  【  Operation  Manual  】   

 

 
 
 

  Compact  digital  meter 

 

 
 
 

    MODEL  :  SP2441  Series     

 
 

(Pulse input type) 

 

Series name 

Output 

Input 

Function 

SP2441 

 

 

 

Sensor  power  :  DC12V  50mA  MAX 
Power  source  :  DC  power  supply(DC24V) 
Preset  output  :  NPN  open  collector(

×

2) 

Input  signal  :  NPN  open  collector(

×

1) 

Color  :  Black 

P1 

 

 

Preset  output  one  points 
  (1c  contact  relay  output) 

AI 

 

  Analog  current  output  (DC4-20mA) 

AV3 

 

  Analog  voltage  output  (DC1-5V) 

AV4 

 

  Analog  voltage  output  (DC0-5V) 

AV5 

 

  Analog  voltage  output  (DC0-10V) 

F    Voltage  pulse  input 

F2    Current  pulse  input 

 

 

 
      !  Caution 
      For  professional  use  only  or  designed  for  use  by  a  licensed  electrician  only. 
 
      !  Caution 
      Check if the label (model name) of the unit and your desired product 
      specification correspond before use. 

 
 

                                                        【  The 3rd edition 21 Aug. 2020  】 
                                                                  @SP2441CE(3)-E 
 

 

Summary of Contents for SP2441 Series

Page 1: ...reset output one points 1c contact relay output AI Analog current output DC4 20mA AV3 Analog voltage output DC1 5V AV4 Analog voltage output DC0 5V AV5 Analog voltage output DC0 10V F Voltage pulse in...

Page 2: ...t to vibration or impact 3 Do not allow metal powder dust water chemicals oil etc to enter the product There is a risk of failure or fire ly for any malfunctions or abnormalities 5 If the product is m...

Page 3: ...ting of Exp value least significant digit the unit time and the decimal point 19 Mode 3 Ratemeter Setting of the sampling time 20 Mode 4 Ratemeter Setting of the moving average range 20 21 Mode 5 Rate...

Page 4: ...Calling up and modifying the offset value setting 34 13 Calling up and modifying the preset value setting 35 14 Adjusting the analog output option 36 37 15 External dimensions 37 16 About a noise coun...

Page 5: ...se that you don t attach by convenience About a guaranteed period and a guaranteed area 1 Guaranteed period The period a product guarantees is 4 years from a delivered day 2 Guaranteed area If we trou...

Page 6: ...at 0 or 0 5 Totalizer Measurement accuracy 0 Scaling is set to 1 Scaling 1 10 9 9999 per pulse Indication area 0 99999 Decimal point 10 1 10 2 10 3 10 4 nothing Overflow Indication 99999 flashing end...

Page 7: ...alue are indicated alternately Data backup Each mode set value and totalized value are saved on FRAM The memory writable number of times is within 100 000 times retention about 10 years Mode protect P...

Page 8: ...the floating input AV3 DC1 5V Load impedance 2k or more AV4 DC0 5V Load impedance 2k or more AV5 DC0 10V Load impedance 2k or more Accuracy Within 0 3 F S for indicated value at 23 Temperature charact...

Page 9: ...ix the body At this time if the body is not secured tightly fasten screws a little more Put the meter on a panel with a thickness of 1 0 4 0mm Fig 3 1 Panel cutout dimensions and pitch for mounting tw...

Page 10: ...4 Connecting terminal boards Terminal boards Fig 4 1 Standard type Fig 4 2 P1 option type Terminal pitch 3 5mm Phoenix SMKDS1 12 3 5 Wire AWG30 16 SQ Conversion 0 05 1 3mm Length of stripped wire 5 0...

Page 11: ...activated to stop the reverse current flow In this case disconnect then reconnect correctly normal operation Caution The input output wiring scheme varies with sensor type Please refer to the connecti...

Page 12: ...8 5 Construction of input output circuit 1 Senser input NPN open collector pulse input Fig 5 1 2 Senser input Voltage pulse input Fig 5 2 3 EXT input NPN open collector input Fig 5 3...

Page 13: ...9 4 Analog output Voltage output AV3 5 Current output AI Fig 5 4 Fig 5 5 5 Preset output Synchronization pulse output NPN open collector output 6 P1 Option relay output Fig 5 6 Fig 5 7...

Page 14: ...ut is selected by setting the dip switch DSW1 1 DSW1 2 OFF ON NPN open collecter pulse input ON Voltage pulse input OFF Input response frequency 0 01Hz 50Hz LOW ON Input response frequency 0 01Hz 10kH...

Page 15: ...ply is supplied while is pushing down Mode Key a test mode functions is called A stop of the test mode function is power supply off Measurement state When Shift Key is pressing for 2 sec or more while...

Page 16: ...Setting state Display Key changes the flash figure when each setting The output bit values increases at the time of analog output adjustment mode setting 5 Reset Key Turning on Throw power supply whi...

Page 17: ...13 8 The setting menu The test mode function Fig 8 Power supply OFF Test mode being pressed Turn power supply on with...

Page 18: ...9 9 9 9 9 9 9 9 9 9 The preset value setting The mode setting 0 0 0 2 0 0 0 0 0 The offset value setting 0 0 F o _ L F n o _ L The mode protect function _ A n 1 n A A Turn power supply on with Adjust...

