig 17 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 46: ...C I B UNIGAS M039207CB 46...
Page 47: ...C I B UNIGAS M039207CB 47...
Page 48: ...C I B UNIGAS M039207CB 48...
Page 49: ...C I B UNIGAS M039207CB 49...
Page 50: ...C I B UNIGAS M039207CB 50 Pumping Unit Electric Wiring Diagrams...
Page 51: ...C I B UNIGAS M039207CB 51...
Page 52: ...C I B UNIGAS M039207CB 52...
Page 55: ...C I B UNIGAS M039207CB 55...
Page 59: ......
Page 74: ......
Page 83: ......
Page 84: ......
Page 85: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 100: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 101: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 102: ...M12927CA MOUNTING 2...
Page 118: ...1 RWF55 5X RWF55 6X User manual M12926CA Rel 0 1 10 2015...
Page 119: ...2 DEVICE INSTALLATION Fixing system Drilling dimensions...
Page 140: ......
Page 141: ...23 Note Specifications and data subject to change Errors and omissions excepted...