Unifire SUPERVISOR I Installation And Operation Manual Download Page 13

 

0014_Installation_Operation_Manual 

Draft 

 

www.unifire.ca

 

 

support@unifire.ca

  

Page 13 of 22 

 

 

Copyright 2017 Unifire 

 

 

The  module  includes  a  field  interface  board  to  which  all  field  connections  are  made.  Connections 
available are as follows. 
 
 

Connection Terminal ID

Function

Specification

1 24V_1

24VDC Input

2 24V_2

24VDC Input

3 0V_1

0VDC Input

4 0V_2

0VDC Input

X801
X802

1 AI+

4-20mA +ve

2 AI-

4-20mA -ve

3 SHLD

4-20mA Shield

1 TC+

Type K +

2 TC-

Type K -

3 SHLD

Type K Shield

1 COMM1+
2 COMM1-
3 SHLD
1 24VDC+

24VDC Source

2 DI1

Process switch input

1 24VDC+

24VDC Source

2 DI2

Start/Reset Input

1 n/a
2 n/a
1 24VDC+

24VDC Source

2 DI3

Flame Scanner Input

1 COMM2+
2 COMM2-
3 SHLD
1 DO1

Pilot Solenoid Drive

2 COM

Pilot Solenoid Return

1 24VDC+

24VDC Source

2 DO2+

DO2 Source Power

3 DO2

DO2 Status Output

4 COM

DO2 Status Return

1 IGN

Ignition Drive

2 COM

Ignition Return

1 24VDC+

24VDC Source

2 DO3+

DO3 Source Power

3 DO3+

DO3 Status Output

4 COM

DO3 Status Return

1 FR

Flame Rod Signal

2 BRNGND Burner Ground
1 GND1

Appliance Ground 1

2 GND2

Appliance Ground 2

1 GND3

Appliance Ground 3

2 GND4

Appliance Ground 4

For connecting to appliance ground. Separated 
from the 0VDC of the module.

Reserved
Reserved

Reserved
Reserved
Reserved

Discrete 24VDC Input for connection to process 
trips. Max 12-24VDC 3A.
Discrete 24VDC Input for START/RESET command. 
Max 12-24VDC 3A.

Discrete 24VDC Input for Flame Scanner status. Max 
12-24VDC 3A.

SW800

Factory Wired

X812

X815

X816

X814

X807

X808

X809

X810

X811

Output Driver for Pilot Solenoid (or Main in direct 
ignition mode). 24VDC @ 3A or low power mode.
Output Driver for status on proven flame. 24VDC @ 
3A. DO2+ can be jumpered to board 24VDC+ source 
or externally sourced. 

24VDC 3A Ignition output for connection to ignition 
transformer.
Output Driver for status on proven flame. 24VDC @ 
3A. DO2+ can be jumpered to board 24VDC+ source 
or externally sourced. 

150V Flame rod signal. Connect to flame ionization 
rod, connect BRNGND to burner.

Terminals are connected on the board. Providing 
redundant 24VDC connection point.
Terminals are connected on the board to provide 
redundant 0VDC connection point.

Factory wired
Factory wired

Reserved

4-20mA input for connection to process transmitter 
or gas pressure transmitter.
24VDC Loop power.
Type K Thermocouple Input

X813

X800

X803

X804

X805

X806

 

 

Figure 4 - Field Interface Board Connections

Summary of Contents for SUPERVISOR I

Page 1: ...0014_Installation_Operation_Manual A0 www unifire ca support unifire ca Copyright 2017 Unifire SUPERVISOR I Installation and Operation Manual...

Page 2: ...9 MAIN FLAME STABILIZATION PERIOD 0 1 10SECONDS 9 6 10 PILOT FLAME FAILURE RESPONSE TIME 0 1 4SECONDS 9 6 11 MAIN FLAME FAILURE RESPONSE TIME 0 1 4 SECONDS 9 6 12 PILOT RECYCLE RETRIAL NUMBER 0 255 9...

Page 3: ...n manuals HAZARD A specific hazard is brought to the attention of the reader Failure to observe these instructions may result in injury or other high severity consequence CAUTION Important information...

Page 4: ...strict product liability for any losses damages costs inconveniences and expenses direct or indirect arising from the use of the product or from defects in workmanship or materials This warranty appli...

Page 5: ...lease contact the Unifire support team using your preferred method below Please include the serial number on the label of the Supervisor I module in your communications to allow us to help you as quic...

Page 6: ...ng light off and once the burner s are in operation the permissive inputs continue to provide a trip mechanism for safe shutdown of the appliance With all permissive inputs proven a factory configured...

Page 7: ...ure 60 C Power Supply 24VDC Quiescent Current TBD Inputs AI TC DI1 DI2 DI3 DO2 DO3 4 20mA Analogue Process Input Thermocouple Type K 50 C 1200 C 12 24VDC Process Permissive 12 24VDC Start Reset 12 24V...

Page 8: ...Source TC FR DI3 If not configured for direct ignition the input to use for the pilot flame safeguard is selected from the TC thermocouple FR Flame Rod or DI3 Flame Scanner inputs 6 5 Pilot Trial for...

Page 9: ...not successful the module will adopt the lock out state unless recycle retrials are configured 6 12 Pilot Recycle Retrial Number 0 255 If permitted by the governing codes of the end user jurisdiction...

Page 10: ...nsmitter Enable Disable The AI input may be used as a fuel pressure transmitter When enabled the transmitter high and low trip setpoints shall be monitored during light off Typically the transmitter w...

Page 11: ...s to prevent damage to the enclosure Figure 1 Dimensions Mounting Kit Small Brackets Medium Brackets Large Brackets Unless requested at the point of ordering the module shall not come pre drilled for...

Page 12: ...s head screws that fasten the baseplate to the enclosure body CAUTION The internal electronics are sensitive to static discharge Care must be taken when handling the electronics to avoid exposure to s...

Page 13: ...d 3 2 GND4 Appliance Ground 4 For connecting to appliance ground Separated from the 0VDC of the module Reserved Reserved Reserved Reserved Reserved Discrete 24VDC Input for connection to process trips...

Page 14: ...an be checked with a multi meter without removing the boards from the enclosure Figure 5 Fuse Test Points To replace fuses it is recommended that the electronics assembly is removed from the enclosure...

Page 15: ...d box Load box field jumper 0VDC FR BRN IGN COM DO2 DO2 COM DO3 DO3 COM DO1 COM COMM1 COMM1 COM COMM2 COMM2 COM DI1 DI2 DI3 24VDC TC TC COM 24VDC max 24mA AI COM reserved 24VDC 24VDC graphic overlay P...

Page 16: ...at all times Outputs FR IGN DO1 DO2 DO3 2 If the FLAME LED is ON all requests to start the system will be ignored until the flame is removed FR IGN DO1 DO2 DO3 3 If the FAULT LED is ON the system is i...

Page 17: ...nd the Ignition IGN output is de energized FR IGN DO1 DO2 DO3 8 On expiry of the flame stable timer the DO2 and DO3 outputs are Energized The system now monitors for flame continuously until STANDBY R...

Page 18: ...me is detected the FLAME LED is held ON and the Ignition IGN output is de energized FR IGN DO1 DO2 DO3 5 On expiry of the flame stable timer the DO2 and DO3 outputs are Energized FR IGN DO1 DO2 DO3 6...

Page 19: ...tton to reset the system Power cycling the module also resets the system In the lock out state all outputs are de energized except for the Flame Rod FR The FAULT LED will flash a number of times that...

Page 20: ...Thermocouple input trip TAHH 6 AI PALL Low Pressure Trip on the AI Input 7 AI PAHH High Pressure Trip on the AI Input 8 DI Input failure Internal hardware software diagnostic indicates failure of DI1...

Page 21: ...0014_Installation_Operation_Manual Draft www unifire ca support unifire ca Page 21 of 22 Copyright 2017 Unifire 10 Troubleshooting To follow...

Page 22: ...0014_Installation_Operation_Manual Draft www unifire ca support unifire ca Page 22 of 22 Copyright 2017 Unifire END OF MANUAL...

Reviews: