OPERATION: AUTOMATION
TITAN DUAL LEG
OPERATION: AUTOMATION
Your product can be integrated into most control systems using dry contact relays. These instructions are
provided for Automation specialist reference only. Please contact us, or an Automation specialist, before
attempting this change.
TO INTEGRATE:
Unplug and remove the original controller and replace it with a DP1U Controller. This is needed as removing
the original controller will remove any stored Up or Down limits. DP1U is used to set the Up and Down limits in
the main control unit.
SET NEW POSITIONS:
On the DP1U, press the UP arrow to bring to the desired height. Press the DOWN arrow to stop. Press the S
button and within 2 seconds press the 1 button. Memory 1 is now set.
Repeat procedure for other Memory positions.
TO AUTOMATE:
Plug in a standard CAT category LAN cable between the Control unit port A2 and external relays. Use the
pinouts below to activate the desired action. Note: a single relay pulse will cause the lift to travel in the
selected direction until it hits the full stroke length. A second pulse of the same relay will cancel the action.
CONTROL BOX PINOUT:
Function
Pins
Colour (T568A)
Colour (T568B)
Up
4 & 5
Blue & Blue/White
Blue & Blue/White
Down
4 & 8
Blue & Brown
Blue & Brown
Store
2 & 8
Green & Brown
Orange & Brown
Memory 1
3 & 5
Orange/White &
Blue/White
Green/White & Blue/White
Memory 2
3 & 8
Orange/White & Brown
Green/White & Brown
Memory 3
2 & 5
Green & Blue/White
Orange & Blue/White
DPU1 CONTROLLER
STANDARS CAT LAN CABLE