NOTE: 

 Do not replace the One Series display module or pres-

sure sensor.  Swapping these amongst devices will cause a 

mis-match between the stored sensor calibration data and the 

pressure sensor.  For proper operation, the display module 

serial number must always match the serial number inside the 

enclosure (see Figure 18).

These serial numbers must match for proper operation.

DISPLAY MODULE CALIBRATION

SETTING THE SCALE

The 4-20 mA output is field scalable.  The default setting is 100% of the sensor’s maximum range, where 4 mA represents minimum and 20 mA 

is maximum range.  If desired, both the 4 mA and 20 mA levels may be set independently to shrink or stretch the portion of the sensor’s range 

represented by the 4-20 mA output.

•  Setting the 4 mA portion of the scale (see Figure 17): 

•  Enter the Programming Mode (see page 10) and use the left 

2

 button to move to the 4MA SET command.

•  Press the right 

g

 button to select a positive or negative scale.  POS is the default.  Use the left 

2

 button to change to NEG.

•  Press the right 

g

 button to view and change the scale.  Press the left 

2

 button to increment the blinking digit. Press the right 

g

       

button to enter and move to the next digit.  This process value must be between -3% and 25% of the sensor’s maximum range.

•  Press the right 

g

 button to enter the new scale and return to the main menu.

•  Setting the 20 mA portion of the scale (see Figure 17):

•  Enter the Programming Mode (see page 10) and use the left 

2

 button to move the 20MA SET command.

•  Press the right 

g

 button to select a positive or negative scale.  POS is the default.  Use the left 

2

 button to change to NEG.

•  Press the right 

g

 button to view and change the scale.  Press the left 

2

 button to increment the blinking digit.  Press the right 

g

 

button to enter and move to the next digit.  This process value must be between 50% and 110% of the sensor’s maximum range.

•  Press the right 

g

 button to enter the new scale and return to the main menu.

NOTE:

 Scaling the 4-20 mA output over a smaller portion of the sensor’s range does not the increase the accuracy of the proportional output.  A 

2:1 turndown is possible using these commands.

Sensor Range

-3 to 25%

50 to 110%

4MA

20MA

0%

100%

Figure 17

Figure 18

Summary of Contents for Field Safety System One Series

Page 1: ...HAZARDOUS AND THE FOLLOWING HAZARDOUS LOCATIONS AND IS ATEX AND IECEX CERTIFIED SUITABLE FOR APPROPRIATE USE IN GAS AND DUST ZONE 1 APPLICATIONS Model 2SLP N America Europe International Flameproof Ce...

Page 2: ...eries transmitter switch product line is based on an all solid state electronic module that incorporates a microprocessor The One Series Field Safety System is a loop powered all in one device connect...

Page 3: ...y pushing the right g button once the display will scroll as follows SP1 XX XX DB1 XX XX SP2 XX XX DB2 XX XX By pushing the left 2 button once the display will scroll the min max process values record...

Page 4: ...re that the sensor housing will not be damaged and where the measured temperature is representative of the surrounding environment For Local Spring Loaded model T A suitable thermowell made from corro...

Page 5: ...ved Tools Required Small flat head screwdriver wire strippers TO PREVENT IGNITION DISCONNECT POWER BEFORE REMOVING ENCLOSURE COVER KEEP COVER TIGHT WHILE IN OPERATION DO NOT DISCONNECT EQUIPMENT UNLES...

Page 6: ...diagnostics to determine the integrity of the SRO wiring and if the SRO is functioning properly NOTE As an alternative to loop power model 2SLP may be wired directly to a 24 VDC power supply and minus...

Page 7: ...t function as normal NOTE The 4 20 mA analog signal is not possible in this wiring configuration In this configuration the 4 20 mA output and IAW Output are monitored by the safety system logic solver...

Page 8: ...Field Safety System fully configured where the health status IAW and SRO switch status signals are being monitored by a logic solver PLC or DCS These connections are not required however UE recommend...

Page 9: ...00 0 39 714 3 1045 5 40 761 9 1090 9 No Fault Displayed 4 20 mA Normal Operating range Unused Fault 3 6 3 8 mA Normal Under range 4 20 20 5 mA Normal Over range 21 0 mA 21 0 mA only when the temperatu...

Page 10: ...t 2 button increments the blinking digit The right g button sets the digit and moves to the next Once a valid password is entered OK will appear on the display Press and release the right g button CLR...

Page 11: ...opens on falling process values that reach the set point OPEN WINDOW The Safety Relay Output opens when process values are within a specified range set by two points set point high and set point low P...

Page 12: ...6 Resetting the Maximum Minimum Values The One Series Field Safety System continuously records the readings from the sensor and stores the minimum and maximum MAX MIN peak hold values in non volatile...

Page 13: ...and change the offset Zero is the factory setting Press the left 2 button to increment the blink ing digit Press the right g button to enter and move to the next digit Press the right g button to ente...

Page 14: ...ity to detect that the process port may be plugged It does this by monitoring the sensor for changes over time The amount of change and the time period are programmable If the process variable does no...

Page 15: ...ations it is desirable to dampen the Safety Relay Output response and prevent intermittent false trips due to pressure spikes or other transient isolated events The Filter feature provides a software...

Page 16: ...left 2 button to change to NEG Press the right g button to view and change the scale Press the left 2 button to increment the blinking digit Press the right g button to enter and move to the next digi...

Page 17: ...en check all sensor connections E 16 Diagnostic Fault Sensor SHORT A short circuit has been detected on the sensor drive pins 2 3 Diagnostic Fault Sensor Short check all sensor connections E 18 Diagno...

Page 18: ...ORIGINAL DATE DRWN CHKD APPD DO NOT SCALE THIS DRAWING DOC DE733010102 Rev B EM ONE SERIES 1X NAMEPLATE A 6211 847 SR 5 14 15 6211 847 DESCRIPTION DATE DRWN APPD UNLESS OTHERWISE SPECIFIED DIMENSIONS...

Page 19: ...end on sensor range Invalid PWORD BOTH Abort NO RESET OK Flash Err Abort BDOOR PWORD Valid SAVING SAVING One Series Field Safety System LCH1 ON OFF OFST POS NEG 8888 Set Blinking Digit Increments Blin...

Page 20: ...R PORT 1 2 14 NPT SENSOR PORT 1 20 NPT SENSOR PORT 1 20 NPT SENSOR PORT 111 92 mm 76 2 mm 133 35 mm 12 7 mm SURFACE MOUNTING KIT 6361 704 144 78 mm 134 62 mm 137 16 mm 154 94 mm 134 62 mm 137 16 mm 26...

Page 21: ...LATED CABLE 0 125 3 18 mm FOR DC UNITS 0 250 6 35 mm 1 2 NPT COMPRESSION FITTING 300 SERIES st st 26 AWG STRANDED TEFLON INSULATION 4 50 114 3 mm FIXED DIM EPOXY SEAL 2 00 50 8 mm FIXED DIM 1 2 14 NPT...

Page 22: ...e de fil lectrique Ne pas monter l unit des temp ratures ambiantes d passant les limites publi es Cela est particuli rement important pour les unit s de tem p rature montage locale L utilisation enve...

Page 23: ...avant de retirer le couvercle du bo tier Maintenir le couvercle ferm pendant le fonctionnement Ne pas d con necter l quipement que lorsque l alimentation est coup e ou que la zone est connue pour tre...

Page 24: ...r personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit accord ing to local and national elect...

Reviews: