Installation 

 

Control box physical installation  

Installation must be made in compliance with electrical norms valid in each specific country; in France norm NF-C 
15-100 or in Europe norm HD 384-7-702 must be applied. More in general, please refer to local equivalent 
regulations. 

Control box must be installed in a technical room and not exposed to ice or very cold weather. The place must be 
protected from rain and from direct sun exposure; it must be placed far from heat sources and from water. 

It must be installed at the right height from floor, ideally between 1.2 and 1.5-meter, vertical position, cable glands 
towards the floor; wall must be flat enough to bear the weight of the control box. 

Control box positioning and drilling: 

1. 

Mark on the wall the four positions corresponding to the four external holes in the corners of the box; you 
can use the drilling position template paper which is included with the package. 

 

Fig.1 – External holes position 

WARNING : 

Not respecting this recommendation will make the warranty void. 

 

2. 

Drill four holes on the mounting wall surface. 

3. 

Insert four plastic anchors nylon polyamide (M6x30) tightly inside the holes. 

4. 

Screw the control box onto the wall (screw – VBA TF 4x30 INOX A4) 

 

 

 

WARNING

 

FOR YOUR SECURITY

 – Installation must be performed by an authorized and trained technician following NF-C 

18-510 or EN 50110-1. 

Definition of a qualified installation technician as per NF C 18-510: « professional having a proven technical 
culture, knowledge and experience and training in electricity allowing him to analyse electrical risks thus avoiding 
related dangers ».

 

Summary of Contents for AN1244

Page 1: ...www unicum tech User and Installation Manual KEEP THIS MANUAL FOR FUTURE REFERENCE DATE VERSION MODIFICATIONS 08 2020 01 AN1244A AN1274A 05 2021 02 Modifications alarms SWx WARNING Basic safety rules...

Page 2: ...be performed by a qualified and authorized technician who has been trained to swimming pool equipment installation Before installing this product please read the whole user manual and follow all instr...

Page 3: ...from sensors Auxiliary Relay for electrolyser or pump management One digit display for alarm notification and troubleshooting FUSES CARACHTERISTICS AN1244 F1 Fuse ATO 10A F2 Fuse 5x20 3 15A Time lag A...

Page 4: ...weight of the control box Control box positioning and drilling 1 Mark on the wall the four positions corresponding to the four external holes in the corners of the box you can use the drilling positi...

Page 5: ...ection identification on the key switch Positions and rotation directions must be clearly identified on the key switch and must remain understand all along cover pool lifetime Fig 3 Example of identif...

Page 6: ...green cable can be used only for ground connection Do not forget to screw cable glands when wiring is done this guarantees correct waterproof level WARNING All electrical connections have to be made...

Page 7: ...e3 For TT operating conditions the circuit must be protected upstream by a bipolar differential circuit breaker with a sensitivity of 30 mA 6 A intensity and a type C trigger curve Use a cable H07 VV...

Page 8: ...mmon COM and contacts normally closed NC normally open NO Mode Pool cover position Etat du relais Led AUX Automatic Completely open NO Moving NC Completely closed NC Manual Depending on motor rotation...

Page 9: ...chapter 3 6 and verify that motor rotation sensor is coherent with three position key switch settings ATTENTION in FORCED mode sensor signal is not taken into account it is therefore possible to move...

Page 10: ...ntrol box has been conceived and sized in order to work continuously up to 10 minutes maximum Beyond this time try to let the board at rest for half an hour to allow components cooling down Temperatur...

Page 11: ...mit switch programming to be done Fix Unused Blinking Unused Fix Safety loop open Blinking Sensor defect Fix Sensor power supply problem Blinking Unused Fix Fuse F1 to be replaced Blinking Important A...

Page 12: ...r eyes and survey while moving the cover This mode allows a normal usage of the cover with automatic stop when limit switch is reached In this mode cover can be controlled by different devices key swi...

Page 13: ...tting is OFF micro switch 1 on SW1 set to OFF corresponding to hold mode for close device This function is inactive when control box is in MANUAL or PROGRAMMATION even if the dip switch is set to ON M...

Page 14: ...ctivated with micro switch 3 on SW1 External device has to be equipped with a contact normally closed which opens in case of abnormal condition thus blocking the motor In this case INFO ALARM display...

Page 15: ...mede force INFO ALARM display will show fix This alarm is risen just for information 4 7 Software defect INFO ALARM display will show fix In this case switch off completely the control board wait 5 se...

Page 16: ...y safe way 5 1 Maintenance Control box doesn t need special maintenance User is invited to check periodically the status of control devices especially for remotes Replace any control device when they...

Page 17: ...r normal usage corresponding to a maximum continuous usage of 10 minutes Beyond this time please wait half an hour for cooling board components Warranty is not applicable in the following cases Replac...

Reviews: