Uflex Velair i10 VSD SMART Installation And User Manual Download Page 7

7

GEnERAL InFORMATIOn

It contains general information and important warnings 

that should be known before installing and using the ap-

pliance.

Product presentation

It addresses all recipients.

It contains the information to identify the product, its com-

ponents, compatible accessories and destination of use.

Installation

It is addressed exclusively to the installer.

It contains specific warnings and all the information nec

-

essary for positioning, mounting and connecting the ap-

pliance.

Commissioning, maintenance and troubleshooting

They are addressed exclusively to the Technical Assistance 

Centre.

It  contains  specific  warnings  useful  information  for  the 

most common commissioning and routine maintenance.

Technical information

It addresses all recipients.

It contains detailed technical information about the appli-

ance.

1�2    General  warnings

 

Specific warnings are given in each chapter of the docu

-

ment and must be read before starting operations.

 

All personnel involved must be aware of the operations 

and dangers that may arise when beginning all unit in-

stallation operations.

 

Installation performed outside the warnings provided 

in this manual and use of the appliance outside the pre-

scribed temperature limits will invalidate the warranty.

 

The installation and maintenance of climate control 

equipment could be dangerous because there is pres-

surised refrigerant gas and live electrical components 

inside the appliances. The installation, initial start-up 

and subsequent maintenance phases must be carried 

out exclusively by authorised and qualified personnel.

 

Any contractual or extra-contractual liability for damage 

caused to persons, animals or property, due to installa-

tion, adjustment and maintenance errors or improper 

use is excluded. All uses not expressly indicated in this 

manual are not permitted.

 

Only  qualified  installer  companies  are  authorised  to 

install the device. After having completed installation, 

the installer will issue a declaration of conformity to the 

plant manager, as required by the applicable standards 

and the guidelines provided by contractor's instruction 

manual supplied with the device.

 

First start-up and repair or maintenance operations 

must be carried out by the Technical Assistance Centre 

or by qualified personnel following the provisions of this 

manual.

 

Do not modify or tamper with the appliance as this can 

lead to dangerous situations.

 

Use suitable accident-prevention clothing and equip-

ment during installation and/or maintenance opera-

tions. The manufacturer is not liable for the non-ob-

servance of the current safety and accident prevention 

regulations.

 

In the event of liquid or oil leaks, disconnect the power 

supply to the unit and the seawater pump and close 

the water taps.  Call the authorised Technical Assistance 

Centre or professionally qualified personnel as soon as 

possible and do not work on the appliance yourself.

 

In case of replacement of parts, use only original parts.

 

During the cold period, if the unit is not in use, empty 

all hydraulic circuits and the seawater condenser to pre-

vent freezing.

 

The manufacturer reserves the right to make changes 

to its models at any time to improve its product, with-

out prejudice to the essential characteristics described 

in this manual. The manufacturer is not obliged to add 

such  modifications  to  machines  previously  manufac

-

tured, already delivered or under construction.

1�2�1 

 SpecificwarningsforR32

 

This document contains only some of the warn-

ings related to the refrigerant R32. For more com-

prehensive information, carefully read the safety 

data sheet available from the dealer.

 

All precautions concerning the treatment of the refrig-

erant must be observed following the regulations in 

force.

 

The unit uses environmentally friendly R32 refrigerant 

gas, with a Global Warming Potential (GWP) = 675. Do 

not release R32 gas into the atmosphere.

 

R32 refrigerant gas is slightly flammable and odourless.

 

If refrigerant gas escapes, aerate the room abundantly 

and leave. Call the Technical Assistance Service or pro-

fessionally qualified personnel as soon as possible and 

do not intervene on the appliance yourself.

 

When refilling the system after any leakage of R32 re

-

frigerant gas, make sure that no foreign substances 

enter the circuit. The presence of air or other foreign 

substances inside the refrigerant circuit can cause the 

system to increase pressure or rupture and cause inju

-

ries to persons.

 

Avoid proximity to sources of ignition in continuous 

operation (open flames, gas appliances, electric stoves, 

lighted cigarettes, etc.).

 

This  unit  contains  fluorinated  greenhouse  gases  cov

-

ered by the Kyoto Protocol. Maintenance and disposal 

operations must be carried out by qualified personnel 

only.

Summary of Contents for Velair i10 VSD SMART

Page 1: ...EN N420881A Rev 00 11 2022 Self contained unit i10 VSD SMART i16 VSD SMART Installation and user manual Translation of original instructions...

Page 2: ...ed in this manual the product you have purchased will operate without problems giving you optimum room temperatures with minimum energy costs UFLEX S r l Conformity This unit complies with the Europea...

Page 3: ...p 10 3 Installation p 11 3 1 Preliminary warnings p 11 3 2 Reception p 11 3 2 1 Preliminary warnings p 11 3 2 2 Package description p 11 3 3 Dimensions and weights with packaging p 11 3 4 Handling wi...

Page 4: ...ectrical panel p 22 3 16 3 Access to the electrical panel p 22 3 16 4 Connection p 23 3 17 Control Panel p 23 3 17 1 Mounting p 23 4 Control Panel p 25 4 1 Interface p 25 4 1 1 Description p 25 4 1 2...

Page 5: ...e filter cleaning p 28 6 Troubleshooting p 29 6 1 Troubleshooting table p 29 7 Limited warranty p 30 7 1 Installation Validation Commissioning p 30 7 2 Limitations and Exclusions p 30 7 3 Owners respo...

Page 6: ...ite numbers in black marks indicate a se ries of actions to be carried out in sequence A The black letter in white identifies an image when there are several images in the same figure 1 1 2 Pictograms...

Page 7: ...d personnel following the provisions of this manual Do not modify or tamper with the appliance as this can lead to dangerous situations Use suitable accident prevention clothing and equip ment during...

Page 8: ...refrigerant R32 For more com prehensive information carefully read the safety data sheet available from the dealer It is forbidden the use of gas and water pipes for grounding the appliance Smoking i...

Page 9: ...he unit Tampering with removal of or lack of identification plates will not allow for the safe identification of the product by its serial number and therefore invalidates the warranty 2 2 Destination...

Page 10: ...expansion valve 6 4 way valve 7 Air filter 8 Room side heat exchanger 9 Condensate collection tray 6 4 9 5 7 8 3 1 2 2 5 Compatible accessories The choice and installation of accessories must be estab...

Page 11: ...ical shock or fire Failure to apply the indicated rules may cause malfunc tions of the appliances and relieves the manufacturer from any warranty and from any damage caused to per sons animals or prop...

Page 12: ...nal reg ulations Do not turn the packaging upside down Do not stack the appliances Only place the appliance in a horizontal position 3 5 2 Appliance with packaging Store the package in a dry and clean...

Page 13: ...ce must be handled only by qualified per sonnel adequately equipped and with equipment suit able for the weight and dimensions of the appliance Move the unit to a horizontal position Stay clear of the...

Page 14: ...e unit must be chosen with the utmost care to guarantee adequate protection from shocks and consequent damage the supporting surface can bear the weight of the appliance the appliance must be installe...

Page 15: ...rou tine and supplementary maintenance operations 3 12 Positioning 3 12 1 Preliminary warnings The unit must be fixed to the supporting surface Make sure that the supporting surface supports the weig...

Page 16: ...dersized piping determines malfunctions and or loss of heating and cooling performance The connection piping must be suitably supported so as not to bear on the appliance with its weight Flush the pla...

Page 17: ...17 Installation A Water line B Boat 1 Unit 2 Seawater pump 3 Filter 4 Ball valve 5 Inlet flow uphill 6 Output flow B 1 A B A 3 6 2 5 4 1 3 6 2 5 4 B A 1 3 6 2 5 B A 1 3 6 2 5 4 4...

Page 18: ...unpleasant smells into the cabin To avoid this it is appropriate to make a trap for blocking the air When connecting the condensation drain be careful not to squeeze the rubber duct The direct dischar...

Page 19: ...ust or foreign matter that could damage the plant The connection piping must be suitably supported so as not to bear on the appliance with its weight The air ducts must be insulated and well stretched...

Page 20: ...ITH INSULATION FLEXIBLE AIR DUCTING WITH INSULATION NO CHOKED CURVE NO FLEXIBLE AIR HOSE WITHOUT INSULATION NO PLENUM WITHOUT ADAPTER NO AIR GRILL SMALL NO PVC ADAPTER WITHOUT CLAMP NO AIR INTAKE OBST...

Page 21: ...tection against overload and or short circuit It is required connect the device an efficient ground connection Momentary high voltage surges caused by lightning or other causes could damage the applia...

Page 22: ...can be detached during installation To move the electric panel unscrew the 3 fixing screw remove the control panel fix the electric panel in another area Maximum distance of 60 cm in a suitably venti...

Page 23: ...nductance EMC 4 Terminal board 3 2 1 4 To make the connection insert the cables through the rubber seal bring the power cord to the terminal block making the connections refer to the information in th...

Page 24: ...l A Base of the control B Holes for the wall mounting C Screws D Hole for the passage of the electrical connections A D B C B For the remote control wall mounting drill holes in the wall pull the elec...

Page 25: ...20 seconds after the last action the panel bright ness is reduced only the room temperature is seen on the display The maximum brightness is restored to the pressure of any key 4 1 2 Display A Display...

Page 26: ...emperature To set up the temperature operate the keys to decrease or increase the desired value The displayed value change The room temperature set point can range between 16 and 31 C 4 2 4 Automatic...

Page 27: ...et adjustment To adjust the room temperature probe offset from display off press the key for about 5 sec onds Access to the variation menu of the AIR probe offset displayed on the display operate the...

Page 28: ...he following operations and checks and must be carried out by the Technical Service Centre or by qualified personnel 5 2 1 Air intake filter cleaning Cleaning the filter must be carried out after prol...

Page 29: ...If the problem persists call the Technical Service Centre F3 E7 High pressure switch alarm In Cooling operation the alarm may be caused by obstructions in the seawater circuit or a malfun ction of th...

Page 30: ...orised installer All installation application releases should be commis sioned validated and documented In case of OEM installa tions this applies only for the first released representative applicatio...

Page 31: ...31 NOTE...

Page 32: ...Uflex s r l Via Milite Ignoto 8 A 16012 Busalla GE Italia tel 39 0 10 9620 244 239 fax 39 0 10 9620 333 www uflex com service ultraflexgroup it...