• InP
typ.
InP
Input settings
dp.s
lo.s
ofs.
Digital filter on input
(if = 0 excludes averaging filter on
sample value)
(*) not available for TC, RTD,
PTC and NTC scales
Digital filter on input
display
Decimal point position for
input scale
Minimum limit of main
input scale
Maximum limit of main
input scale
Offset correction
of main input
0.0 ... 20.0 sec
0 ... 9.9
scale points
dP_S Format
0
xxxx
1
xxx.x
2
xx.xx (*)
3
x.xxx (*)
min...max input range
selected in tyP
min...max input range
selected in tyP
-999 ... 999
scale points
flt
sp.r
Def. remote setpoint
fld
xi.s
0 default (remote setpoint present)
Max. non-linearity error for
thermocouples (TC),
resistors (PT100) and
thermistors (PTC, NTC).
The error is calculated as
deviation from theoretical
value and is expressed as
percentage of full scale
(in °C).
S, R range 0...1750°C; error < 0.2% f.s. (t > 300°C) / for other
range; error < 0.5% f.s.
T
error < 0.2% f.s. (t > -150°C)
B
range 44...1800°C; error < 0.5% f.s. (t > 300°C) / range
44,0...999,9; error < 1% f.s. (t > 300°C)
U
range -99,9...99,9 and -99...99°C; error < 0.5% f.s. / for other
range; error < 0.2% f.s. (t > -150°C)
G
error < 0.2% f.s. (t > 300°C)
D
error < 0.2% f.s. (t > 200°C)
C
range 0...2300; error < 0.2% f.s. / for other range;
error < 0.5% f.s.
NTC error < 0.5% f.s.
Tc: J, K, E, N, L error < 0,2% f.s.
JPT100 and PTC error < 0,2% f.s.
PT100 scale -200...850°C
Precision better than 0,2% f.s. at 25°C
In range 0...50°C:
• Precision better than 0,2% f.s. in range -200...400°C
• Precision better than 0,4% f.s. in range +400...850°C
(where f.s. refers to range -200... +850°C)
Type
Probe type
without decimal point
with decimal point
Sensore:
TC
0
TC J °C
0/1000
0.0/999.9
1
TC J °F
32/1832
32.0/999.9
2
TC K °C
0/1300
0.0/999.9
3
TC K °F
32/2372
32.0/999.9
4
TC R °C
0/1750
0.0/999.9
5
TC R °F
32/3182
32.0/999.9
6
TC S °C
0/1750
0.0/999.9
7
TC S ° F
32/3182
32.0/999.9
8
TC T °C
-200/400
-199.9/400.0
9
TC T °F
-328/752
-199.9/752.0
28
TC
CUSTOM
CUSTOM
29
TC
CUSTOM
CUSTOM
30
PT100 °C
-200/850
-199.9/850.0
31
PT100 °F
-328/156 2
-199.9/999.9
32
JPT100 °C
-200/600
-199.9/600.0
33
JPT100 °F
-328/1112
-199.9/999.9
34
PTC °C
-55/120
-55.0/120.0
35
PTC °F
-67/248
-67.0/248.0
36
NTC °C
-10/70
-10.0/70.0
37
NTC °F
14/158
14.0/158.0
38
0...60 mV
-1999/9999
-199.9/999.9
39
0...60 mV
Custom scale
Custom scale
40
12...60 mV
-1999/9999
-199.9/999.9
41
12...60 mV
Custom scale
Custom scale
42
0...20 mA
-1999/9999
-199.9/999.9
43
0...20 mA
Custom scale
Custom scale
44
4...20 mA
-1999/9999
-199.9/999.9
45
4...20 mA
Custom scale
Custom scale
46
0...10 V
-1999/9999
-199.9/999.9
47
0...10 V
Custom scale
Custom scale
48
2...10 V
-1999/9999
-199.9/999.9
49
2...10 V
Custom scale
Custom scale
50
0...5 V
-1999/9999
-199.9/999.9
51
0...5 V
Custom scale
Custom scale
52
1...5 V
-1999/9999
-199.9/999.9
53
1...5 V
Custom scale
Custom scale
54
0...1 V
-1999/9999
-199.9/999.9
55
0...1 V
Custom scale
Custom scale
56
200mv..1V
-1999/9999
-199.9/999.9
57
200mv..1V
Custom scale
Custom scale
58 Cust10 V-20mA
-1999/9999
-199.9/999.9
59 Cust10 V-20mA
Custom scale
Custom scale
60
Cust 60mV
-1999/9999
-199.9/999.9
61
Cust 60mV
Custom scale
Custom scale
62
PT100-JPT
CUSTOM
CUSTOM
63
PTC
CUSTOM
CUSTOM
64
NTC
CUSTOM
CUSTOM
Probe type, signal, enable custom linearization,
and main input scale
For custom linearization:
- LO signal is generated with variable below Lo.S or at minimum calibration
value
- HI signal is generated with variable above Lo.S or at maximum calibration
value
+2 Times of pre-heating and gradients of set digit/sec
0
30
0.1
0.5
1
0.0
850.0
0
lo.l
Lower limit for setting SP
and absolute alarms
Lo.S ... Hi.S
Upper limit for setting SP
and absolute alarms
Lo.S ... Hi.S
xi.l
30.0
130.0
5
80379_MHW_600V-T73_06-2012_ENG
Summary of Contents for KTP1030
Page 25: ...C I B UNIGAS M039207CB 25 Fig 17 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 46: ...C I B UNIGAS M039207CB 46...
Page 47: ...C I B UNIGAS M039207CB 47...
Page 48: ...C I B UNIGAS M039207CB 48...
Page 49: ...C I B UNIGAS M039207CB 49...
Page 50: ...C I B UNIGAS M039207CB 50 Pumping Unit Electric Wiring Diagrams...
Page 51: ...C I B UNIGAS M039207CB 51...
Page 52: ...C I B UNIGAS M039207CB 52...
Page 55: ...C I B UNIGAS M039207CB 55...
Page 59: ......
Page 74: ......
Page 83: ......
Page 84: ......
Page 85: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 100: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 101: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 102: ...M12927CA MOUNTING 2...
Page 118: ...1 RWF55 5X RWF55 6X User manual M12926CA Rel 0 1 10 2015...
Page 119: ...2 DEVICE INSTALLATION Fixing system Drilling dimensions...
Page 140: ......
Page 141: ...23 Note Specifications and data subject to change Errors and omissions excepted...