11
Tec
hnical Features
ENGLISH
The
D
t between supply and return boiler must
never be less than 15 ° K.
NOTE:
The use of a mixing header fitted between the
boiler circuit and the system circuit is always ad-
visable. It becomes INDISPENSABLE if the sy
-
stem requires flow rates superior to the
maximum permitted boiler flow rates, which is to
say lower than 15K.
Avaible Head m.c.a.
(m/H
2
O)
The table provides an indication the flow the pump in function of the
D
t of the primary circuit.
KONf 100
KONf 115
Power supply in kW
kW
99,5
115
Max flow rate demanded l/h (
D
t 15 K)
l/h
5700
6600
Nominal flow rate request (
D
t 20 K)
l/h
4280
4950
Power supply in condensation (50/30)
kW
105
120,3
Max flow rate demanded l/h (
D
t 15 K)
l/h
6020
6897
Nominal flow rate request (
D
t 20 K)
l/h
4520
5173
2.4 - DIAGRAM OF FLOw RATE/PRESSURE AVAILABLE FOR INSTALLATION
Q = Flow rate (l/h)
Summary of Contents for KONf 115
Page 1: ...100 115 KONf E N G L I S H INSTALLATION AND SERVICING MANUAL...
Page 10: ...10 2 3 DIMENSIONS Front view View from above Left Side view...
Page 38: ...38...
Page 39: ...39...