Page 19: ...on pulse output C Analog output Setting of measurement choice option and the output digit d Analog output Setting of maximum output option indication Presetting output set value Table 9 Preset value I...

Page 20: ...Key is pressed the number goes up by one 0 1 9 0 In situation doesn t indicate by a setting figure up to nine 1 d Changes the value of the mode No Each time Mode Key is pressed the number goes up by o...

Page 21: ...exponential value a minus power of 10 the scaling ratio per pulse can be set The exponential value a minus power of 10 is set in mode No Ex Using a flow meter which emits 1 pulse per 1 234mL the cumul...

Page 22: ...e can be adjusted slightly Ex 2 Revolution Factor 1 revolution 30 pulse 1 30 0 033333 3333 10 5 Mode No 1 Exp value Mode No 2 Sensor Please register 3333 at Mode No 1 and 5 for The number of gear teet...

Page 23: ...form of indication for the least significant digit digit on the right end is selected 0 Real Synchronized at the sampling time 1 Fixed at 0 Always 0 2 0 or 5 0 4 are expressed as 0 and 5 9 as 5 Cauti...

Page 24: ...ving average count is set to 4 at mode No 4 four pulses intervals are averaged and measured When a new next pulse comes in the measurement is repeated to discharge the oldest pulse interval take in th...

Page 25: ...0 5 0 3 Caution Please note that the display response is delayed until it stabilizes because the display sampling time is taken in the set number of times If the data is less than the moving average c...

Page 26: ...ndicated EXT input The function of terminals No 6 7 can be registered selectable 0 Reset Totalizer is made offset value When the presetting output OUT1 2 is output it is released 1 Hold During input o...

Page 27: ...s the same as that of the mode No 1 Mode No Totalizer Setting of Exp value reset dwell time overflow indication and the decimal point Decimal point 0 0 0000 1 0000 0 2 000 00 3 00 000 4 0 0000 Overflo...

Page 28: ...shing Counting from 0 when the total exceeds 99999 the indication flashes Internal totaling is continued To resume totaling from 0 reset 1 5 digits endless Display is continued endlessly When the tota...

Page 29: ...ion pulse output Disabled time interval 0 sec 5 sec 1 sec 6 sec 2 sec 7 sec 3 sec 8 sec 4 sec 9 sec The presetting output compares display value with the preset value and outputs it by the result Refe...

Page 30: ...ode The length of a presetting output is specified 0 Comparison This is output when the indication value exceeds the upper lower limit setting value preset value When the indication value returns to w...

Page 31: ...27 Chart at the timing of the preset output Chart at the timing of the offset return output...

Page 32: ...er when 1 is chosen 1 Totalizer by output selection Disabled time interval 0 0sec 5 8sec 1 1sec 6 10sec 2 2sec 7 20sec 3 3sec 8 30sec 4 6sec 9 60sec Each setting is the same as that of the mode No 9 S...

Page 33: ...2nd digit D 2 3rd digit C 3 4th digit B Output digit The digit whose change is to trigger the pulse output is specified Pulse output width The output width of synchronization pulse is specified Cauti...

Page 34: ...the calculation value Synchronized with the sampling time Selecting between rate total The value to be outputted is selected And the indication value or the calculation value is selected too 0 Rate me...

Page 35: ...hat s compared by at most 5 digits left 4digits by calculation The analog output is outputting to the indication value into which the reach from a least significant digit to the highest rank figure wa...

Page 36: ...cation value E 0 Digit selection Right 4 digits B E Setting of maximum output indication 5000 Caution Even if the indication value goes over the indication value setting of analog maximum output it ou...

Page 37: ...Procedure The mode protect present Press the key for 2 sec or more The present mode protect state is displayed The regular factory setting is L oFF The mode protect change Keep pressing Shift Key for...

Page 38: ...nd the present offset value is displayed Shifts the flashing indication to the digit to the right Each time Shift Key is pressed shifts the indication to one right Changes the value of the flashing di...

Page 39: ...the flashing digit Each time Display Key is pressed the number goes up by one 0 1 9 0 The OUT2 led lights up and the preset value setting for OUT2 is shown Press Shift Key and Dispay Key to set the d...

Page 40: ...he output minimum value of AI AV3 5 When Dispay Key is pressed the bit values increases When Shift Key is pressed the bit values decreases The variable range is 0000 3FFF Measured value After adjustin...

Page 41: ...MAX 5 000V In case of AV5 0 10V In case of AI 4 20mA Items Voltage Adjustment MIN 0 000V Adjustment MAX 10 000V 15 External dimensions External dimensions Fig 15 1 Unit mm Items Voltage Adjustment MIN...

Page 42: ...ise 2 Please avoid a source of noise power supply line and inverter make it as short as possible After that please install a sensor code 3 Please separate from a power supply line in a case affected b...

Page 43: ...em of this meter suitable for the output signal of the sensor Check the setting again Refer to page 17 32 Check the connection of the sensor Refer to page 6 Check with the test mode Refer to page 15 T...

Page 44: ...an Tel 81 72 274 6001 Fax 81 72 274 6005 Tokyo Office Tel 81 3 5256 8311 Fax 81 3 5256 8312 U https www uinics co jp Scan the QR code to access the website Please understand that the specifications of...