5
PID parameters set and modifications
(PArA):
Push
Enter
button, on the green display
Opr
appears; using the
down arrow,
scroll until group
PArA
is reached and push
Enter
.
On the green display
Pb1
e appears and on the red one the set parameter. Push is sequence the
down or up
arrow the menu is scrolled.
Push
Enter
to select and the
arrows
to choose the desired value.
Enter
to confirm
(*) Parameters affected by setting of decimal place (
ConF > dISP
parameter
dECP
)
Parameter
Display
Range
Factory
setting
Remarks
Proportional band
Pb1
1… 9999 digit
10
Typical value for temperature
erivative action
dt
0… 9999 sec.
80
Typical value for temperature
Integral action
rt
0… 9999 sec.
350
Typical value for temperature
Т
Dead band
(*)
db
0… 999,9 digit
1
Typical value
Servocontrol
running time
tt
10… 3000 sec.
15
Set servocontrol running time
Switch-on differential (*)
HYS1
0,0… -1999 digit
-5
Value under setpoint below which
the burner switches back on
(1N-1P closes)
Switch-off differential 2° stage
(*)
HYS2
0,0 … HYS3
3
(enable only with parameter bin1 = 4)
Upper switch-off
differential
(*)
HYS3
0,0… 9999 digit
5
Value over setpoint above which the burner
switches off (1N-1P opens)
Switch-on differential on cooling
controller (*)
HYS4
0,0… 9999 digit
5
Do not used
(enable only with parameter
CACt
= 0)
Switch-off differential 2° stage
on cooling controller (*)
HYS5
HYS6…0,0 digit
5
Do not used
(enable only with parameter
CACt
= 0 and parame-
ter
bin1
=0)
Upper switch-off
differential on cooling controller
(*)
HYS6
0,0… -1999 digit
5
Do not used
(enable only with parameter CACt = 0)
Delay modulation
q
0,0… 999,9 digit
0
Do not alter
T Outside temperature Curve
point 1 (*)
At1
-40 ...120 digit
-10
First point of external temperature for climatic curve
Boiler temperature Curve point 1
(*)
Ht1
SPL...SPH
60
Set-point temperature for the external temperature
1
TT Outside temperature Curve
point 2 (*)
At2
-40 ...120 digit
20
Second point of external temperature for climatic
curve
Boiler temperature Curve point 2
(*)
Ht2
SPL...SPH
50
Set-point temperature for the external temperature
2
Summary of Contents for G258A
Page 46: ......
Page 47: ......
Page 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 3 01 2017...
Page 56: ...8 Parameters level heating engineer...
Page 98: ...50 ERROR CODE TABLE...
Page 99: ...51...
Page 100: ...52...
Page 101: ...53...
Page 102: ...54...
Page 103: ...55...
Page 104: ...56...
Page 105: ...57...
Page 106: ...58...
Page 107: ...59...
Page 108: ...60...
Page 109: ...61...
Page 110: ...62...
Page 111: ...63...
Page 112: ...64...
Page 117: ......
Page 118: ......
Page 119: ......
Page 134: ......
Page 143: ......
Page 144: ......
Page 145: ...MANUAL FOR OPERATION AND CALIBRATION MODULATOR SIEMENS RWF 40 M12905CH Rev 07 11 09...
Page 161: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 176: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 177: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 178: ...M12927CA MOUNTING 2...
Page 194: ...1 RWF55 5X RWF55 6X User manual M12926CA Rel 0 1 10 2015...
Page 195: ...2 DEVICE INSTALLATION Fixing system Drilling dimensions...
Page 216: ......
Page 217: ...23 Note Specifications and data subject to change Errors and omissions excepted...