- 28 -
Mode No. Setting of OUT2 preset output
A
※ Not displayed when P1 option is selected
A B C D E
A. 0 0 0 0
Output mode (2-9 : One shot output)
0 : Comparison 5 : 100ms
1 : Hold 6 : 250ms ◆
2 : 30ms 7 : 500ms ◆
3 : 50ms 8 : 1sec.
4 : 80ms 9 : 2sec.
◆It outputs as "one shot output" at rate meter.
It outputs as "offset return" at totalizer.
Upper or lower limit selection
0 : Upper limit
1 : Lower limit (Immediate)
2 : Lower limit (Delay) ! <Caution>
※It's the same from
Output selection which is chosen "1",
0 : Rate meter when "1" is chosen
1 : Totalizer by"output selection".
Disabled time interval
0 : 0sec. 5 : 8sec.
1 : 1sec. 6 : 10sec.
2 : 2sec. 7 : 20sec.
3 : 3sec. 8 : 30sec.
4 : 6sec. 9 : 60sec.
Each setting is the same as that of the mode No. 9
"Setting of OUT1 preset output".
【 Offset return 】
When the indication value exceeds the upper limit (preset value),
this outputs one pulse of the set width one time, and the indication is
returned to the offset value and totaling is resumed.
"Output error : ±2ms"
In case of "the upper limit" does function, but in case of "the lower limit"
doesn't function.
! < Caution >
* The following settings are required .
"Preset value > Offset value"
Always reset before starting count.