background image

IMTX200H-03

www.ueonline.com

WIRING

No special or separate wiring is required for digital communication with HART 

devices since the HART FSK (Frequency Shift Keying) signal is superimposed 

on top of the 4-20 mA output signal. Digital data is sent to and from the field 

device via a HART master while real-time process information is available via 

the 4-20 mA signal.  It is recommended that a high quality twisted pair or 

shielded wire cable be used where extended lengths are required or electrical 

noise may be present.

NOTE

:  The TX200H is reverse bias protected so no damage will result in 

the event of accidental reversal of power leads.

DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING UNIT. ELECTRICAL 
RATINGS STATED IN LITERATURE AND ON THE TRANSMITTER MUST 
NOT BE EXCEEDED. 

WIRE IN ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL 
CODES. THROUGH PROPER INSTALLATION, THE WIRES SHALL BE 
PROTECTED AGAINST MECHANICAL DAMAGE, I.E. BY USE OF A  

 

           CONDUIT.

THE TX200H TRANSMITTER ACCEPTS A SUPPLY VOLTAGE OF 10-36 
VDC  AND  SHALL  NOT  EXCEED  36  VDC.  THE  SUPPLY  VOLTAGE  MUST             
BE ISOLATED FROM MAINS VOLTAGE BY DOUBLE/REINFORCED     

           INSULATION.

EARTH GROUND MUST ALWAYS BE CONNECTED TO THE GREEN WIRE 
TO PROVIDE SHIELDING AND ELECTRICAL SAFETY.

THE TX200H WIRING MUST BE INSTALLED IN A GROUNDED METAL 
CONDUIT OR WITH OTHER SUITABLE SHIELDING IN ORDER TO MEET 
EUROPEAN EMC DIRECTIVE REQUIREMENTS.

ATEX REQuIREMENTS oNLY

THE WIRING TO THE PRESSURE SENSOR MUST ONLY BE CONNECTED 
IN THE SAFE AREA OR BY AN APPROVED TERMINAL BOX CERTIFIED 
TO EN 60079-0:2012, EN 60079-1:2007, EN 60079-31:2009 FOR       

HAZARDOUS LOCATIONS.

EXTERNAL GROUNDING SCREW (OPTION M460) IS REQUIRED FOR 
NON-METALLIC CONDUIT SYSTEMS (SEE FIGURE 1).

A 1/2” NPT (male) or M20 conduit connection is provided on the top of the 

transmitter with 18 AWG, 72” length lead-wires. An external grounding screw 

and clamp is provided when selecting option M460 (see figure 1). The lead-

wires are color coded as follows:

Red: +signal
Black: - signal
Green: Earth ground

Bench operation:

To operate the TX200H on the bench, it must be connected to a power supply 

and a load resistor (see Figure 2). The HART master (e.g., handheld com-

municator) may also be connected directly across the red and black wires at 

the TX200H.  A voltmeter across the 250 Ω resistor can be used to measure 

the current in the loop ( Iloop = Vresistor / 250 ).  At 4mA the voltmeter will 

read 1 volt and at 20 mA the meter will read 5 volts.

Field operation:

The TX200H can be connected to any HART compatible input card or module 

or any standard 4-20mA input if the HART interface is not being used.  In 

most cases the power supply and the load resistor are built into the input 
card or module (see Figure 3).

Power Supply/Load Limits:

For general operation of the TX200H while using HART the series loop resis-

tance should be between 230 to 600 ohms and the power supply voltage 

should be 24V nominal.

The TX200H can be operated without the HART interface within the operating 

limits of the power supply and loop resistance as shown in Figure 4.

Fault Currents:

Under normal operating conditions the analog output signal of the TX200H 

will remain between 4-20mA.   In the event that the pressure goes beyond 

the operating range of the device or in a fault condition, the TX200H will indi-

cate the condition on the 4-20mA loop as follows:

Loop Current 

Description

3.7 mA   

Check Sum Error

3.9 mA   

Low Limit of Output Range

22.0 mA   

Upper Limit of Output Range

24 mA 

 

Fault Current

Figure 1

Figure 2

 

Power Supply 

 

TX200H 

HART Master or  

Hand Held  

Calibrator 

Red 

Black 

250 Ω

 

Voltmeter 

HART master/ 

handheld 

communicator

Figure 3

Input Card/

Module

TX200H

Red

Black

Green

Loop 

Resis

tance (max.)

Power Supply Voltage

Figure 4

Summary of Contents for TX200H

Page 1: ...m prod_approval PROOF PRESSURE LIMITS STATED IN THE LITERATURE AND ON THE TRANSMITTER HOUSING MUST NEVER BE EXCEEDED EVEN BY SURGES IN THE SYSTEM OCCASIONAL OPERATION OF UNIT TX200H HART Pressure Transmitter UP TO MAXIMUM PRESSURE IS ACCEPTABLE E G START UP TESTING CONTINUOUS OPERATION SHOULD NOT EXCEED THE DESIGNATED OVER RANGE PRESSURE Proof Pressure The maximum pressure to which a pressure sens...

Page 2: ...ed on the top of the transmitter with 18 AWG 72 length lead wires An external grounding screw and clamp is provided when selecting option M460 see figure 1 The lead wires are color coded as follows Red signal Black signal Green Earth ground Bench Operation To operate the TX200H on the bench it must be connected to a power supply and a load resistor see Figure 2 The HART master e g handheld com mun...

Page 3: ... the HART interface Basic Detailed Setup Features Include 1 Device Tag The device tag identifies where the device will be placed into service A replacement device can be programmed to have the same tag as the device it is replacing prior to installation 2 Process Variable Units Allows the user to select the units of mea sure e g wc Hg psi mbar bar kg cm2 kPa MPa 3 Process Variable Limits Allows th...

Page 4: ...0 0 G LM6 Autoclave male 15 16 1 32 33 5 H G 1 4 male 15 16 1 03 26 2 J G 1 2 male 1 3 8 1 78 45 2 Code Range 03 0 to 15 psis 04 0 to 30 psis 05 0 to 50 psis 06 0 to 100 psis 07 0 to 250 psis 08 0 to 500 psis 09 0 to 1000 psis 17 0 to 1500 psis 18 0 to 2000 psis 10 0 to 2500 psis 19 0 to 3000 psis 11 0 to 5000 psis 20 0 to 6000 psis 12 0 to 7500 psis 13 0 to 10 000 psis 14 0 to 15 000 psis 15 0 to...

Page 5: ...Write Message 18 Write Tag Descriptor Date 19 Write Final Assembly Number 20 Read Long Tag 21 Read Unique Identifier Associated with Long Tag 22 Write Long Tag 38 Reset Configuration Changed Flag 48 Read Additional Device Status Command Number Common Practice Commands Command Function 33 Read Device Variables 34 Write Primary Variable Damping Value 35 Write Primary Variable Range Values 36 Set Pri...

Page 6: ...town Massachusetts INCOTERMS provided however that this warranty applies only to equipment found to be so defective within a period of 36 months from the date of manufacture by the Seller Seller shall not be obligated under this warranty for alleged defects which examination discloses are due to tampering misuse neglect improper storage and in any case where products are disassembled by anyone oth...

Reviews: