LOAD TESTING OPTION
To access the off load testing option: keep SET pressed for 2 seconds; press + and select the TS (TS =
test ) option; press SET to confirm. Use + to select password number “13” and press SET to confirm. This
will activate the off
-
load testing process, that is the activation of each component connected electronically
to the circuit board. To browse press +. Once the test has been completed, press ESC to exit. (An electronic
component testing tool is available. This can also issue a test report).
Test position
Parameter explanation
Measurement
Unit
C0
Test mode ready
//
C1
Igniter activation
//
C2
Combustion blower fan activation with encoder signal check
g/s
C3
Auger motor activation with electrical consumption check
A
C4
Convection blower activation
//
C5
Thermocouple temperature measurement
°C
C6
Combustive air flow sensor signal reading
Volt
C7
Room temperature probe reading
°C