INSTALLATION
13
UFO
LIGHTING
CONNECTION
-
FOR
DIRECT
MAINS
OPERATION
(
AC
SUFFIX
MODELS
)
There may up to three connections required via the appropriate gland:
1. The fibre harness.
2. The DMX or 0-10V cables for any light sources with that control functionality
3. Mains supply cable.
The fibre harness should be connected first. Loosen the fibre optic gland in the gland
plate and carefully feed the harness through the gland, insert the common end connector
into the light source aperture and tighten the locking screw to hold it in place. Ensure
the fibre optic connector is fully inserted into the aperture before tightening the gland to
create a seal. Do not overtighten the nylon gland. Never run the luminaire with the fibre
optic harness out of the aperture.
Loosen the gland for the DMX or 0-10V cables and feed the cables carefully through the
gland leaving sufficient slack inside the enclosure to reach the back of the light source.
Tighten the gland and fit RJ45 or XLR connectors to the cables as detailed in the light
source user guide. Plug the cables into the light source.
Loosen the gland for the mains cable and feed the cable carefully through the gland
leaving sufficient slack inside the enclosure to reach the fused terminal block. Prepare
the cable end and wires for connection allowing sufficient bare conductor to enter the
terminal fully.
Connect the incoming wires as follows:
• Green to earth
• Black to Live
• White to Neutral