PART I: SPECIFICATIONS
6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Fuel
The burner technical specifications, described in this manual, refer to natural gas (calorific net value Hi = 9.45 kWh/Stm
3
, density
ρ
=
0.717 Kg/Stm
3
) and LPG (calorific net value Hi = 26.79 kWh/Stm
3
, density
ρ
= 2.151 Kg/Stm
3
). For different fuel such as town gas and
biogas, multiply the values of flow and pressure by th corrective factors shown in the table below.
For example, to obtain the flow and pressure values for the biogas:
Type
E115X
Model
M-.
MD. SR.
*.
A.
1.
80.
EA
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
1
BURNER TYPE
E115X, E150X, E180X
2
FUEL
M - Natural gas
L - LPG
B - Biogas
C - Town gas
3
OPERATION (Available versions)
PR - Progressive
MD - Fully modulating
4
BLAST TUBE AND AIR INLET CONFIGURATION
(see the figure on page 5)
SR = Standard blast tube + ABS polymer (silenced) air intake
SP = Standard blast tube + aluminium air intake
LR = Extended blast tube + ABS polymer (silenced) air intake
LP = Extended blast tube + aluminium air intake
5
DESTINATION COUNTRY
* - see data plate
6
BURNER VERSION
A - Standard
Y - Special
7
EQUIPMENT
0 = 2 gas valves
1 = 2 gas gas proving system
7 = 2 gas maximum gas pressure switch
8 = 2 gas gas proving maximum gas pressure switch
8
GAS CONNECTION
see Specifications
40 = Rp1 1/2
50 = Rp2
65 = DN65
80 = DN80
9
MICRO-PROCESSOR CONTROL
EA = micro-processor control, without inverter
EB = micro-processor control, with inverter
EC = micro-processor control, without inverter
Fuel
Hi
(KWh/Stm
3
)
ρ
(kg/Stm
3
)
f
Q
f
p
Town gas
4,88
0,6023
1,936
3,3
Biogas
6,395
1,1472
1,478
3,5
LPG
26,79
2,151
0,353
0,4
ATTENTION! The combustion head type and the settings depend on the fuel. The burner must be used only for its
intended purpose specified in the burner data plate .
ATTENTION: the corrective factors in the above table depend on the gas composition, so on the calorifc value and
the density of the gas. The above value can be taken only as reference.
Q
biogas
Q
naturalGas
1 478
=
p
biogas
p
naturalGas
3 5
=
Summary of Contents for E150X
Page 43: ......
Page 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 52: ...8 Parameters level heating engineer...
Page 94: ...50 ERROR CODE TABLE...
Page 95: ...51...
Page 96: ...52...
Page 97: ...53...
Page 98: ...54...
Page 99: ...55...
Page 100: ...56...
Page 101: ...57...
Page 102: ...58...
Page 103: ...59...
Page 104: ...60...
Page 105: ...61...
Page 106: ...62...
Page 107: ...63...
Page 108: ...64...
Page 113: ......
Page 114: ......
Page 115: ......