Unical HP OWER 60 User'S And Installer'S Manual Download Page 10

HP-OWER

 

10

 

5.4.4

 

Hydraulic circuit 

Models: HP_OWER 

A

B

H

F

G

E

D

I

C

 

KEY

 

Plate heat exchanger 

Air vent valve 

Water flow switch 

Safety valve 

Service valve 

Pressure gauge

 

Pump with DC brushless motor 

Reverse-flow 4-way valve 

Expansion vessel 

 

 

5.5

 

REFRIGERANT DIAGRAM OF HP_OWER 60/90 

SE

EEV

LR

IN

OUT

4WV

DT

LP

HP

ST

M

P

C

LS

FL

FL

CLS

Pr

 

COMPRESSOR 

CLS 

COMPRESSOR LIQUID SEPARATOR  

ST 

COMPRESSOR INLET TEMPERATURE 

DT 

COMPRESSOR OUTLET TEMPERATURE 

HP 

HIGH PRESSURE TRANSDUCER 

Pr 

HIGH PRESSURE FLOW SWITCH 

LP 

LOW PRESSURE TRANSDUCER 

LS 

LIQUID SEPARATOR (only for model 09) 

4WV 

VALVE FO INVERTING CYCLE 

LR 

LIQUID RECEIVER 

EEV 

ELECTRONIC EXPANSION VALVE 

FL 

FILTER 

AXIAL FAN 

SE 

OUTDOOR AIR TEMPERATURE 

CIRCULATOR ON BOARD UNIT 

IN 

WATER INLET TEMPERATURE 

OUT 

WATER OUTLET TEMPERATURE 

 

5.6

 

REFRIGERANT DIAGRAM OF HP_OWER 120/150 

SE

EEV

LR

IN

O U T

4W V

D T

LP

H P

ST

M

P

C

LS

O S

FL

FL

N R V

CP

C LS

Pr

 

COMPRESSOR 

CLS 

COMPRESSOR LIQUID SEPARATOR  

OS 

OIL SEPARATOR 

ST 

COMPRESSOR INLET TEMPERATURE 

DT 

COMPRESSOR OUTLET TEMPERATURE 

HP 

HIGH PRESSURE TRANSDUCER 

Pr 

HIGH PRESSURE FLOW SWITCH 

LP 

LOW PRESSURE TRANSDUCER 

LS 

LIQUID SEPARATOR 

4WV 

VALVE FO INVERTING CYCLE 

LR 

LIQUID RECEIVER 

EEV 

ELECTRONIC EXPANSION VALVE 

NRV 

NO RETURN VALVE 

FL 

FILTER 

AXIAL FAN 

SE 

OUTDOOR AIR TEMPERATURE 

CIRCULATOR ON BOARD UNIT 

IN 

WATER INLET TEMPERATURE 

OUT 

WATER OUTLET TEMPERATURE 

CP 

CAPILLARY 

 

Summary of Contents for HP OWER 60

Page 1: ...User s and Installer s Manual 60 90 120 150...

Page 2: ...L CONNECTIONS 11 5 7 1 Wiring terminal block 11 5 7 2 Removal of protective carter for models 120 and 150 12 6 START UP 13 7 SHUTDOWNS FOR LONG PERIODS 13 8 MAINTENANCE AND PERIODICAL CONTROLS 13 9 TE...

Page 3: ...HP_OWER 3...

Page 4: ...the manufacturer as an attachment to this manual The company is available to give any detailed information about this manual and to give information regarding the use and the maintenance of its own u...

Page 5: ...86 CEE 2009 104 CE 86 188 CEE and 77 576 CEE directives Every employer shall implement such provisions and ensure that their workers to respect them We observe therefore that Do not tamper with or rep...

Page 6: ...ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator apparatus The vapors are heavier than air and can cause s...

Page 7: ...t only by QUALIFIED PERSONNEL Before any operation on the unit make sure the power supply is disconnected WARNING MOVING PARTS RISK OF DEATH Disconnect the power supply and ensure that the fan is stop...

Page 8: ...o not exceed the maximum head loss on the plant side please see the technical data given in the table of Paragraph 12 available pressure head WARNING Connect the pipes to the attacks by using always k...

Page 9: ...WARNING The water on the charging topping up pipe must be suitably pre filtered from any impurities and suspended particles Make sure that you have installed a cartridge filter removable WARNING Befo...

Page 10: ...ALVE FO INVERTING CYCLE LR LIQUID RECEIVER EEV ELECTRONIC EXPANSION VALVE FL FILTER M AXIAL FAN SE OUTDOOR AIR TEMPERATURE P CIRCULATOR ON BOARD UNIT IN WATER INLET TEMPERATURE OUT WATER OUTLET TEMPER...

Page 11: ...witch connections altered or not properly made the guarantee will be invalidated WARNING The remote control panel is connected to the water chiller by means of no 4 wires having a 1 5 mm 2 section The...

