Installation diagram of light oil pipes
PLEASE READ CAREFULLY THE “WARNINGS” CHAPTER AT THE BEGINNING OF THIS MANUAL.
The pumps that are used can be installed both into single-pipe and double-pipe systems.
Single-pipe system:
a single pipe drives the oil from the tank to the pump’s inlet. Then, from the pump, the pressurised oil is driven to
the nozzle: a part comes out from the nozzle while the othe part goes back to the pump. In this system, the by-pass plug, if provided,
must be removed and the optional return port, on the pump’s body, must be sealed by steel plug and washer.
Double-pipe system:
as for the single pipe system, a pipe that connects the tank to the pump’s inlet is used besides another pipe that
connects the pump’s return port to the tank, as well. The excess of oil goes back to the tank: this installation can be considered self-ble-
eding. If provided, the inside by-pass plug must be installed to avoid air and fuel passing through the pump.
Burners come out from the factory provided for double-pipe systems. They can be suited for single-pipe system (recommended in the
case of gravity feed) as decribed before.To change from a 1-pipe system to a 2-pipe-system, insert the by-pass plug
G
(as for ccw-rota-
tion- referring to the pump shaft).
Caution:
Changing the direction of rotation, all connections on top and side are reversed.
Bleed
Bleeding in two-pipe operation is automatic : it is assured by a bleed flat on the piston. In one-pipe operation, the plug of a pressure
gauge port must be loosened until the air is evacuated from the system.
About the use of fuel pumps
Make sure that the by-pass plug is not used in a single pipe installation, because the fuel unit will not function properly and damage
to the pump and burner motor could result.
Do not use fuel with additives to avoid the possible formation over time of compounds which may deposit between the gear teeth,
thus obstructing them.
After filling the tank, wait before starting the burner. This will give any suspended impurities time to deposit on the bottom of the
tank, thus avoiding the possibility that they might be sucked into the pump.
On initial commissioning a "dry" operation is foreseen for a considerable length of time (for example, when there is a long suction
Fig. 17 - Double-pipe system
The burner is supplied with filter and flexible hoses, all the parts upstream the filter and downstream the return flexible hose, must be
installed by the customer. As far as the hoses connection, see the related paragraph.
Key
1
Burner
2
Flexible hoses (fitted)
3
Light oil filter (fitted)
4
Automatic interceptor (*)
5
One-way valve (*)
6
Gate valve
7
Quick-closing gate-valve (outside the tank or boiler rooms)
(*) Only for installations with gravity, siphon or forced
circulation feed systems. If the device installed is a
solenoid valve, a timer must be installed to delay the
valve closing.
The direct connection of the device without a timer
may cause pump breaks.
Suntec TA
Suntec T
From tank
To tank
G
G