PART IV: MAINTENANCE
32
Flame detection probe
To clean/replace the detection photocell, proceed as follows:
1
Disconnect the system from the electrical power supply.
2
Shut off the fuel supply;
3
remove the photocell from its slot (see next figure);
4
clean the bulbe if dirty, taking care not to touch it with bare hands;
5
if necessary, replace the bulb;
replace the photocell into its slot.
Checking the detection current with electrode (natural gas)
To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of
the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.
Burner service term
- In optimal operating conditions, and with preventive maintenance, the burner can last up to 20 years.
- Upon expiry of the burner service term, it is necessary to carry out a technical diagnosis and, if necessary, an overall repair.
- The burner status is considered to be at its limit if it is technically impossible to continue using it due to non-compliance with safety
requirements or a decrease in performance.
- The owner makes the decision whether to finish using the burner, or replacing and disposing of it based on the actual state of the
appliance and any repair costs.
- The use of the burner for other purposes after the expiry of the terms of use is strictly prohibited.
Seasonal stop
To stop the burner in the seasonal stop, proceed as follows:
1
turn the burner main switch to 0 (Off position)
2
disconnect the power mains
3
close the fuel valve of the supply line
Burner disposal
In case of disposal, follow the instructions according to the laws in force in your country about the “Disposal of materials”.
WIRING DIAGRAMS
Refer to the attached wiring diagrams.
WARNING
1 - Electrical supply 230V / 400V 50Hz 3N a.c.
2 - Do not reverse phase with neutral
3 - Ensure burner is properly earthed
TROUBLESHOOTNG GUIDE
Gas operation
Fig. 7: Detection by photocell QRA..
Control box
Minimum detection signal
Siemens LME7...
70µA (with UV detector)
Summary of Contents for K750A
Page 1: ...M039462NB 0 1 11 2021 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES K750A K890A K990A...
Page 2: ...2 1 CO 2 a a RESET 3 3a...
Page 34: ...34...
Page 35: ......
Page 37: ...LME73 000Ax PME73 831AxBC LME73 831AxBC M12921NB Rel 1 2 02 2016...
Page 41: ...5 Info EK LME73 I LED EK LED 1 2 2 LED tw OFF OK OK T Led Led Led Led Led...
Page 42: ...6 1 515 1 259 01 0...
Page 43: ...7 2 515 1 259 01 0...
Page 48: ...12 2x 23 21 23 F A code Service OEM info enter Info Service enter reset ESC...
Page 49: ...13 Info LME73 Info Service...
Page 52: ...16...
Page 57: ...21 41 42 60 123 140 242 243 244 245 259 01 SO OEM LME73 831AxBC...
Page 58: ......
Page 59: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......