Unical HP OWER 60 User'S And Installer'S Manual Download Page 8

HP-OWER

 

8

 

 

Models 

B* 

E** 

HP_OWER 60 

1500  500 

400 

400 

500 

HP_OWER 90 

1500  500 

400 

400 

500 

HP_OWER 120 

1500  500 

400 

400 

500 

HP_OWER 150 

1500  500 

400 

400 

500 

* The recommended minimum distance for installation and maintenance. 
** The recommended minimum  distance for assistance and maintenance 

5.4

 

HYDRAULIC CONNECTIONS 

The hydraulic connections have to be installed in accordance with national and local regulations; pipes can be made up of steel, 
galvanized steel or PVC. Pipes have to be designed depending on the nominal water flow and on the hydraulic pressure drops of 
the system. All pipes have to be insulated with closed-cell material of adequate thickness. Chillers have to be connected to piping 
by means of flexible joints. Piping should include: 
• 

Hole thermometers to monitor the system’s temperature. 

• 

Manual gate valves to separate the chiller from the hydraulic circuit. 

• 

Y-shaped metallic filter (to be mounted on the inlet pipe) with a mesh not larger than 1mm. 

• 

Charging group and discharge valve, where necessary. 

 

WARNING: Make sure that, when designing the pipe length and diameter, do not exceed the maximum head loss 
on the plant side, please see the technical data given in the  table of Paragraph 12 (available pressure head).

 

WARNING: Connect the pipes to the attacks by using always key against key system. 

WARNING: The expansion vessel have a limited volume. The installator have to provide a further expansion vessel 
if it is necessary. 
WARNING:  Unit  water  inlet  pipe  have  to  be  in  correspondence  with  the  connection  labelled:  ”WATER  INLET”, 
otherwise the evaporator may freeze. 
WARNING: It is compulsory to install on the WATER INLET connection a metallic filter with a mesh not larger than 
1mm. Should the water flow switch be altered or should the filter not be installed, the warranty will no longer be 
valid. The filter have to be kept clean, so make sure it is clean after the unit has been installed, and then check it 
periodically. 
All  units  are  standard  supplied  with  the  water  flow  switch  (factory  installed).  Should  the  water  flow  switch  be 
altered, removed, or should the water filter not be installed on the unit, the warranty will be invalidated. Please 
refer to the wiring diagram for the water flow switch electric connections. 

 
 
 
 

 
 
 

 
 
 
 

 
 
 
 
 
 
 

1. Vibration-damping joint
2. Gate valve
3. Filling / Drain valve
4. Differential by-pass
5. Filtre
6. System expansion vessel      

Heating / Cooling system

Summary of Contents for HP OWER 60

Page 1: ...User s and Installer s Manual 60 90 120 150...

Page 2: ...L CONNECTIONS 11 5 7 1 Wiring terminal block 11 5 7 2 Removal of protective carter for models 120 and 150 12 6 START UP 13 7 SHUTDOWNS FOR LONG PERIODS 13 8 MAINTENANCE AND PERIODICAL CONTROLS 13 9 TE...

Page 3: ...HP_OWER 3...

Page 4: ...the manufacturer as an attachment to this manual The company is available to give any detailed information about this manual and to give information regarding the use and the maintenance of its own u...

Page 5: ...86 CEE 2009 104 CE 86 188 CEE and 77 576 CEE directives Every employer shall implement such provisions and ensure that their workers to respect them We observe therefore that Do not tamper with or rep...

Page 6: ...ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator apparatus The vapors are heavier than air and can cause s...

Page 7: ...t only by QUALIFIED PERSONNEL Before any operation on the unit make sure the power supply is disconnected WARNING MOVING PARTS RISK OF DEATH Disconnect the power supply and ensure that the fan is stop...

Page 8: ...o not exceed the maximum head loss on the plant side please see the technical data given in the table of Paragraph 12 available pressure head WARNING Connect the pipes to the attacks by using always k...

Page 9: ...WARNING The water on the charging topping up pipe must be suitably pre filtered from any impurities and suspended particles Make sure that you have installed a cartridge filter removable WARNING Befo...

Page 10: ...ALVE FO INVERTING CYCLE LR LIQUID RECEIVER EEV ELECTRONIC EXPANSION VALVE FL FILTER M AXIAL FAN SE OUTDOOR AIR TEMPERATURE P CIRCULATOR ON BOARD UNIT IN WATER INLET TEMPERATURE OUT WATER OUTLET TEMPER...

Page 11: ...witch connections altered or not properly made the guarantee will be invalidated WARNING The remote control panel is connected to the water chiller by means of no 4 wires having a 1 5 mm 2 section The...

Page 12: ...eutral output of auxiliary electric heater for plant water 230V 50Hz 5A AEH Digital output DO3 230 Vac Phase output of auxiliary electric heater for plant water 230V 50Hz 5A SAN Analogue ST9 digital D...

