Unicont SPb Ltd
Technical Documentation CH-105
Page 8
Safety precautions:
-
Do not allow the device to get into water, as well as ingress of water inside the
device.
-
When cleaning the device surface do not use organic solvents to exclude damage of
marks and inscriptions.
DO NOT:
-
tense the cables connected to
ABC
;
-
connect
ABC
to networks with parameters different from the ones specified in the
present Manual;
-
use the device against its intended use;
-
operate faulty device.
5.2.2.
Connection of AB to ABC
Connect the cable of accumulator battery to terminal "BATTERY" of ABC.
Figure 3 Diagram of AB connection to ABC
Table 3 Cross-section of ABC terminals
Designation of
terminal
BATTERY
Output
24 V DC
Input
AU-106
TS
Remote/Bat_control
Wire cross-section
16 mm
2
6 mm
2
1.5 mm
2
5.2.3.
Connection of Additional Devices to ABC:
Besides the accumulator battery the following devices can be connected to battery
charger:
– thermal sensor DTS-135
– alarm unit AU-106
– remote-control unit UCB-91
Thermal sensor DTS-135 is intended for checking the temperature of charged battery. It
is recommended to use the thermal sensor as part of ABC with helium batteries. Temperature
sensor DTS-135 is connected to terminal "TS" of ABC (refer to Figure 4).
Alarm unit AU-106 is intended to inform the navigator that
ABC is in alarm
mode by
means of visual and sound signal and it is used when
ABC
is installed inside the panel or in the
rooms remote from the bridge (refer to Para 7) Alarm unit AU-106 is connected to terminal
"AU-106" of ABC (refer to Figure 4).