background image

36

4.6  -  ERROR CODES

DIsplay Controller E8 (Optional)

For error codes relating to the heating system, refer to the 

section “Faults Finding” in Instructions for use supplied with 

the contoller E8.

Control panel

When indicator fault light, 

press the LIGHT BLUE key to view the error code on the 

display.

( Num ) = 

vedi legenda Par. 2.2

CODE

DISPLAY

E8

CODE

DESCRIPTION  

SOLUTION

E13

DHW sensor failure (only if the boiler is combined 
with an external storage tank)

Check the sensor’s efficiency and/or its wiring

E32

Mains voltage < 190 Vac 

Check that the mains voltage is <190 Vac, if the 
mains voltage is correct replace

the control board.

E02

Gas pressure not sufficient

  

Check the gas pressure; if is correct check the 

efficiency of the pressure gas and / or wiring

E 29

Water inside the combustion chamber

Intervention Level Sensor (SL)

Verify condensing water draining pipe.

E15

Difference between the heating temperature 
sensor (SR) and the heating return
sensor (SRR) > 35°C.

Check the installation

E14

HEATING RETURN SENSOR (22)

 

Failure of the heating return sensor

(SRR)

Check the efficiency of the sensor and/or wiring  

(22)

E06

HIGH TEMPERATURE

Over high temperature detected by

the heating sensor (SR) (>95°C)

Check the operation the pump and possibly clean 

the heat exchanger. (24)

E05

Loss of flame signal during boiler
operation

Press the reset key on the panel

E04

No flame detected during the ignition
phase.

Press the reset key on the
control panel

E24

FAN SPEED OUT OF CONTROL

Alteration of the fan speed.

Fan speed is not achieved.

Check the operation of the fan (18) and con-

nections

E26

SPEED OUT OF CONTROL 

Alteration of the fan speed 

Fan speed hightest than that required

Check the operation of the fan (18) and con-

nections

E200

Verify parameter St (if 0) fault will be detected    Rectify parameter St. 

Summary of Contents for KONf 115

Page 1: ...100 115 KONf E N G L I S H INSTALLATION AND SERVICING MANUAL...

Page 2: ...the local authorities or to a dealer who offers this service Separate disposal of a domestic appliance avoids possible negative consequences for the environment and human health deriving from inapprop...

Page 3: ...8 3 8 Filling the system 19 3 9 Electrical connections 20 3 10 Commissioning 22 3 11 Measurement of combustion efficiency during installation 23 3 11 1 Calibration function activation 23 3 11 2 Probes...

Page 4: ...t and must be kept by the user Read the warnings contained in this instruction booklet carefully as they provide important guidelines regarding installation use and maintenance safety Keep the booklet...

Page 5: ...onsultation Inform the user about the importance of the air vents and the flue gas exhaust system highlighting their essential features and the absolute prohibition of modifying them Inform the user c...

Page 6: ...e Do not modify the following parts the boiler the gas air water and electricity supply lines the flue gas pipe the safety valve and the exhaust pipe the construction parts which affect the operating...

Page 7: ...x Class A Heating circuit characteristics 9 Pn Effective nominal output 10 Pcond Effective output in condensation 11 Qn Maximum heat output 12 Adjusted Qn Adjusted for rated heat output 13 PMS Max hea...

Page 8: ...c price list ATTENTION see general warnings 1 1 The heating only models are NOT suitable for the production of water for human con sumption according to Ministerial Decree D M 174 2004 Attention Any d...

Page 9: ...valve 30 SMG Sensor Flow General 31 Condensation drain trap 32 Outlet flue inspection 35 Ignition transformer 37 Flow shut off 3 Way valve 38 Gas pressure switch 39 Differential Pressure switch inser...

Page 10: ...10 2 3 DIMENSIONS Front view View from above Left Side view...

Page 11: ...es which is to say lower than 15K Avaible Head m c a m H 2 O The table provides an indication the flow the pump in function of the Dt of the primary circuit KONf 100 KONf 115 Power supply in kW kW 99...

Page 12: ...ue losses with burner in operation max 1 95 2 29 Minimum heating circuit pressure bar 0 5 0 5 Maximum heating circuit pressure bar 6 6 Water content l 9 9 Gas Consumption Natural 20 mbar gas G 20 a Qn...

Page 13: ...er at 30 of the rated heat output with low temperature capacity Tr 30 C P1 kW 32 2 36 9 Performance at 30 of the rated heat output with low temperature capacity Tr 30 C 1 98 5 96 5 Boiler with output...

Page 14: ...2 INSTALLATION STANDARDS t must be installed by a professionally qualified technician who shall take the responsibility of observing all local and or national laws published in the official journal a...

Page 15: ...omply with the instruction above In the packaging in addition to the boiler you can also find the following contents ENVELOPE DOCUMENTATION Instruction manual for the person in charge of the appliance...

Page 16: ...ered To grant an easy access to the boiler components in order to facilitate the ordinary and extraordinary service operations The floor should not be of flammable material If the floor is flammable a...

Page 17: ...ndards in force To connect the flue gas exhaust pipe local and na tional standards must be observed In the event the boiler is replaced ALWAYS re place the flue gas pipe as well The boiler is type app...

Page 18: ...installation Installation Type B23p Air inlet from upper grid and smoke outlet 100 Detail A Optional Combustion air inlet is carried out through the indicated grid hole a through the air intake holes...

Page 19: ...The gas connection must be carried out only by a qualified installer who must respect and apply that foreseen by relevant laws in force in the local prescriptions of the supply company Incorrect in st...

Page 20: ...ng tap on the heating circuit or use the optional accessories The boiler is equipped with its own drain valve the position of which is indicated in the figure to par 2 2 14 This tap can never be used...

Page 21: ...jeop ardise the safety of the appliance The power cable must be replaced by technical personnel authorised using original spare parts only Failure to comply with the above can jeop ardise the safety o...

Page 22: ...nician Always disconnect the power supply before making any connections or any operation on the electrical parts and make sure that it can not be accidentally re inserted Safety connection Safety Conn...

Page 23: ...valves open does the gas to be used correspond to the boiler calibration gas otherwise perform the boiler conversion in order to use the gas available see section 4 3 this operation must be carried o...

Page 24: ...ISABLING After calibration press the PLUS and MINUS at the same time the symbol off Flue gas probe To determine the combustion efficiency one must make the following measurements measurement of the co...

Page 25: ...TING THE BURNER 2 Minimum output adjustment Operate the boiler in calibration mode at MINIMUM OUTPUT see 3 11 1 Once the burner is on check that the CO2 MINIMUM value corresponds to that indicated in...

Page 26: ...ducts are not obstructed Check the levels of CO2 often especially with low flow rates They refer to the boiler with a closed combustion chamber NOZZLES PRESSURE FLOW RATES TABLE 3 Conclusion of the b...

Page 27: ...tance Centres only The user is NOT authorised to activate the function described below It is possible to adjust the maximum thermal capacity in heating mode by decreasing the burner pressure value 3 1...

Page 28: ...previously Vent and if necessary restore the heating pressure until reaching a pressure of 0 8 1 0 bar Open the gas shut off valve Switch the boiler on Make sure the appliance is gas tight and watert...

Page 29: ...eating Heat the TL until it intervenes at 102 C and check that it intervenes at 102 DK safety pressure switch against water deficiency 13 Does the pressure switch block the boiler if the water pressur...

Page 30: ...the instructions given ATTENTION After performing the conversion for the op eration of the boiler with a type of gas e g propane gas other than that specifically requested when ordering the appliance...

Page 31: ...utton shown 4 4 PROGRAMMING OF THE OPERATION PARAMETERS ATTENTION Function reserved for Authorised Assistance Centres only B Operation CHANGE PARAMETER Press key PLUS MINUS to modify BURNER MODULATION...

Page 32: ...ers by pressing the MINUS Repeat the operations A B C to change value VALUE FROM TO DEFAULT 20 100 99 DHW ENABLE THE TEMPERATURE SENSOR 7 Continue with the modification of parameters by pressing the M...

Page 33: ...ion of parameters by pressing the MINUS Repeat the operations A B C to change value VALUE FROM TO DEFAULT 35 C 45 C 40 C SETTING OF MAXIMUM HEATING TEMP 9 Continue with the modification of parameters...

Page 34: ...speed Pu Fan tacho Pulse Revolution Sb Fanmodulation level at burner standby Fu Massima velocit ventilatore METANO GPL FH Maximum relative fun speed GPL FL Minimum relative fun speed GPL dt Storage ta...

Page 35: ...s HSCP E8 E ACC Ignition Electrode E RIV Detection Elecrode INAIL Safety connection PF Smoke Pressostat PG Gas Pressostat SL Level sensor condensat SR Flow heating sensor SRR Return heating sensor TL...

Page 36: ...Intervention Level Sensor SL Verify condensing water draining pipe E15 Difference between the heating temperature sensor SR and the heating return sensor SRR 35 C Check the installation E14 Heating re...

Page 37: ...r 4 or its connections E30 PARAMETERS OF FACTORY Alteration of the factory settings due to any electromagnetic interference Press the reset button if the fault does not clear replace the board E11 FLA...

Page 38: ...38...

Page 39: ...39...

Page 40: ...l eu AG S p A 00337209 1 a edizione 05 17 www unical eu Unical declines every responsibility for the possible inaccuracies if owed to errors of transcript or press Also reserves the right to bring tho...

Reviews: