PART III: OPERATION
42
7.1
Oil Flow Rate Settings
1
Once the air and gas flow rates are adjusted, turn the burner off, switch to the oil operation (OIL, on the burner control panel).
2
with the electrical panel open, prime the oil pump acting directly on the related
CP
contactor (see next picture): check the pump
motor rotation and keep pressing for some seconds until the oil circuit is charged;
3
bleed the air from the
M
pressure gauge port (Fig. 25) by loosing the cap without removing it, then release the contactor.
Fig. 26
4
As for setting the fuel/air ratio curve, see the LMV related manual.
5
Only if necessary, adjust the supply pressure as follows (see related paragraph); insert a pressure gauge into the port shown on
Fig. 26 and act on on the pump adjusting screw
VR
(see Fig. 25) as to get the nozzle pressure at 20bar (Monarch or Fluidics noz-
zles - see page 38-38).
6
In order to get the maximum oil flow rate, adjust the pressure (reading its value on the
PG
pressure gauge) without changing the air
flow rate set during the gas operation adjustments (see previous paragraph), checking always the combustion parameters.
Turn the burner off; then start it up again. If the adjustment is not correct, repeat the previous steps.
7.2 Maximum oil pressure switch
The oil pressure switch on the return line, checks that the pressure does not exceed a default
value. This value must not be higher than the maximum acceptable pressure on the return line
(this value is reported on the specification table). A pressure change on the return line could
affect the combustion parameters: for this reason, the pressure switch must be set, say, at 20%
over the pressure recorded during the combustion adjustment.
It is recommended to verify that the combustion parameters are within the range of acceptable
values even against a pressure variation that gets close to the limit of the pressure switch
This check should be carried out along the whole range of the burner output.
In case of inacceptable values, reduce from 20% to 15% the overpressure; later on, repeat the
adjustments described above.
Suntec E7
Suntec TA.
HP Technik UHE
Fig. 27
Fig. 28
CP
VR
M
VR
M
VR
M
Pressure gauge port
PG