C.I.B. UNIGAS - M039219CA
17
Pressure adjusting range
The pressure adjusting range, downstream the gas valves group, changes according to the spring provided with the valve group.
Keys
1 spring
2 cap
DUNGS MBC valves:
Siemens VGD valves with SKP actuator:
Once the train is installed, connect electrically all its elements: gas valves group, pressure switches, gas proving system.
Hydraulic diagrams for light oil supplying circuits
DUNGS MBC..SE
Siemens SKP actuator
Performance range (mbar)
4 - 20
20 - 40
40 - 80
80 - 150
Spring colour
-
ed
black
green
Performance range (mbar)
0 - 22
15 - 120
100 - 250
Spring colour
neutral
yellow
red
ATTENTION:
once the gas train is mounted according to the diagram on Fig. 4, the gas proving test mus be performed,
according to the procedure set by the laws in force.