F- THINGS THAT MUST BE DONE BEFORE CALLING AUTHORIZED
SERVICE
F- THINGS THAT MUST BE DONE BEFORE CALLING AUTHORIZED
SERVICE
Digital thermostat failures
Alarm signals for Elstat thermostat;
Alarm signals for Dixel thermostat;
Alarm signals for Elstat thermostat;
Alarm signals for Carel thermostat;
Setting the digital thermostat values other than the factory settings are completely under the
user's responsibility. Our company shall not be held responsible for the material and moral losses
that may arise in connection thereto.
Setting the digital thermostat values other than the factory settings are completely under the
user's responsibility. Our company shall not be held responsible for the material and moral losses
that may arise in connection thereto.
MESSAGE REASON
PROCEEDINGS TO BE FOLLOWED
P1
Room sensor failure
Check the sensor connection
P2 sen
Evaporator sensor failure
Check the sensor connection before replacing the sensor.
HA pa-
Maximum temperature alarm
Check compressor operation and relevant parameter values.
LA pa-
Maximum temperature alarm
Check compressor operation and relevant parameter values.
EA
External alarm
Alarm stops automatically when digital entry is deactivated.
MESSAGE REASON
PROCEEDINGS TO BE FOLLOWED
=
Door is open
Check the product's door.
rSF
Cooling system failure
Check compressor operation and relevant parameter values.
PF1
PF2
Sensor failure
Cabinet and condenser
sensor
Check the sensor
Check parameter values.
MESSAGE REASON
PROCEEDINGS TO BE FOLLOWED
EO
Control sensor 1 failure
(Control)
Check the sensor
E1
Control sensor 2 failure
(Defrost)
Check the sensor and d0=0/1/4,F0=1
E2
Control sensor 3 failure
(Condenser)
Check the sensor and whether it is (A4=10)
IA
External alarm
Check external alarm outlets or A4 and A7 parameters.
dOr
Open door alarm
Check that the door is closed or A4 and A7 parameters.
LO
Low temperature alarm
Alarm will be turned-off automatically when the temperature
returns to the set value range. Also check the set value.
HI
High temperature alarm
Alarm will be turned-off automatically when the temperature
returns to the set value range. Also check the set value. Check
whether the cooling system runs properly.
EE/Eer
Unit parameter failure
Check the parameters.
EF
Operating parameter failure
Check dT,dP and d4 parameters; defrost effect. Alarm will be closed
automatically when defrost operation finishes.
ED
Defrost completed out of
its time
dT, dP ve d4 parametrelerini; defrost etkisini kontrol et. Defrost
işlemi normal olarak bittiğinde alarm kapanacaktır.
58
59
Summary of Contents for USS 60 DTKL
Page 92: ...RU RU B B EN23953 2 U ur So utma A 182 183...
Page 95: ...RU RU C 10 10 16 12 11 D 23 1 220 240 50 13 0 1 1 14 15 10 11 12 13 14 15 188 189...
Page 98: ...RU RU E D 18 U ur So utma A 2 U ur 18 194 195...
Page 99: ...RU RU F U ur U ur U ur U ur U ur U ur D 65 196 197...
Page 102: ...AR AR PCT PCB CFC R600a R134a R404a R290 10 U UR SO UTMA A 202 203...
Page 103: ...AR AR 204 205...
Page 104: ...AR AR 1 50 240 220 2 3 1 2 20 24 WEEE EC 2002 96 WEEE 1 2 3 206 207...
Page 105: ...AR AR R290 R600a 208 209...
Page 106: ...AR AR EN23953 2 U ur So utma A 210 211...
Page 107: ...AR AR 4 5 1 6 15 150 7 51 051 1 51 051 2 8 3 25 16 60 4 30 16 55 5 40 16 45 7 4 5 6 8 212 213...
Page 109: ...AR AR 10 61 01 21 11 10 11 12 23 1 13 50 240 220 15 14 1 1 0 13 14 15 216 217...
Page 112: ...AR AR 81 2 81 222 223...
Page 113: ...AR AR 20 65 224 225...
Page 115: ......