Page 12: ...eutral output of auxiliary electric heater for plant water 230V 50Hz 5A AEH Digital output DO3 230 Vac Phase output of auxiliary electric heater for plant water 230V 50Hz 5A SAN Analogue ST9 digital D...

Page 13: ...terminate immediately WARNING The summer winter operating mode have to be selected at the beginning of the related season Frequent and sudden changes of this seasonal operating mode have to be avoided...

Page 14: ...d discharge piping of the compressor are usually high Be careful when working near condensing coils The aluminum fins are very sharp and can cause serious injuries After the maintenance operations clo...

Page 15: ...R410A R410A R410A Refrigerant quantity kg 1 55 2 10 3 65 3 90 Design pressure high low MPa 4 2 2 7 4 2 2 7 4 2 2 7 4 2 2 7 Hydraulic circuit Water flow rate 3 m3 h 0 99 0 99 1 56 1 56 2 13 2 13 2 44 2...

Page 16: ...allation and maintenance Read precautions for installation and maintenance at specific chapters on user s and installation s manual PRODUCT FICHE HP_OWER for medium temperature application Tout 55 C S...

Page 17: ...Tj bivalent temperature Pdh 4 2 kW Tj bivalent temperature COPd 2 73 Tj operation limit temperature Pdh 3 8 kW Tj operation limit temperature COPd 2 35 For air to water heat pumps Tj 15 C if TOL 20 C...

Page 18: ...Tj bivalent temperature Pdh 7 2 kW Tj bivalent temperature COPd 2 73 Tj operation limit temperature Pdh 6 9 kW Tj operation limit temperature COPd 2 48 For air to water heat pumps Tj 15 C if TOL 20 C...

Page 19: ...j bivalent temperature Pdh 9 2 kW Tj bivalent temperature COPd 2 69 Tj operation limit temperature Pdh 8 1 kW Tj operation limit temperature COPd 2 29 For air to water heat pumps Tj 15 C if TOL 20 C P...

Page 20: ...Tj bivalent temperature Pdh 10 2 kW Tj bivalent temperature COPd 2 58 Tj operation limit temperature Pdh 9 4 kW Tj operation limit temperature COPd 2 21 For air to water heat pumps Tj 15 C if TOL 20...

Page 21: ...Pd 3 50 Tj bivalent temperature Pdh 4 0 kW Tj bivalent temperature COPd 2 21 Tj operation limit temperature Pdh 3 6 kW Tj operation limit temperature COPd 2 00 For air to water heat pumps Tj 15 C if T...

Page 22: ...Pd 3 26 Tj bivalent temperature Pdh 7 1 kW Tj bivalent temperature COPd 2 10 Tj operation limit temperature Pdh 6 8 kW Tj operation limit temperature COPd 1 99 For air to water heat pumps Tj 15 C if T...

Page 23: ...OPd 3 56 Tj bivalent temperature Pdh 8 3 kW Tj bivalent temperature COPd 1 93 Tj operation limit temperature Pdh 7 4 kW Tj operation limit temperature COPd 1 69 For air to water heat pumps Tj 15 C if...

Page 24: ...OPd 3 37 Tj bivalent temperature Pdh 9 3 kW Tj bivalent temperature COPd 1 78 Tj operation limit temperature Pdh 8 5 kW Tj operation limit temperature COPd 1 55 For air to water heat pumps Tj 15 C if...

Page 25: ...cessary to refer always to the technical data label stuck on right side panel of the unit 12 HEAT PUMPS AVAILABLE HEAD PRESSURE Below the characteristic curves corresponding to Head pressure Water flo...

Page 26: ...HP OWER 26 13 WATER PUMP CURVES 13 1 MODELS HP_OWER 60 90 13 2 MODELS HP_OWER 120 150...

Page 27: ...lure in the case of insufficient water flow but it does not ensure the minimum flow rate required in order the unit can work properly Models HP_OWER 60 90 120 150 Cooling capacity for reference kW 5 3...

Page 28: ...WFCF Water flow rate correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation with...

Page 29: ...HP_OWER 29 16 DIMENSIONS 16 1 MODELS HP_OWER 60 IN OUT 1 M 16 2 MODELS HP_OWER 90 IN OUT 1 M...

Page 30: ...HP OWER 30 16 3 MODELS HP_OWER 120 150 IN OUT 1 M...

Page 31: ...HP_OWER 31 17 WIRING DIAGRAMS 17 1 MODELS HP_OWER 60 90 Temp Sensor Heat Sink...

Page 32: ...HP OWER 32 17 2 MODEL HP_OWER 120 Temp Sensor Heat Sink...

Page 33: ...HP_OWER 33 17 3 MODEL HP_OWER 150 Temp Sensor Heat Sink CN604 CN607 DC DC1 DC2 DC DC1 DC2 20A 5mH Reactor...

Page 34: ...perature sensors for the environment thermohygrometer analysis and manage the double set point for the radiant floor panel that use a dehumidification system The intuitive interface simplifies the use...

Page 35: ......

Page 36: ...s It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 660556 in...

Reviews: