System Operation 

9.1

 

Typical Startup for Continuous Pilot (or Main Direct Ignition) 

 

1.

 

Power Up, verify that POWER LED is ON 
and 

after 

short 

pause 

the 

STANDBY/PURGE  LED  is  ON  and  the 
Flame  Rod  (FR)  output  is  energized 
enabling  flame  detection.  FR  remains 
on at all times. 

Outputs: 

FR 

IGN 

DO1 

DO2 

DO3 

 

2.

 

If  the  FLAME LED  is  ON  all  requests  to 
start  the  system  will  be  ignored  until 
the flame is removed. 

 

FR 

IGN 

DO1 

DO2 

DO3 

 

3.

 

If the FAULT LED is ON the system is in 
lockout,  presss  START/RESET  to  reset 
the system or cycle the power. 

 

FR 

IGN 

DO1 

DO2 

DO3 

 

4.

 

With FAULT and FLAME OFF the system 
can  be  started  by  pressing  the 
START/RESET  button.  The  PURGE 
commences  with  the  STANDBY/PURGE 
LED flashing. 

 

FR 

IGN 

DO1 

DO2 

DO3 

 

5.

 

Press START/RESET at any time to reset 
the  system.  STANDBY/PURGE  stops 
flashing. 

 

FR 

IGN 

DO1 

DO2 

DO3 

 

Summary of Contents for SUPERVISOR I

Page 1: ...0014_Installation_Operation_Manual A0 www unifire ca support unifire ca Copyright 2017 Unifire SUPERVISOR I Installation and Operation Manual...

Page 2: ...9 MAIN FLAME STABILIZATION PERIOD 0 1 10SECONDS 9 6 10 PILOT FLAME FAILURE RESPONSE TIME 0 1 4SECONDS 9 6 11 MAIN FLAME FAILURE RESPONSE TIME 0 1 4 SECONDS 9 6 12 PILOT RECYCLE RETRIAL NUMBER 0 255 9...

Page 3: ...n manuals HAZARD A specific hazard is brought to the attention of the reader Failure to observe these instructions may result in injury or other high severity consequence CAUTION Important information...

Page 4: ...strict product liability for any losses damages costs inconveniences and expenses direct or indirect arising from the use of the product or from defects in workmanship or materials This warranty appli...

Page 5: ...lease contact the Unifire support team using your preferred method below Please include the serial number on the label of the Supervisor I module in your communications to allow us to help you as quic...

Page 6: ...ng light off and once the burner s are in operation the permissive inputs continue to provide a trip mechanism for safe shutdown of the appliance With all permissive inputs proven a factory configured...

Page 7: ...ure 60 C Power Supply 24VDC Quiescent Current TBD Inputs AI TC DI1 DI2 DI3 DO2 DO3 4 20mA Analogue Process Input Thermocouple Type K 50 C 1200 C 12 24VDC Process Permissive 12 24VDC Start Reset 12 24V...

Page 8: ...Source TC FR DI3 If not configured for direct ignition the input to use for the pilot flame safeguard is selected from the TC thermocouple FR Flame Rod or DI3 Flame Scanner inputs 6 5 Pilot Trial for...

Page 9: ...not successful the module will adopt the lock out state unless recycle retrials are configured 6 12 Pilot Recycle Retrial Number 0 255 If permitted by the governing codes of the end user jurisdiction...

Page 10: ...nsmitter Enable Disable The AI input may be used as a fuel pressure transmitter When enabled the transmitter high and low trip setpoints shall be monitored during light off Typically the transmitter w...

Page 11: ...s to prevent damage to the enclosure Figure 1 Dimensions Mounting Kit Small Brackets Medium Brackets Large Brackets Unless requested at the point of ordering the module shall not come pre drilled for...

Page 12: ...s head screws that fasten the baseplate to the enclosure body CAUTION The internal electronics are sensitive to static discharge Care must be taken when handling the electronics to avoid exposure to s...

Page 13: ...d 3 2 GND4 Appliance Ground 4 For connecting to appliance ground Separated from the 0VDC of the module Reserved Reserved Reserved Reserved Reserved Discrete 24VDC Input for connection to process trips...

Page 14: ...an be checked with a multi meter without removing the boards from the enclosure Figure 5 Fuse Test Points To replace fuses it is recommended that the electronics assembly is removed from the enclosure...

Page 15: ...d box Load box field jumper 0VDC FR BRN IGN COM DO2 DO2 COM DO3 DO3 COM DO1 COM COMM1 COMM1 COM COMM2 COMM2 COM DI1 DI2 DI3 24VDC TC TC COM 24VDC max 24mA AI COM reserved 24VDC 24VDC graphic overlay P...

Page 16: ...at all times Outputs FR IGN DO1 DO2 DO3 2 If the FLAME LED is ON all requests to start the system will be ignored until the flame is removed FR IGN DO1 DO2 DO3 3 If the FAULT LED is ON the system is i...

Page 17: ...nd the Ignition IGN output is de energized FR IGN DO1 DO2 DO3 8 On expiry of the flame stable timer the DO2 and DO3 outputs are Energized The system now monitors for flame continuously until STANDBY R...

Page 18: ...me is detected the FLAME LED is held ON and the Ignition IGN output is de energized FR IGN DO1 DO2 DO3 5 On expiry of the flame stable timer the DO2 and DO3 outputs are Energized FR IGN DO1 DO2 DO3 6...

Page 19: ...tton to reset the system Power cycling the module also resets the system In the lock out state all outputs are de energized except for the Flame Rod FR The FAULT LED will flash a number of times that...

Page 20: ...Thermocouple input trip TAHH 6 AI PALL Low Pressure Trip on the AI Input 7 AI PAHH High Pressure Trip on the AI Input 8 DI Input failure Internal hardware software diagnostic indicates failure of DI1...

Page 21: ...0014_Installation_Operation_Manual Draft www unifire ca support unifire ca Page 21 of 22 Copyright 2017 Unifire 10 Troubleshooting To follow...

Page 22: ...0014_Installation_Operation_Manual Draft www unifire ca support unifire ca Page 22 of 22 Copyright 2017 Unifire END OF MANUAL...

Reviews: