Unicont SPb Ltd
Technical Documentation CH-105
Page 7
Table 2 Diameters of through holes of ABC glands
Type of gland
Internal diameter of gland
MG 16
6–10 mm
MG 20
9–14 mm
MG 25
13–18 mm
MG 32
18–25 mm
5.2
Connection OF ABC
5.2.1.
ABC Connection Procedure
ABC is
connected in the following sequence:
1.
Remove the device lower cover;
2.
Insert the
connecting wires of supply circuit, accumulator battery and other connected
devices through the glands located in the lower part of the device case
3.
Ground
ABC
case to the common grounding bus. The grounding bolt is located from
the right side in the lower part of ABC case (Figure 2).
4.
Connect the wires of accumulator battery and peripheral equipment to battery
charger terminals in accordance with the diagrams (refer to Paras 5.2.2 and 5.2.3).
5.
This paragraph is applicable only to battery charger with marking CH-105
(Table 1).
Ensure that the onboard power supply complies with the requirements of this OM
(110 or 220 VAC). From factory
ABC
is delivered adjusted to supply voltage from network of
220 V 50/60 Hz. If
ABC receives power supply from
network of 110 V 50/60 Hz, switch the
power unit to power supply from 110 V network. To switch the supply voltage of
ABC to
voltage 110 V 50/60 Hz, on power unit set the voltage selector from position "220 V
"
to position
"110 V
"
(bottom-upwards). Supply voltage selector is located from the right side of power unit.
6.
Connect the power cable to terminals "Input" of ABC (refer to Para. 5.2.5).
CAUTION! For safety of the personnel before connecting the power cable to
ABC
make sure that it is completely de-energized.
7.
Apply
power to
ABC
with the help of key switch located on the left side of
ABC
case. Five seconds after start
ABC
will be set to operating mode and will display present value
of
AB
voltage. From the factory
ABC
is delivered adjusted to charging current and voltage
values of 0.2
А
and 25.5 V, respectively (if a battery with operating voltage below 24 V is
connected to
ABC, take into consideration that
because the value of charging current is small,
the battery charger will not damage the battery since the preset current is comparable with
AB
leakage current; however do not leave
ABC enabled for a long time
without changing the
charging voltage to the appropriate value).
Note!
During
adjustment of
ABC
built-in signalling can operate. To disable the sound
signal, press the key "Mute" (refer to Figure 9).
8.
In
ABC
menu set the value of charging current and voltage corresponding to the
connected
AB
(refer to Para 10).
9.
Make sure that
ABC
operates normally: charging current and voltage do not exceed
the set values and green or yellow light-emitting diode glows (refer to functions of light-emitting
diodes, Table 6).
If the alarm operates, find and eliminate the cause of its operation (refer to the table of
alarms, Table 4).