7
ConF > OutP (parameter under group only for RWF50.3)
Parameter Value
Description
FnCt
tipo di controllo
1
4
1 = analog input 1 doubling with possibility to convert
(depending on par
SiGn
)
4 = modulation controller
SiGn
type of output signal
0
1
2
physical output signal (terminals A+, A-)
0 = 0÷20mA
1 = 4÷20mA
2 = 0÷10V
rOut
Value when out of
input range
0
…101
signal (in percent) when measurement range is crossed
oPnt
zero point
-1999…
0
..+9999
value range of the output variable is assigned to a physical
output signal Per default, the setting corresponds to 0...100%
angular positioning for the controller outputs (terminals A+, A-)
(effective only with
FnCt
= 1)
End
End value
-1999…
100
..+9999
value range of the output variable is assigned to a physical
output signal Per default, the setting corresponds to 0...100%
angular positioning for the controller outputs (terminals A+, A-)
(effective only with
FnCt
= 1)
(
bold
= factory settings)
ConF > binF
Parameter Value
Description
bin1
digital inputs
(terminals DG - D1)
0
1
2
4
0 = without function
1 = set-point changeover (SP1 / SP2)
2 = set-point shift (
Opr
>
dSP
parameter = value of set-point
modify)
4 = changeover of operating mode
open – modulating operation;
close – 2 stage operation.
(
bold
= factory settings)
ConF > dISP
Parameter Value
Description
diSU
upper display
(red)
0
1
4
6
7
display value for upper display:
0 = display power-off
1 = analog input value
4 = Controller’s angular positioning
6 = set-point value
7 = end value with thermal shock protection
diSL
lower display
(green)
0
1
4
6
7
display value for lower display:
0 = display power-off
1 = analog input value
4 = Controller’s angular positioning
6 = set-point value
7 = end value with thermal shock protection
tout
timeout 0..
180
..250
time (s) on completion of which the controller returns
automatically to the basic display, if no button is pressed
dECP
decimal point
0
1
2
0 = no decimal place
1 = one decimal place
2 = two decimal places
CodE
level lockout
0
1
2
3
0 = no lockout
1 = configuration level lockout (ConF)
2 = Parameter and configuration level lockout (PArA & ConF)
3 = keyboard lockout
(
bold
= factory settings)
Summary of Contents for G258A
Page 46: ......
Page 47: ......
Page 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 3 01 2017...
Page 56: ...8 Parameters level heating engineer...
Page 98: ...50 ERROR CODE TABLE...
Page 99: ...51...
Page 100: ...52...
Page 101: ...53...
Page 102: ...54...
Page 103: ...55...
Page 104: ...56...
Page 105: ...57...
Page 106: ...58...
Page 107: ...59...
Page 108: ...60...
Page 109: ...61...
Page 110: ...62...
Page 111: ...63...
Page 112: ...64...
Page 117: ......
Page 118: ......
Page 119: ......
Page 134: ......
Page 143: ......
Page 144: ......
Page 145: ...MANUAL FOR OPERATION AND CALIBRATION MODULATOR SIEMENS RWF 40 M12905CH Rev 07 11 09...
Page 161: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 176: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 177: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 178: ...M12927CA MOUNTING 2...
Page 194: ...1 RWF55 5X RWF55 6X User manual M12926CA Rel 0 1 10 2015...
Page 195: ...2 DEVICE INSTALLATION Fixing system Drilling dimensions...
Page 216: ......
Page 217: ...23 Note Specifications and data subject to change Errors and omissions excepted...