Page 13: ...terminate immediately WARNING The summer winter operating mode have to be selected at the beginning of the related season Frequent and sudden changes of this seasonal operating mode have to be avoided...

Page 14: ...d discharge piping of the compressor are usually high Be careful when working near condensing coils The aluminum fins are very sharp and can cause serious injuries After the maintenance operations clo...

Page 15: ...R410A R410A R410A Refrigerant quantity kg 1 55 2 10 3 65 3 90 Design pressure high low MPa 4 2 2 7 4 2 2 7 4 2 2 7 4 2 2 7 Hydraulic circuit Water flow rate 3 m3 h 0 99 0 99 1 56 1 56 2 13 2 13 2 44 2...

Page 16: ...allation and maintenance Read precautions for installation and maintenance at specific chapters on user s and installation s manual PRODUCT FICHE HP_OWER for medium temperature application Tout 55 C S...

Page 17: ...Tj bivalent temperature Pdh 4 2 kW Tj bivalent temperature COPd 2 73 Tj operation limit temperature Pdh 3 8 kW Tj operation limit temperature COPd 2 35 For air to water heat pumps Tj 15 C if TOL 20 C...

Page 18: ...Tj bivalent temperature Pdh 7 2 kW Tj bivalent temperature COPd 2 73 Tj operation limit temperature Pdh 6 9 kW Tj operation limit temperature COPd 2 48 For air to water heat pumps Tj 15 C if TOL 20 C...

Page 19: ...j bivalent temperature Pdh 9 2 kW Tj bivalent temperature COPd 2 69 Tj operation limit temperature Pdh 8 1 kW Tj operation limit temperature COPd 2 29 For air to water heat pumps Tj 15 C if TOL 20 C P...

Page 20: ...Tj bivalent temperature Pdh 10 2 kW Tj bivalent temperature COPd 2 58 Tj operation limit temperature Pdh 9 4 kW Tj operation limit temperature COPd 2 21 For air to water heat pumps Tj 15 C if TOL 20...

Page 21: ...Pd 3 50 Tj bivalent temperature Pdh 4 0 kW Tj bivalent temperature COPd 2 21 Tj operation limit temperature Pdh 3 6 kW Tj operation limit temperature COPd 2 00 For air to water heat pumps Tj 15 C if T...

Page 22: ...Pd 3 26 Tj bivalent temperature Pdh 7 1 kW Tj bivalent temperature COPd 2 10 Tj operation limit temperature Pdh 6 8 kW Tj operation limit temperature COPd 1 99 For air to water heat pumps Tj 15 C if T...

Page 23: ...OPd 3 56 Tj bivalent temperature Pdh 8 3 kW Tj bivalent temperature COPd 1 93 Tj operation limit temperature Pdh 7 4 kW Tj operation limit temperature COPd 1 69 For air to water heat pumps Tj 15 C if...

Page 24: ...OPd 3 37 Tj bivalent temperature Pdh 9 3 kW Tj bivalent temperature COPd 1 78 Tj operation limit temperature Pdh 8 5 kW Tj operation limit temperature COPd 1 55 For air to water heat pumps Tj 15 C if...

Page 25: ...cessary to refer always to the technical data label stuck on right side panel of the unit 12 HEAT PUMPS AVAILABLE HEAD PRESSURE Below the characteristic curves corresponding to Head pressure Water flo...

Page 26: ...HP OWER 26 13 WATER PUMP CURVES 13 1 MODELS HP_OWER 60 90 13 2 MODELS HP_OWER 120 150...

Page 27: ...lure in the case of insufficient water flow but it does not ensure the minimum flow rate required in order the unit can work properly Models HP_OWER 60 90 120 150 Cooling capacity for reference kW 5 3...

Page 28: ...WFCF Water flow rate correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation with...

Page 29: ...HP_OWER 29 16 DIMENSIONS 16 1 MODELS HP_OWER 60 IN OUT 1 M 16 2 MODELS HP_OWER 90 IN OUT 1 M...

Page 30: ...HP OWER 30 16 3 MODELS HP_OWER 120 150 IN OUT 1 M...

Page 31: ...HP_OWER 31 17 WIRING DIAGRAMS 17 1 MODELS HP_OWER 60 90 Temp Sensor Heat Sink...

Page 32: ...HP OWER 32 17 2 MODEL HP_OWER 120 Temp Sensor Heat Sink...

Page 33: ...HP_OWER 33 17 3 MODEL HP_OWER 150 Temp Sensor Heat Sink CN604 CN607 DC DC1 DC2 DC DC1 DC2 20A 5mH Reactor...

Page 34: ...perature sensors for the environment thermohygrometer analysis and manage the double set point for the radiant floor panel that use a dehumidification system The intuitive interface simplifies the use...

Page 35: ......

Page 36: ...s It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 660556 in...

Reviews: