C.I.B. UNIGAS
- M039213CB
13
MOUNTINGS AND CONNECTIONS
Packing
The burners are despatched wooden cages whose dimensions:
9xA series: 1730mm x 1280mm x 1020mm (L x P x H)
5xxA series:
1720mm x 1500mm x 1150mm (L x P x H)
525A series:
1800mm x 1500mm x 1300mm (L x P x H)
Packing cases of this kind are affected by humidity and are not suitable for stacking. The fol-
lowing are placed in each packing case:
To get rid of the burner’s packing, follow the procedures laid down by current laws on disposal of
materials
Handling the burner
The burner is mounted on a stirrup provided for handling the burner by means of a fork lift truck: the forks must be inserted into the A
anb B ways. Remove the stirrup only once the burner is installed to the boiler.
The burner is designed to work positioned according to the picture below. For different installations, please contact the Technical
Department.
Fitting the burner to the boiler
To install the burner into the boiler, proceed as follows:
1
make a hole on the closing door of the combustion chamber as described on paragraph “Overall dimensions”)
2
place the burner to the boiler: lift it up and handle it according to the procedure described on paragraph “Handling the burner”;
3
place the 4 stud bolts (5), according to the burner’s drilling plate described on paragraph “Overall dimensions”;
4
fasten the 4 stud bolts;
5
place the ceramic fibre plait on the burner flange;
6
install the burner into the boiler;
7
fix the burner to the stud bolts, by means of the fixing nuts, according to the next picture.
8
After fitting the burner to the boiler, ensure that the gap between the blast tube and the refractory lining is sealed with appropriate
insulating material (ceramic fibre cord or refractory cement).
ATTENTION! The lhandling operations must be carried out by specialised and trained personnel. If these opera-
tions are not carried out correctly, the residual risk for the burner to overturn and fall down still persists.
To move the burner, use means suitable to support its weight (see paragraph “Technical specifications”).
The unpacked burner must be lifted and moved only by means of a fork lift truck.
H
P
L
A
B
SIDE UP
SIDE
DOWN
Summary of Contents for HR93A
Page 45: ...C I B UNIGAS M039213CB 45...