Installation Instructions
Preliminary operations:
Fit the Ø 100 mm smoke outlet hose
provided in the package as shown.
3.6 -
FLUE GAS EXHAUST PIPE CONNECTION (Forced draw boiler)
B23P
TOTAL LENGTH ( LS exhaust)
SINGLE Ø100
FROM [m]
TO [m]
1
42
Connection to a combustion products evacuation
pipe outside the room; the combustion air is tak-
en directly from the room where the appliance is
installed.
C63x
C63
Boiler intended for connection to a combustion air
intake and combustion products evacuation system,
approved and sold separately
ATTENTION:
The flue must comply with standards
in force.
To connect the flue gas exhaust pipe, local and na
-
tional standards must be observed
In the event the boiler is replaced, ALwAYS re-
place the flue gas pipe as well.
The boiler is type approved for the exhaust configu
-
rations listed below:
ATTENTION:
For the type of connection
B23P
the
room follows the same installation rules
for boilers with natural draught.
Please note:
These values relate to exhausts/
made by means of rigid pipes and
smooth original UNICAL.
CAUTION
LT
total length is a reference value
for the dimensioning of the ducts of
A
(intake) and
S
(Exhaust). Subtracting
the values of
LT
reported, at values of
bends* / terminals* / extensions* you
get the value:
if > 0 = OK
- POSSIBLE configuration
if < 0 = NO
- WRONG configuration
(*) Values in the
MT018
available on the website.