7
BURNER SPECIFICATIONS
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Technical specifications
Note:
the Output values are referred to comburent air temperature lower than 50°C.
Type
HTP91A
Model
MG. PR. S. *. A. 1. 80
(1) (2) (3) (4) (5) (6) (7) (8)
(1) BURNER TYPE
HTP91A
(2) FUEL
M - Natural gas G - Light oil
(3) OPERATION
PR - Progressive MD - Fully modulating
(4) BLAST TUBE
S - Standard
(5) DESTINATION COUNTRY
* - see data plate
(6) BURNER VERSION
A - Standard Y - Special
(7) EQUIPMENT
1 = 2 gas proving system
8 = 2 gas proving maximum pressure switch
(8) GAS CONNECTION
50 = Rp2
65 = DN65
80 = DN80 100 = DN100
BURNER TYPE
HTP90A
HTP91A
HTP92A
HTP93A
Output
min - max kW
320-2300
480 - 2670
480 - 3050
550 - 4100
Fuel
Natural gas - Light oil
Gas category
(see next paragraph)
Gas rate
min.-max. (Stm
3
/h)
34 - 243
51 - 283
51 - 323
58 - 434
Gas pressure
(see Note 2)
Oil viscosity
cSt @ 40°C
2 - 7.4
Oil density
kg/m
3
840
Light oil rate
min.-max. kg/h
27 - 194
40 - 225
40 - 257
46 - 346
Power supply
230V 3~ / 400V 3N~ 50Hz
Pump motor
kW
0.55
1.1
1.1
1.1
Total power consumption
kW
1.05
1.6
1.6
1.6
Protection
IP40
Operation
Progressive - Fully modulating
Gas train 50
ØValves gas /Connection
2” / Rp 2
Gas train 65
ØValves / Connection
2”
1/2
/ DN65
Gas train 80
ØValves / Connection
3” / DN80
Gas train 100
ØValves / Connection
4” / DN100
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Intermittent
Summary of Contents for HTP90A
Page 33: ...33 Fig 16...
Page 54: ...54...
Page 56: ...56...
Page 57: ...57...
Page 58: ......
Page 59: ......
Page 61: ...LME73 000Ax PME73 831AxBC LME73 831AxBC Service instruction manual M12921CB Rel 1 2 02 2016...
Page 83: ...23...
Page 84: ...Note Specifications and data subject to change Errors and omissions excepted...