ELECTRICAL CONNECTIONS 

Check out that the power supply meets the unit’s electric nominal data (tension, phases, frequency) reported  on the label in the 
unit’s  right-side  panel.  Power  connections  have  to  be  made  in  accordance  to  the  wiring  diagram  enclosed  with  the  unit  and  in 
conformity with the national and international norms in force (providing equipment as general magnetothermic circuit breaker, 
differential circuit breakers for each electric line, proper grounding for the plant, etc.). Power cables, electric protections and line 
fuses have to be sized according to the specifications listed in the wiring diagram enclosed with the unit and in the electrical data 
contained in the table of technical characteristics. 

 

WARNING:  Installer has to provide a general circuit  breaker (for example  a  magnetothermic circuit  breaker) at the 
beginning of unit circuit system. 

 

WARNING: The supply voltage’s fluctuations cannot exceed ±10% of the nominal value. Should this tolerance not be 
respected, please contact our technical department. 

 

WARNING:  The  power  supply  have  to  respect  the  listed  limits:  failing  this,  warranty  will  terminate  immediately. 
Before any operation on the unit, be sure that the power supply is disconnected. 
WARNING: The water flow switch (B component in the previous hydraulic circuit and factory installed) have ALWAYS 
to  be  connected  following  the  indications  listed  in  the  wiring  diagram.  Never  bridge  the  water  flow  switch 
connections  in  the  terminal  board.  Should  the  water  flow  switch  connections  altered  or  not  properly  made,  the 
guarantee will be invalidated. 

 

WARNING:  The  remote  control  panel  is  connected  to  the  water  chiller  by  means  of  no.4  wires  having  a  1,5  mm

2

 

section. The power supply cables have to be separated from the remote control wires. The maximum distance is 50m. 

 

WARNING: The remote control panel cannot be installed in areas with strong vibrations, corrosive gases, and excess 
of dirtiness or high humidity levels. Leave free the area near the cooling openings. 

5.7.1

 

Wiring terminal block 

 

Electrical wiring have to be done only by qualified personnel. 

The electrical connections have to be realized by qualified personnel.

 The terminal block is located under the plastic cover on the 

side of the hydraulic connections (for the models 120 and 150, it is necessary to remove the protective carter). The wiring to the 
terminal block has to be realized in accordance to the below notes (the drawing is for illustration). 

 

The connections indicated below are standard. Other connections are shown in the manual of the on board control  
 
Terminal 

Type 

Connection 

GND 

Power supply 
1-Ph/N/PE 
230V, 50Hz 
(3-Ph/N/PE 
400 Vac, 50Hz for the model of 15kW) 

Connect the grounding wire 

N1 

Power supply 
1-Ph/N/PE 
230V, 50Hz 
(3-Ph/N/PE 
400 Vac, 50Hz for the model of 15kW) 

Connect the power supply neutral wire; 

L1 

Power supply 
1-Ph/N/PE 
230V, 50Hz 
(3-Ph/N/PE 
400 Vac, 50Hz for the model of 15kW) 

Connect the power supply phase wire; (note that, in the three-phases 
versions there are two other terminals, L2 and L3) 

NC1 

Digital output 
230 Vac with changeover contact

 

Power supply NC terminal (230V AC) for 3-way valve for sanitary hot water 
boiler (used only for 3-way valve with 3 contacts for power supply 

Summary of Contents for HP OWER 60

Page 1: ...User s and Installer s Manual 60 90 120 150...

Page 2: ...L CONNECTIONS 11 5 7 1 Wiring terminal block 11 5 7 2 Removal of protective carter for models 120 and 150 12 6 START UP 13 7 SHUTDOWNS FOR LONG PERIODS 13 8 MAINTENANCE AND PERIODICAL CONTROLS 13 9 TE...

Page 3: ...HP_OWER 3...

Page 4: ...the manufacturer as an attachment to this manual The company is available to give any detailed information about this manual and to give information regarding the use and the maintenance of its own u...

Page 5: ...86 CEE 2009 104 CE 86 188 CEE and 77 576 CEE directives Every employer shall implement such provisions and ensure that their workers to respect them We observe therefore that Do not tamper with or rep...

Page 6: ...ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator apparatus The vapors are heavier than air and can cause s...

Page 7: ...t only by QUALIFIED PERSONNEL Before any operation on the unit make sure the power supply is disconnected WARNING MOVING PARTS RISK OF DEATH Disconnect the power supply and ensure that the fan is stop...

Page 8: ...o not exceed the maximum head loss on the plant side please see the technical data given in the table of Paragraph 12 available pressure head WARNING Connect the pipes to the attacks by using always k...

Page 9: ...WARNING The water on the charging topping up pipe must be suitably pre filtered from any impurities and suspended particles Make sure that you have installed a cartridge filter removable WARNING Befo...

Page 10: ...ALVE FO INVERTING CYCLE LR LIQUID RECEIVER EEV ELECTRONIC EXPANSION VALVE FL FILTER M AXIAL FAN SE OUTDOOR AIR TEMPERATURE P CIRCULATOR ON BOARD UNIT IN WATER INLET TEMPERATURE OUT WATER OUTLET TEMPER...

Page 11: ...witch connections altered or not properly made the guarantee will be invalidated WARNING The remote control panel is connected to the water chiller by means of no 4 wires having a 1 5 mm 2 section The...

Page 12: ...eutral output of auxiliary electric heater for plant water 230V 50Hz 5A AEH Digital output DO3 230 Vac Phase output of auxiliary electric heater for plant water 230V 50Hz 5A SAN Analogue ST9 digital D...

Page 13: ...terminate immediately WARNING The summer winter operating mode have to be selected at the beginning of the related season Frequent and sudden changes of this seasonal operating mode have to be avoided...

Page 14: ...d discharge piping of the compressor are usually high Be careful when working near condensing coils The aluminum fins are very sharp and can cause serious injuries After the maintenance operations clo...

Page 15: ...R410A R410A R410A Refrigerant quantity kg 1 55 2 10 3 65 3 90 Design pressure high low MPa 4 2 2 7 4 2 2 7 4 2 2 7 4 2 2 7 Hydraulic circuit Water flow rate 3 m3 h 0 99 0 99 1 56 1 56 2 13 2 13 2 44 2...

Page 16: ...allation and maintenance Read precautions for installation and maintenance at specific chapters on user s and installation s manual PRODUCT FICHE HP_OWER for medium temperature application Tout 55 C S...

Page 17: ...Tj bivalent temperature Pdh 4 2 kW Tj bivalent temperature COPd 2 73 Tj operation limit temperature Pdh 3 8 kW Tj operation limit temperature COPd 2 35 For air to water heat pumps Tj 15 C if TOL 20 C...

Page 18: ...Tj bivalent temperature Pdh 7 2 kW Tj bivalent temperature COPd 2 73 Tj operation limit temperature Pdh 6 9 kW Tj operation limit temperature COPd 2 48 For air to water heat pumps Tj 15 C if TOL 20 C...

Page 19: ...j bivalent temperature Pdh 9 2 kW Tj bivalent temperature COPd 2 69 Tj operation limit temperature Pdh 8 1 kW Tj operation limit temperature COPd 2 29 For air to water heat pumps Tj 15 C if TOL 20 C P...

Page 20: ...Tj bivalent temperature Pdh 10 2 kW Tj bivalent temperature COPd 2 58 Tj operation limit temperature Pdh 9 4 kW Tj operation limit temperature COPd 2 21 For air to water heat pumps Tj 15 C if TOL 20...

Page 21: ...Pd 3 50 Tj bivalent temperature Pdh 4 0 kW Tj bivalent temperature COPd 2 21 Tj operation limit temperature Pdh 3 6 kW Tj operation limit temperature COPd 2 00 For air to water heat pumps Tj 15 C if T...

Page 22: ...Pd 3 26 Tj bivalent temperature Pdh 7 1 kW Tj bivalent temperature COPd 2 10 Tj operation limit temperature Pdh 6 8 kW Tj operation limit temperature COPd 1 99 For air to water heat pumps Tj 15 C if T...

Page 23: ...OPd 3 56 Tj bivalent temperature Pdh 8 3 kW Tj bivalent temperature COPd 1 93 Tj operation limit temperature Pdh 7 4 kW Tj operation limit temperature COPd 1 69 For air to water heat pumps Tj 15 C if...

Page 24: ...OPd 3 37 Tj bivalent temperature Pdh 9 3 kW Tj bivalent temperature COPd 1 78 Tj operation limit temperature Pdh 8 5 kW Tj operation limit temperature COPd 1 55 For air to water heat pumps Tj 15 C if...

Page 25: ...cessary to refer always to the technical data label stuck on right side panel of the unit 12 HEAT PUMPS AVAILABLE HEAD PRESSURE Below the characteristic curves corresponding to Head pressure Water flo...

Page 26: ...HP OWER 26 13 WATER PUMP CURVES 13 1 MODELS HP_OWER 60 90 13 2 MODELS HP_OWER 120 150...

Page 27: ...lure in the case of insufficient water flow but it does not ensure the minimum flow rate required in order the unit can work properly Models HP_OWER 60 90 120 150 Cooling capacity for reference kW 5 3...

Page 28: ...WFCF Water flow rate correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation with...

Page 29: ...HP_OWER 29 16 DIMENSIONS 16 1 MODELS HP_OWER 60 IN OUT 1 M 16 2 MODELS HP_OWER 90 IN OUT 1 M...

Page 30: ...HP OWER 30 16 3 MODELS HP_OWER 120 150 IN OUT 1 M...

Page 31: ...HP_OWER 31 17 WIRING DIAGRAMS 17 1 MODELS HP_OWER 60 90 Temp Sensor Heat Sink...

Page 32: ...HP OWER 32 17 2 MODEL HP_OWER 120 Temp Sensor Heat Sink...

Page 33: ...HP_OWER 33 17 3 MODEL HP_OWER 150 Temp Sensor Heat Sink CN604 CN607 DC DC1 DC2 DC DC1 DC2 20A 5mH Reactor...

Page 34: ...perature sensors for the environment thermohygrometer analysis and manage the double set point for the radiant floor panel that use a dehumidification system The intuitive interface simplifies the use...

Page 35: ......

Page 36: ...s It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 660556 in...

Reviews: