DIGITAL DIFFERENTIAL PRESSURE TRANSMITTER

Copyright

2003.08 ULFA TECHNOLOGY CO.,LTD

http://www.ulfatech.com

4

Function

Setting and Calibration

Zero setting :

Optimize display and current out to

zero automatically by front key pressed.

Peak pressure Measurement :

This mode is

display for peak pressure by supplied pressure. And

the display is cleared by press enter key in the peak

mode.

Offset( p)

pressure

Measurement :

This

mode is display the changed pressure based on the

current pressure. Current pressure is turned into "0"

when offset mode selected. This mode does not

concern to 4-20mA current out put.

Sampling time setting :

Sample rate is 0.1sec of

this product. Sampling time is measuring time by

sample rate. For example, if setting time is 2 sec,

SDT measures 20 times for 2 seconds and out to

display and 4-20mA out put by average of 20 times

measured value.

Transmitter :

SDT has 4-20mA current out put.

Span (20mA) range can be changed within original

range.

Communication(option) :

Measurement

pressure can be sent by RS232 or RS485 for option

specification.

ID setting :

This mode set identification number for

communication.

Over pressure warning :

SDT displays warning

on LCD for over pressure (positive and negative).

Upper 4 elements of segment("

") blink for

― ― ― ―

warning when measurement pressure over 10% for

high pressure(factory setting value), And under 4

elements of segment("_ _ _ _") blink for warning

when measurement pressure under 10% for low

pressure(factory setting value),

Factory setting recovery :

The parameters are

changed all to factory setting value and all user

setting value is cleared.

Hear by describe key function and setting methode.
Please read this section carefully for the correct and
optimum use of this product.

Key functions

UP

- Increase setting value
- Offset mode set/reset

DOWN

- Decrease setting value
- Peak pressure mode set/reset

MODE

- Entering into the setting mode
- Setting item circulation

ENTER

- Save setting value
- Clear peak value in the peak mode
- Release setting mode

Peak mode

Press

the

PEAK(down)

key once to set peak
mode

"PEA" displayed like left
while press peak key

Press

the

ENTER

to

reset

peak

value

and

newly start

Press

the

PEAK(down)

key once more to release
peak mode

Offset mode

Press the

P(UP) key

once to set offset mode

"dELt" displayed like left
while press

P key

Press the

P(UP) key

once

more

to

release

offset mode

P

PEAK

P

PEAK

P

PEAK

P

PEAK

PEAK

P

PEAK

P

PEAK

P

PEAK

P

Summary of Contents for JANITOR SDT Series

Page 1: ...fferential Pressure Transmitter 1 General Specification 2 Installation 3 Wiring 4 Function 5 Setting Calibration Thank you very much for using SDT pressure transmitter Please read this Instruction Manual carefully and throughly for the correct and optimum use of the gauge Kindly keep this Manual in a convenient place for quick reference 4 Digit Display 4 20mA Output ...

Page 2: ...ssure Range Refer to range table ELECTRICAL Power Supply DC24V 100 220VAC 50 60Hz Connections 2 screw terminal block Display 4 Digit LCD Warm up Time 15 minutes TRANSMITTER Connections 2 Screw terminal block Output Signal 4 20mADC limited at 30mADC Loop Resistance 0 1100Ω Zero Span Adj One touch Adjustable on Panel PERFORMANCE AT 23 Range Table Zero Output 4 mA Model No Range Resolution Full Span ...

Page 3: ...re to pressure port POWER CONNECTION The following procedures are to be used to install a standard 24VDC main power source 1 Before connection the user must first confirm that the power specification is DC24V or AC220V 2 Verify that the facility s main power source is turned off or disconnected 3 Connect lead cable to power terminal matching polarity as shown in FIG 2 below Take care that wrong wi...

Page 4: ...n number for communication Over pressure warning SDT displays warning on LCD for over pressure positive and negative Upper 4 elements of segment blink for warning when measurement pressure over 10 for high pressure factory setting value And under 4 elements of segment _ _ _ _ blink for warning when measurement pressure under 10 for low pressure factory setting value Factory setting recovery The pa...

Page 5: ...ling time setting It can be set 0 1 5 0 seconds by 0 1 sec resolution PDT reading pressure 0 1sec interval for a setting time and calculate average pressure to display and 4 20mA output ex setting time 2 sec SDT reading pressure 20 times for 2 seconds and calculate average of measured 20 data to display and 4 20mA current output This functions is useful to measure hunted pressure 4mA current setti...

Page 6: ... zero span etc Press MODE key for more than 3 seconds till appear Int on LCD display Press MODE key once till appear FACt on LCD display Press ENTER key once to recall and exit to measure mode Press ENTER key for more than 3 seconds till appear SAvE on LCD display to recall and exist in the setting mode ID No setting ID number is use for address for communication to master It s concern to SDT comm...

Reviews: